SECTION 6 - OPERATION
FORM 201.30-ICOM1 (519)
ISSUE DATE: 05/22/2019
6
PROGRAM ◄DEF 0.0% LO 0.0% HI 100.0%
HPC SHUTDOWN POSITION = XX.X
With service level password access, navigate to the
following setup parameters and set them properly to
maintain approximately 1 in. coverage above the top of
the condenser subcooler in accordance with the refrig-
erant charge level description in
in this manual.
For instructions to access these setpoints, service
technicians may refer to the
YVWA Service Manual
(Form 201.30-M1).
Default Values
A listing of the low and high limits, and default pro-
grammable values is noted in each display and can be
found in
. The English units are
exact values while the metric units are approximate.
Unit "SETUP MODE" will allow the programming all
of the programmable values that the user should never
change. These will either be programmed at the factory
or by service personnel on the job. This mode may be
entered by pressing the PROGRAM key, entering the
password "4245", and pressing
(ENTER) key.
PROGRAM HPC DIRECTION
◄► XXXXXXXXXXXXXXXXXXXXXXXXXXXX
PROGRAM ◄DEF 0.0% LO 0.0% HI 100.0%
HPC MINIMUM POSITION = XX.X
TABLE 38 -
PROGRAM LIMITS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
Chilled Liquid Leaving Temperature Cutout
Water
Cooling
–
–
36.0°F
–
–
2.2°C
Glycol
Cooling
5.0°F
36.0°F
36.0°F
15.0°C
2.2°C
2.2°C
Motor Current Limit
–
30% FLA
100% FLA
100% FLA
Pulldown Motor Current Limit
–
30% FLA
100% FLA
100% FLA
Pulldown Motor Current Limit Time
–
0 Min
255 Min
0 Min
Motor Temperature Unload
–
150.0°F
250.0°F
240.0°F
65.6°C
121.1°C
115.6°C
Sys 1 Condenser Level Control Setpoint
20.0%
80.0%
33.0%
Sys 2 Condenser Level Control Setpoint
(Not displayed on tandem circuit units)
20.0%
80.0%
33.0%
Unit ID Number
–
0
7
0
Head Pressure Control
--
DISABLED
ENABLED
DISABLED
Head Pressure Setpoint
HPC Enabled
"25.0 PSID
(1.72 BARD)"
"35.0 PSID
(2.41 BARD)"
"28 PSID
(1.93 BARD)"
HPC Kp
HPC Enabled
0.1
50.0
5.0
HPC Ti
HPC Enabled
10 Sec
1000 Sec
50 Sec
HPC Td
HPC Enabled
0 Sec
60 Sec
0 Sec
HPC Direction
HPC Enabled
DIRECT
REVERSE
DIRECT
HPC Minimum Position
HPC Enabled
0.0%
100.0%
0.0%
HPC Shutdown Position
HPC Enabled
0.0%
100.0%
0.0%
Содержание YVWA
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 64: ...JOHNSON CONTROLS 64 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 82: ...JOHNSON CONTROLS 82 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 146: ...JOHNSON CONTROLS 146 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 152: ...JOHNSON CONTROLS 152 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 155: ...JOHNSON CONTROLS 155 NOTES...