JOHNSON CONTROLS
166
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
SECTION 9 – SERVICE AND TROUBLESHOOTING
TABLE 30 -
ENTERING/LEAVING CHILLED LIQUID
TEMP. SENSOR, TEMPERATURE/
VOLTAGE CORRELATION
TEMP °F
VOLTAGE
(SIGNAL INPUT
TO RETURN)
TEMP °C
10
1.33
-12
12
1.39
-11
14
1.46
-10
16
1.51
-9
18
1.58
-8
20
1.65
-7
22
1.71
-6
24
1.78
-4
26
1.85
-3
28
1.91
-2
30
1.98
-1
32
2.05
0
34
2.12
1
36
2.19
2
38
2.26
3
40
2.33
4
42
2.40
6
44
2.47
7
46
2.53
8
48
2.60
9
50
2.65
10
52
2.73
11
54
2.80
12
56
2.86
13
58
2.92
14
60
2.98
16
62
3.05
17
64
3.11
18
66
3.17
19
68
3.23
20
70
3.29
21
72
3.34
22
74
3.39
23
76
3.45
24
78
3.5
26
80
3.54
27
Liquid and Refrigerant Sensor Test Points
Entering Chilled Liquid Sensor
J6-5 = +5VDC regulated supply to sensor.
J6-8 = VDC input signal to the I/O board. See
for voltage readings that cor-
respond to specific liquid temperatures.
J6-2 = drain (shield connection = 0VDC) Return
Leaving Chilled Liquid Temperature Sensor
J6-4 = +5VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See
for voltage readings that cor-
respond to specific liquid temperatures.
J6-1 = drain (shield connection = 0VDC) return
Analog Inputs – Pressure
See the unit wiring diagram. Pressure inputs are con-
nected to the microboard on plugs J7 and J9. These an-
alog inputs represent varying DC signals correspond-
ing to varying pressures. All voltages are in reference
to the unit case (ground).
System 1 discharge and suction pressures will be con-
nected to J7 of the microboard. System 2 discharge and
suction pressure transducers will be connected to J9 of
the microboard.
The discharge transducers are optional on all units. If
the discharge transducers are not installed, no connec-
tions are made to the microboard and the discharge
pressure readout on the display would be zero.
The suction pressure transducers are standard on all
YLAA’s. The suction pressure transducers have a
range of 0 to 400 PSIG. The output will be linear from
0.5VDC to 4.5VDC over the 400 PSIG (27.5 barg)
range.
The discharge transducers have a range from 0 to
650 PSIG. The output will be linear from 0.5VDC to
4.5VDC over the 600 PSIG (41.25 barg) range. Fol-
lowing is the formula that can be used to verify the
voltage output of the transducer. All voltage reading
are in reference to ground (unit case).
Содержание YLAA Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...JOHNSON CONTROLS 106 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...JOHNSON CONTROLS 148 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 172: ...JOHNSON CONTROLS 172 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...