JOHNSON CONTROLS
133
SECTION 7 – UNIT CONTROLS
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
7
C U R R E N T F E E D B A C K
O N E P E R S Y S T E M
This mode should be selected when an optional 2ACE
module is installed to allow individual current moni-
toring of each system. SYS 1 input is to J7 of the I/O.
SYS 2 input is to J8 of the I/O.
Option 12 – Power Fail Restart
P O W E R F A I L R E S T A R T
A
U T O
M
A T I C
Chiller auto restarts after a power failure.
P O W E R F A I L R E S T A R T
M
A
N
U
A L
After a power failure, the UNIT switch must be tog-
gled before restart at the unit is allowed. NORMALLY
MANUAL RESTART should NOT BE SELECTED.
Option 13 – Soft Start Enable/Disable
S O F T S T A R T
D I S A B L E D
SOFT START “DISABLED” MUST be selected on all
chillers.
This message may not be viewable on non-European
chillers.
Option 14 – Unit Type
U N I T T Y P E
L I Q U I D C H I L L E R
The UNIT TYPE message cannot be modified under
the unit keys.
“Liquid CHILLER” must be displayed, or
damage to compressors or other compo-
nents will occur if operated in the HEAT
PUMP or CONDENSING UNIT modes.
If unit type needs to be changed to make the unit a
liquid chiller, remove power and then remove the
jumper between J11-7 and J11-12 on the I/O Board.
Reapply power to the
micro panel
and the
micropro-
cessor
will store the change.
Option 9 – Condenser Fan Control Mode
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Condenser fans are controlled by discharge pressure
only. This mode must be chosen.
or
F A N C O N T R O L
A M B I E N T & D S C H P R E S S
Do not select this option on R-410A chillers.
Option 10 – Manual Override Mode
M A N U A L O V E R R I D E M O D E
D I S A
B L E D
This option allows overriding of the daily schedule
that is programmed. MANUAL OVERRIDE MODE –
DISABLED indicates that override mode has no effect.
or
M A N U A L O V E R R I D E M O D E
E N
A
B L E D
Manual Override Mode is enabled. This is a service
function and when enabled, will allow the unit to start
when shut down on the daily schedule. It will auto-
matically be disabled after 30 minutes.
Option 11 – Current Feedback Options
Installed
C U R R E N T F E E D B A C K
N
O
N
E
This mode should be selected when the panel is not
equipped with current sensing capability.
or
C U R R E N T F E E D B A C K
O N E P E R U N I T
This mode should be selected when an optional 2ACE
Module is installed to allow combined current moni-
toring of all systems by sensing current on the incom-
ing line.
or
Содержание YLAA Series
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 30: ...JOHNSON CONTROLS 30 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 106: ...JOHNSON CONTROLS 106 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...JOHNSON CONTROLS 148 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 172: ...JOHNSON CONTROLS 172 FORM 150 72 ICOM6 ISSUE DATE 12 29 2017 THIS PAGE INTENTIONALLY LEFT BLANK ...