JOHNSON CONTROLS
131
FORM 201.30-ICOM1 (519)
ISSUE DATE: 05/22/2019
7
SECTION 7 - MAINTENANCE
GENERAL REQUIREMENTS
The maintenance requirements for YVWA chillers are
shown below. The procedure is in the left-hand column
and the required frequency is marked with an
X
in the
right-hand column. Refer to the notes at the bottom of
the table to maintain warranty validation.
TABLE 43 -
OPERATION/INSPECTION /MAINTENANCE REQUIREMENTS FOR YVWA CHILLERS
PROCEDURE
DAILY
WEEKLY
MONTHLY
ANNUALLY
Record operating conditions (on applicable log form)
X
Check oil level in oil level sight glass
X
Check refrigerant levels
X
Check oil return system operation
X
Check operation of motor starter
X
Check oil heater operation
X
Check 3-phase voltage and current balance
X
Check programmable operating setpoints and safety
cutouts. Make sure they are correct for the application.
X
Verify condenser and evaporator liquid flows
X
Check and repair leaks as needed¹
X
Check and tighten all electrical connections
X
Check
the motor windings resistance
X
Clean or back flush VSD heat exchanger
X
¹
Replace VSD coolant (after cleaning heat exchanger)
X
Perform oil analysis on compressor lube oil
X
¹
Perform refrigerant analysis
X
Perform Eddy current testing and inspect tubes
X²
Clean evaporator and condenser tubes
X²
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact a local Johnson Controls Field
Service Office.
¹ This procedure must be performed at the specified time interval by an industry certified technician, who has been trained and qualified to
work on this type of YORK equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment
owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
² More frequent service may be required, depending on local operating conditions or relaxed with good engineering controls (water quality).
Compressor vibration analysis is not prescribed. Due
to the compressor design, a typical vibration analysis
can be misleading.
Periodic oil filter changes are not recommended.
Change the oil, filter, and filter driers only when an oil
analysis indicates a moisture issue.
Содержание YVWA
Страница 14: ...JOHNSON CONTROLS 14 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 64: ...JOHNSON CONTROLS 64 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 82: ...JOHNSON CONTROLS 82 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 146: ...JOHNSON CONTROLS 146 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 152: ...JOHNSON CONTROLS 152 FORM 201 30 ICOM1 519 ISSUE DATE 05 22 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 155: ...JOHNSON CONTROLS 155 NOTES...