![York YMAA 0045 Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/york/ymaa-0045/ymaa-0045_installation-manual_4255008076.webp)
FORM NO.:6U6K-B01E-NB-EN
JOHNSON CONTROLS
76
TABLE 24 -
GRAVITY CENTER OF STANDARD UNIT
Note
Co-ordinates measured from geometric center of the unit.
TABLE 25 -
GRAVITY CENTER OF UNIT WITH HYDRO
KIT
Note
1.Co-ordinates measured from geometric center of the unit
(excluding Hydro Kit);
2.The units with fixed speed pump have the same dimensions
and weight distributions as base models.
ISOLATORS – WEIGHT DISTRIBUTION AND ISOLATOR MOUNTING POSITIONS
GENERAL
Weights of specific unit models vary significantly as options are
added. As a result, total weights, weights at individual isolator
positions, and actual isolator selection at each position cannot
be published due to the vast number of possible combinations.
This information will be available when the specific unit/ option
selection is made from the local Johnson Controls sales office.
Be aware, weights may change with each option along with
possible isolator changes. Weights and isolators may need to be
recalculated when the option selections are changed.
Whenever the isolator option is ordered, the isolators will be
shipped loose with the unit. Packed with the unit is a mass
distribution label indicates the loads specifically for each unit,
based on the option selection. The label will be similar to the
ones shown below. The label will show the isolator locations
along with the weight in kilograms at the specific location,
isolator position, and location measurements for each isolator.
CENTER OF GRAVITY
SECTION 5 – TECHNICAL DATA
YMAA/YMPA
Without Hydro Kit
Gravity Center (mm)
x
y
z
0045
-1.1
-20.6
-104.3
0065
7.1
-2.1
-126.2
0080
33.1
-25.3
-98.5
00100
40.6
-27.7
-115.8
00130
3.6
-46.8
-142.2
0160
5.4
-71.6
-139.1
0200
-11.2
-112.9
-132
0230
-2.8
34.5
-147.1
0260
-11.4
-4.2
-148.8
YMAA/YMPA
With Hydro Kit
Gravity Center (mm)
x
y
z
0045
236.3
-30.4
-368.9
0065
222.2
-12.8
-376.2
0080
253.6
-20.7
-221.9
00100
248.5
-23.6
-325.4
00130
218.4
-43.4
-302.9
0160
10.6
-65.5
-134.6
0200
-4.3
-102.9
-129.6
0230
8.1
32.7
-160
0260
-0.2
-3.2
-161.2
Note
X-axis is in parallel with liquid outler direction.
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz