SECTION 7 – UNIT CONTROLS
This MUST be programmed correctly to
assure proper chiller operation.
N U
M
B E R
O F F A
N S
P E R S Y S T E
M = X
The Number of Fans Per System must be programmed
as needed to match the number of fans on each system.
S Y S X T R I P V O L T S
= X . X V O L T S
U N I T T R I P V O L T S
= X . X V O L T S
F A N D I F F E R E N T I A L O F F
P R E S S U R E = X X X P S I G
The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the
condenser fans OFF, in relation to discharge pressure.
See
Standard Condenser Fan Control on page 154
in
.
T O T A L N U M B E R O F
C O M P R E S S O R S = 6
The TOTAL NUMBER OF COMPRESSORS is the
total quantity of compressors in the chiller, and deter-
mines the stages of cooling available. Note in
, the chiller may have single or dual systems. Single
system units can have 2 or 3 compressors, while dual
system units may have 4 or 6 compressors.
TABLE 13 -
PROGRAM KEY LIMITS AND DEFAULT
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
325 PSIG
575 PSIG
570 PSIG
22.4 BARG
39.6 BARG
39.3 BARG
SUCTION PRESSURE CUTOUT
WATER COOLING
80.0 PSIG
120.0 PSIG
80.0 PSIG
5.52 BARG
8.27 BARG
5.52 BARG
GLYCOL COOLING
42.0 PSIG
70.0 PSIG
44.0 PSIG
2.9 BARG
4.83 BARG
3.03 BARG
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0 °F
60.0 °F
25.0 °F
-3.9 °C
15.6 °C
-3.9 °C
LOW AMBIENT
0 °F
60.0 °F
25.0 °F
-17.8 °C
15.6 °C
-3.9 °C
LEAVING CHILLED LIQUID
TEMP. CUTOUT
WATER COOLING
—
—
36 °F
2.2 °C
GLYCOL COOLING
-1.0 °F
36.0 °F
36.0 °F
-18.3 °C
2.2 °C
2.2 °C
ANTI-RECYCLE TIMER
—
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON PRESSURE
—
360 PSIG
485 PSIG
385 PSIG
24.8 BARG
33.4 BARG
26.5 BARG
FAN DIFFERENTIAL OFF PRESSURE
—
80 PSID
160 PSID*
125 PSID
5.51 BARD
11.03 BARD*
8.62 BARD
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
DUAL SYSTEM
4
6
6
NUMBER OF FANS PER SYSTEM
—
2
4
3
UNIT/SYSTEM TRIP VOLTS
CURRENT FEEDBACK
0.5 Volts
4.5 Volts
2.5 Volts
REMOTE UNIT ID
—
0
7
0
* The minimum discharge pressure allowed is 235 PSIG. The Fan Differential Off Pressure High Limit will be lowered (reduced) to prevent
going below 235 PSIG based on where the fan control On Pressure is programmed.
Содержание YLAA Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...JOHNSON CONTROLS 106 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...JOHNSON CONTROLS 148 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 172: ...JOHNSON CONTROLS 172 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...