1.2.5 Parameters relating to the compressor
Parameters relating to the compressor
Display
Description
Level
VS
Unit
Max.
Min.
Value
c01
Minimum operating time
U
25 (R/W)
Seconds
999
0
120
c02
Minimum stoppage time
U
26 (R/W)
Seconds
999
0
60
c03
Time between start-ups of one compressor
U
27 (R/W)
Seconds
999
0
300
c04
Time between start-ups of two compressors
U
28 (R/W)
Seconds
999
0
3
c05
Time between stoppage of two compressors
U
29 (R/W)
Seconds
999
0
3
c06
Start-up timing
U
30 (R/W)
Seconds
999
0
10
c07
Compressor start-up delay with regard to the pump
U
31 (R/W)
Seconds
150
0
20
c08
Pump stoppage delay with regard to the compressor
U
32 (R/W)
Minutes
150
0
1
c10
Operating hour counter for compressor 1
D
90 (R)
Hours
800
0
-
c11
Operating hour counter for compressor 2
D
91 (R)
Hours
800
0
-
c14
Operating hour counter for compressor maintenance
U
34 (R/W)
Hours
100
0
0
c15
Operating hour counter for pump
D
94 (R/W)
Hours
800
0
-
c17
Minimum time between pump start-ups
U
35 (R/W)
Minutes
150
0
5
c18
Minimum operating time for pump
U
36 (R/W)
Minutes
15
0
2
User manual
1
Operating instructions µC2 (YLHA 50, 60 and 80)
1.2
13