5725848-XIM-A-0319

Johnson Controls Ducted Systems

17

Minimum Position and the Economizer Minimum Position Low 
Speed Fan" set points, in relationship to the VFD output 
percentage. On a constant volume single speed supply fan 
system both set-points should be set to the same value. 

Free cooling

Four types of free cooling options are available: dry bulb 
changeover, single enthalpy, dual enthalpy changeover, and 
Auto.

Dry bulb changeover

For dry bulb economizer operation, the outside air is suitable for 
free cooling if the outside air temperature is 1°F below the 
Economizer OAT Enable Setpoint 

and

 1°F below the Return Air 

Temperature.

Free cooling is no longer available if the outside air temperature 
rises above 

either

 the Economizer OAT Enable setpoint 

or

 the 

return air temperature.

Single enthalpy changeover

For single enthalpy economizer operation, the outside air is 
suitable for free cooling if the outside air enthalpy is at least 1 
BTU/lb below the Economizer Outside Air Enthalpy Setpoint 

and

 the outside air temperature is no greater than the RAT plus 

9°F.

If the outside air temperature rises above the RAT plus 10°F, 
free cooling is no longer available. The outside air temperature 
must drop to no greater than RAT plus 9°F to enter free cooling 
again.

Free cooling is no longer available if the outside air enthalpy 
rises above the Economizer Outside Air Enthalpy Setpoint.

Dual enthalpy changeover

For dual enthalpy economizer operation, the outside air 
enthalpy must be lower than the return air enthalpy by 1 btu/lb 
AND the outside air temperature is no greater than the RAT 
plus 9°F.

Auto

The control determines the type of free cooling changeover 
based on which sensors are present and reliable. Conditions 
include:

• Return and outside air dry bulb = dry bulb changeover
• Return and outside air dry bulb and outside air humidity = 

single enthalpy

• Return and outside air dry bulb and return and outside air 

humidity = dual enthalpy

• If either the return or outside air dry bulb sensors are 

unreliable, free cooling is not available

Free cooling operation

When the control determines that the outside air is suitable, the 
first stage of cooling will always be free cooling.

Thermostat

In free cooling, with a thermostat input to Y1, the dampers 
modulate to control the supply air temperature to the 
Economizer Se/- 1°F (default 55°F).

If the thermostat provides an input to Y2 

and

 the parameter 

Compressors Off in Free Cooling is turned OFF a compressor 
output energizes. The economizer dampers continue to 
modulate to control the supply air temperature to the 
Economizer Setpoint.

If the supply air temperature cannot be maintained within 50F of 
the economizer setpoint, the first stage compressor (C1) will be 
turned on. Second stage compressor (C2) will be added as 
needed to keep the supply air temperature within the 50F of the 
economizer setpoint.

Sensor

In free cooling, with a demand from the zone/return sensor for 
the first stage of cooling, the dampers modulate to control the 
supply air temperature to the Economizer Se/- 1°F.

If the economizer output is at 100% 

and

 the SAT is greater than 

the Economizer se 1°F, the control starts a 12-minute 
timer to energize a compressor output.

If at any time the economizer output drops below 100% the 
timer stops and resets when the economizer output returns to 
100%.

Once a compressor output is turned ON, the economizer 
dampers continue to modulate to control the supply air 
temperature to the Economizer Setpoint.

At no time will a compressor output be turned ON if the 
economizer output is less than 100%, even if the differential 
between zone (or return) temperature and the current cooling 
setpoint is great enough to demand more than one stage of 
cooling.

If the economizer output goes to minimum position 

and

 the SAT 

is less than Economizer Setpoint -1°F, the control starts a 12-
minute timer to de-energize a compressor output.

If at any time the economizer output goes above the minimum 
position the timer stops and resets when the economizer output 
returns to minimum position.

If the demand for cooling from the space/return is satisfied, the 
economizer output will modulate to minimum position and the 
compressor outputs will be de-energized as long as their 
minimum run timers have expired.

Содержание ZF076

Страница 1: ...Burner air shutter adjustment 43 Checking gas input 43 Adjustment of temperature rise 44 Troubleshooting 45 Cooling troubleshooting guide 45 Gas heat troubleshooting guide 46 Flash code troubleshooti...

Страница 2: ...od 30 18 Unit dimensions rear view 31 19 Disconnect blower access location 31 20 Belt adjustment 36 21 Pressure drop across coil 37 22 Gas valve piping 40 23 Proper flame adjustment 43 24 Typical valv...

Страница 3: ...parts and electrical components installation and servicing of air conditioning equipment can be hazardous Only qualified trained ser vice personnel should install repair maintain or service this equi...

Страница 4: ...es refrigerant containers and recovery systems must be designed to handle R 410A If you are unsure consult the equipment manufacturer Failure to use R 410A compatible servicing equipment may result in...

Страница 5: ...mbustible material 4 For use with natural gas convertible to LP with kit This product must be installed in strict compliance with the enclosed installation instructions and any applicable local state...

Страница 6: ...d Filters Merv 8 4 Coil Guard CG STD Filter 5 2 Pleated Filter CG A Std Cabinet B HDF HingedFLTR Tooless DR E SSD SST Drain Pan F SSD HFD A No Economizer C Economizer w o Barometric RLF F Econ BAS Rdy...

Страница 7: ...al Code CSA C22 1 2 Installation Codes CSA B149 1 3 Local plumbing and waste water codes and 4 Other applicable local codes Refer to unit application data found in this document After installation gas...

Страница 8: ...air in accordance with section 5 3 of Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 Latest Edition in U S A or Sections 7 2 7 3 or 7 4 of Gas Installation Codes CSA B149...

Страница 9: ...f the evaporator coil and must be kept clean or replaced with same size and type Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown Minimum filter a...

Страница 10: ...2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 1 4 3 1 2 4 Second stage ot required on single stage he g units Jumper is required if there is n...

Страница 11: ...tolerances which must be maintained at the compressor terminals during starting and running OCC C RC G Y2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THER...

Страница 12: ...led heaters are wired for single point power supply Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper...

Страница 13: ...3 50 M3 S 0 47 0 57 0 57 0 61 CFM 1100 1200 1200 1300 4 380 415 3 50 M3 S 0 61 0 61 0 61 0 61 CFM 1300 1300 1300 1300 5 380 415 3 50 M3 S 0 75 0 75 0 75 0 75 0 75 CFM 1600 1600 1600 1600 1600 6 3 380...

Страница 14: ...uitable for the purpose NEVER USE A FLAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at te...

Страница 15: ...od slips in under the top of the access panel opening when installing Refer to Vent and Combustion Air Hood Figure 7 The vent hood is installed by inserting the top flange of the hood into the slotted...

Страница 16: ...EDs at the center left of the RRS Economizer Controller indicate POWER green Lit whenever 24 volts AC power is present to the RRS Economizer Controller C and R pins FAULT red Lit then flashes during t...

Страница 17: ...t available Free cooling operation When the control determines that the outside air is suitable the first stage of cooling will always be free cooling Thermostat In free cooling with a thermostat inpu...

Страница 18: ...No inputs are present for non modulating power exhaust Outputs a 2 10 VDC from ECON on Economizer Expansion module b 24 vac from EX FAN to energize exhaust fan on Economizer Expansion module Operation...

Страница 19: ...istor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Страница 20: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Страница 21: ...negative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HO...

Страница 22: ...pad layout Keypad The four navigation buttons illustrated in Fig 8 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the ke...

Страница 23: ...E Economizer Module accessory instruction P N 1150208 UAI A 0514 included in this instruction packet for additional menu information Economizer setup and configuration Before being placed into service...

Страница 24: ...ry the economizer sets the economizing mode to YES economizing is available When conditions are above the selected boundary the conditions are not good to economize and the mode is set to NO Fig 9 sho...

Страница 25: ...LEFT FRONT Table 8 ZF036 076 metric Size Tons Model Weight kg Center of Gravity mm 4 point Load Location kg 6 point Load Location kg Shipping Operating X Y A B C D A B C D E F 036 3 0 ZF036 228 225 10...

Страница 26: ...F 15 45 25 70 25 55 25 55 Gas Limit Setting F Direct Drive 240 210 Gas Limit Setting F Belt Drive 210 210 Gas piping connecting in 1 2 1 2 1 2 1 2 DIMENSIONS inches Length 82 1 4 82 1 4 82 1 4 82 1 4...

Страница 27: ...VAP FAN DATA Quantity 1 1 Fan Size Inch 12 x 10 12 x 11 Type Centrifugal Centrifugal Motor Sheave 1VL44 IVM50 Blower Sheave AK54 AK56 Belt A35 A36 Motor HP each 1 1 2 1 1 2 RPM 1450 1450 Frame size 56...

Страница 28: ...3 25 2EH04512046 12 2 2 18 5 29 4 30 415 3 50 7 8 51 5 12 1 1 3 4 24 NONE 15 3 20 2EH04510746 5 1 1 7 1 15 3 20 2EH04511046 7 5 1 10 4 19 2 20 2EH04511546 10 2 2 14 2 23 9 25 2EH04512046 14 6 2 20 3 3...

Страница 29: ...as heat front view 829 325 8 1140 447 8 64 21 2 213 83 8 292 111 2 445 171 2 445 171 2 181 77 8 171 63 4 206 81 8 137 53 8 2089 821 4 165 61 2 178 7 111 43 8 165 61 2 819 321 4 819 32 1 4 mm inch 829...

Страница 30: ...omizer rain hood Figure 17 Unit with fixed outdoor air motorized damper rain hood DETAIL A 699 271 2 699 271 2 41 15 8 260 101 4 1140 447 8 502 193 4 mm inch DETAIL B 454 177 8 184 71 4 699 271 2 485...

Страница 31: ...th Belt Drive Option Control Box Access A B Wiring Entry See Detail B Mounting Bracket for Disconnect Switch Field Supplied Field Supplied Disconnect Switch Location Blower Motor Access Filter Access...

Страница 32: ...25 LOW 0 67 645 0 63 620 0 58 595 0 53 575 CFM UNIT TONNAGE MOTOR SPEED AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS 31 HI 1699 825...

Страница 33: ...25 1101 980 1130 1045 1158 1075 CFM UNIT TONNAGE AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM...

Страница 34: ...75 1118 1150 1148 1250 1176 1360 CFM UNIT TONNAGE AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM...

Страница 35: ...id bases and are inherently protected These motors can be selected to operate into their service factor because they are located in the moving air upstream of any heating device Table 20 Static resist...

Страница 36: ...4 Knowing the pressure drop across a dry coil the actual volumetric flow rate through the unit can be determined from the curve in Pressure Drop vs Supply Air flow rate Figure 21 After readings have b...

Страница 37: ...the fan off delay for cooling To be available a compressor must not be locked out due to a high or low pressure switch or freezestat trip Simplicity Lite Control or Evaporator Low Limit sensor detecti...

Страница 38: ...ser fan If the call for cooling is still present at the conclusion of the ASCD the UCB will re energize the halted compressor Should a freezestat open three times within two hours of operation the UCB...

Страница 39: ...and on any compressor reset or lock out Flash codes or error messages The UCB will initiate flash a code on the Simplicity Lite Control see Table 26 or sent error message to the LCD Smart Equipment Co...

Страница 40: ...peration of the draft motor The UCB continues the operation of the indoor blower for a configurable amount of time after the call for heat is satisfied Two stage furnace only If a W1 only call for hea...

Страница 41: ...of the main gas valve will shut off the flow of gas to both the pilot and main gas valves Centrifugal switch The centrifugal switch is mounted on the end of the draft motor and it is an integral part...

Страница 42: ...installed Operating instructions Lighting the pilot and main burners 1 Turn off electric power to unit 2 Turn room thermostat to lowest setting 3 Turn gas valve knob to on position 4 Turn on electric...

Страница 43: ...unction properly Burner instructions To check or change burners pilot or orifices CLOSE MAIN MANUAL SHUT OFF VALVE AND SHUT OFF ALL ELECTRIC POWER TO THE UNIT 1 Remove the screws holding either end of...

Страница 44: ...e readings of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat Increase the blower Volumetric Flow Rate to decrease t...

Страница 45: ...terminal is connected to the G terminal of the UCB and for loose wiring 10 If the thermostat and UCB are properly wired replace the UCB On a call for cooling the supply air blower motor is operating b...

Страница 46: ...1 ECON terminal 13 For units with economizers If 24 volts is present at the Y1 OUT terminal check for 24 volts at the Y1 ECON terminal If 24 volts is not present check for loose wiring from the Y1 OUT...

Страница 47: ...e ICB LED If it now flashes the heartbeat then the fault was a bad connection between the harness connector and the ICB connector or a broken wire exists in the harness With the harness connected to t...

Страница 48: ...manual reset type If either one opens then the ICB removes power to the gas valve and the UCB energizes the indoor blower until the primary limit automatically resets or the auxiliary limit is manuall...

Страница 49: ...e the motor 6 If 24 volts is not present at M2 check that 24 volts is present at the supply air blower motor terminal on the UCB If 24 volts is present at the UCB terminal check for loose wiring betwe...

Страница 50: ...es for obstruction and alignment Removal procedure is described in BURNER INSTRUCTIONS on page 43 Clean or replace burner orifices and burners as needed Unit flash codes Various flash codes are utiliz...

Страница 51: ...Operation 1 Flash Not Applicable 2 Flashes Control waiting ASCD1 1 These flash codes do not represent alarms 3 Flashes HPS1 Compressor Lock out 5 Flashes LPS1 Compressor Lock out 7 Flashes FS1 Compres...

Страница 52: ...the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in serie...

Страница 53: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Страница 54: ...reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for rehe...

Страница 55: ...ut for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permis...

Страница 56: ...er of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Страница 57: ...indicates the UCB is supplying power to the communication sub board 1 When wiring unit and other devices using the SA Bus and FC Bus see Table 29 Table 28 Smart Equipment UCB details continued Descri...

Страница 58: ...5848 XIM A 0319 58 Johnson Controls Ducted Systems Typical wiring diagrams Simplicity Lite control board Figure 28 Typical ZF036 048 with Simplicity Lite control with without electric heat wiring diag...

Страница 59: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 59 Figure 29 Typical ZF036 048 with Simplicity Lite control with gas heat wiring diagram...

Страница 60: ...5725848 XIM A 0319 60 Johnson Controls Ducted Systems Figure 30 Typical ZF060 076 with Simplicity Lite control with without electric heat wiring diagram...

Страница 61: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 61 Figure 31 Typical ZF060 076 with Simplicity Lite control with gas heat wiring diagram...

Страница 62: ...5725848 XIM A 0319 62 Johnson Controls Ducted Systems Smart Equipment Figure 32 Typical ZF036 048 with Smart Equipment control with without electric heat wiring diagram...

Страница 63: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 63 Figure 33 Typical ZF036 048 with Smart Equipment control with gas heat wiring diagram...

Страница 64: ...5725848 XIM A 0319 64 Johnson Controls Ducted Systems Figure 34 Typical ZF060 076 with Smart Equipment control with without electric heat wiring diagram...

Страница 65: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 65 Figure 35 Typical ZF060 076 with Smart Equipment control with gas heat wiring diagram...

Страница 66: ...LDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HTX...

Страница 67: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Страница 68: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Страница 69: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Страница 70: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Страница 71: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Отзывы: