TABLE 5 -
MOTOR VOLTAGE VARIATIONS
FREQ.
RATED
VOLTAGE
NAMEPLATE
VOLTAGE*
OPERATING VOLTAGE
MIN.
MAXIMUM
60 HZ
200
200/208
180
220
230
220/240
208
254
380
380
342
415
416
416
375
457
460
440/460/480
414
508
575
575/600
520
635
2300
2300
2070
2530
3300
3300
2970
3630
4000
4000/4160
3600
4576
50 HZ
346
346
311
381
380
380/400
342
423
415
415
374
440
3300
3300
2970
3630
*For motor voltage above 4160V/60Hz and 3300V/50HZ, contact your JCI Sales Office for a specific selection.
MOTOR ELECTRICAL DATA
The smallest motor available which equals or exceeds the Input power (kW) from the
chiller rating program is selected from
Table 9 on page 60 to Table 12 on page 62
The full load amperes (FLA) listed in the tables is maximum values and corresponds to
the maximum motor kW listed. When the input power (kW) is less than maximum motor
kW, the FLA should be reduced per the following equation:
FLA =
Motor kW x Maximum Motor FLA
Maximum Motor kW
The benefit from the FLA correction is the possible use of smaller power wiring and/or
starter size. The locked rotor amperes (LRA) are read directly from
for
specific Motor Code and voltage.
This is because the LRA is dependent only on motor size and voltage and is independent
of input power (kW). Inrush amperes (IRA) depend on LRA and the type of starter applied.
The inrush can be calculated using a percentage of LRA shown in
Application Data (Cont'd)
Содержание YK
Страница 4: ...JOHNSON CONTROLS FORM 160 75 EG1 519 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...JOHNSON CONTROLS FORM 160 75 EG1 519 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 59: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 59 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 83: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 83 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 91: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 91 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 113 THIS PAGE INTENTIONALLY LEFT BLANK...