Parameters relating to fans
Parameters relating to fans
Display
Description
Level
VS
Unit
Max.
Min.
Value
F01
Fan outlet:
0= Absent (function not available
1= Present
F
10 (R/W)
1
0
1
F02
Operating mode:
0=Always ON (function not available)
1= parallel to the compressor (function not
available)
2=ON/OFF operation (function not availa‐
ble)
3= parallel to the compressor and speed
adjustment
U
48 (R/W)
3
0
3
F03
Minimum Triac voltage
F
49 (R/W)
step
F04
0
35
F04
Maximum Triac voltage
F
50 (R/W)
step
100
F03
85
F05
Minimum speed temp, cool cycle
F
24 (R/W)
°C
80
-40
30
Minimum speed pressure, cool cycle (1)
bar
22,2
F06
Maximum speed temp differential, cool cy‐
cle
F
26 (R/W)
°C
50
0
15
Maximum speed pressure differential, cool
cycle (1)
bar
3,7
F07
Fan stoppage temp differential, cool cycle
F
28 (R/W)
°C
50
0
10
Fan stoppage pressure differential, cool cy‐
cle (1)
bar
6,5
F08
Minimum speed temp, heat cycle
F
30 (R/W)
°C
80
-40
6
F09
Maximum speed differential, heat cycle
F
32 (R/W)
°C
50
0
3
F10
Fan stoppage temp differential, heat cycle
F
34 (R/W)
°C
F08
0
6
F11
Fan start-up time
F
51 (R/W)
Seconds
120
0
10
F12
Triac impulse duration
F
52 (R/W)
Seconds
10
0
2
F13
Fan management in defrost mode:
0= fan disabled
1= fan enabled in cool cycle mode (function
not available).
2= fan disabled until the defrost end tem‐
perature is reached and with top-speed
start-up during d16
F
53 (R/W)
2
0
2
F14
Fan operating when starting with high am‐
bient temperature
U
91 (R/W)
Seconds
999
0
30
(1) Parameters to be checked when pressure probes are to be used (low ambient accessory) YLCA 5 to 15.
A
Fan speed
B
Condensing temperature
C
Evaporation temperature
A
A
C
B
1
Technical Information
1.13 Operating instructions
56