Parameters relating to defrost
Parameters relating to defrost
Parameters
Description
Level
VS
Unit
Max.
Min.
Value
d01
Defrost operation:
0= Absent (function not available
1= Present
U
7 (R/W)
-
1
0
1
d02
Defrost at time or temperature:
0= Time (function not available)
1= Temperature / Pressure
U
8 (R/W)
-
1
0
1
d03
Defrost start temp
U
19 (R/W)
°C
d04
-40/
-3
Defrost start pressure
bar
11
6,2
d04
Defrost end temp
U
21 (R/W)
°C
80/
d03
20
Defrost end pressure
bar
12
14,4
d05
Minimum defrost start time
U
37 (R/W)
Seconds
150
10
10
d06
Minimum defrost duration
U
38 (R/W)
Seconds
150
0
0
d07
Maximum defrost duration
U
39 (R/W)
Minutes
15
1
6
d08
Time between two defrost cycles
U
40 (R/W)
Minutes
150
10
30
d11
Activation of heaters during defrost:
0= No
1= Yes
U
9 (R/W)
-
0
1
1
d12
Compressor stoppage before defrost
F
43 (R/W)
Minutes
3
0
1
d13
Compressor stoppage after defrost
F
44 (R/W)
Minutes
3
0
1
d16
Forced ventilation time at defrost end (if F13=2
only)
F
47 (R/W)
Seconds
360
0
60
A
Defrost end temperature
(d04)
E
Minimum defrost start
time (d05)
B
Defrost start
F
Timer start
C
Defrost end
G
Defrost start tempera‐
ture (d03)
D
Maximum defrost dura‐
tion (d06)
A
B
C
D
E
F
G
Technical Information
1
Operating instructions 1.13
57