JOHNSON CONTROLS

 FORM 160.75-EG1 (519)

60

Application Data (Cont'd)

TABLE 9

 - 60 HZ ELECTRICAL DATA (CONT'D)

MOTOR CODE

CF

CG

CH

CJ

CK

CL

CM

CN

CP

CR

CS

CT

CU

CV

CW

MOTOR CODE

CX

CY

CZ

CA

CB

DA

DB

DC

DD

DE

DF

DH

DJ

DK

DL

SHAFT HP (MAX)

154

177

201

237

270

302

327

351

385

424

468

503

554

608

655

SHAFT HP (MAX)

690

740

790

845

900

1000

1100

1200 1300 1400 1500 1750 2000 2250 2500

INPUT KW (MAX)

123

140

161

190

214

240

257

276

302

333

367

395

435

477

514

INPUT KW (MAX)

542

578

618

660

703

781

859

937

1015 1093

1171

1359 1554 1748 1942

F.L. EFF. - % 

1

93.6

94.5

93.3

93

94

94

95

95

95

95

95

95

95

95

95

F.L. EFF. - % 

1

95

95.5

95.3

95.5

95.5

95.5

95.5

95.5

95.5

95.5

95.5

96

96

96

96

F.L. POWER 

FACTOR 

1

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.86

0.87

0.87

0.87

0.87

0.87

0.87

F.L. POWER 

FACTOR 

1

0.87

0.88

0.88

0.89

0.89

0.87

0.87

0.87

0.88

0.88

0.88

0.87

0.89

0.89

0.89

VOLTS

AMPERES (MAXIMUM)

VOLTS

AMPERES (MAXIMUM)

200

FLA

405

465

527

618

707

787

831

921

1014 1085 1208

-

-

-

-

200

FLA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

LRA

2598

3111

3111

3810 4550 4900 5470 5780 5780 7350 7794

-

-

-

-

LRA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

208

FLA

389

447

507

594

680

757

799

886

975

1043

1162

-

-

-

-

208

FLA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

LRA

2702 3235 3235 3962 4732 5096 5689

6011

6011

7644 8106

-

-

-

-

LRA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

230

FLA

352

404

464

540

610

685

749

804

882

944

1050

1130

-

-

-

230

FLA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

LRA

2598 2598 2865 3460 3788 4260 4755 5162 5780 5780 6900 7400

-

-

-

LRA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

240

FLA

337

387

445

518

585

656

718

771

845

905

1006 1083

-

-

-

240

FLA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

LRA

2711

2711

3120 3610 3953 4445 4962 5386 6031 6031 7200 7722

-

-

-

LRA

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

380

FLA

217

249

285

336

378

421

453

487

534

571

636

684

756

817

879

380

FLA

942

997

1065

1126

1200 1364 1500 1636

-

-

-

-

-

-

-

LRA

1385 1385 1730 2153 2500 2577 2955 3254 3637 3810 4179 4480 4671 5326 5780

LRA

5780 5780 6644 7610 7513 7794 8491 9431

-

-

-

-

-

-

-

416

FLA

199

228

260

307

346

385

412

445

488

522

581

625

691

747

810

416

FLA

860

911

973

1029 1096 1246 1370 1495

-

-

-

-

-

-

-

LRA

1385 1385 1638 1967 2190 2356 2700 2976 3536 3637 3810 3810 4270 4869 5640

LRA

5670 5694 6069 6900 6863 7120 7755 8618

-

-

-

-

-

-

-

440

FLA

184

211

238

281

319

358

392

397

461

493

549

591

646

706

759

440

FLA

813

861

920

973

1036

1178

1295 1413

-

-

-

-

-

-

-

LRA

1177

1301 1320 1655 1865 2037 2485 2485 2976 2976 3300 3644 3644 4209 4783

LRA

5357 4783 5249 5791 5529 6160 6709 7455

-

-

-

-

-

-

-

460

FLA

176

202

228

269

305

342

375

380

441

472

525

565

618

675

726

460

FLA

778

824

880

931

991

1127

1239 1352

-

-

-

-

-

-

-

LRA

1230 1360 1380 1730 1950 2130 2598 2598

3111

3111

3450 3500 3810 4400 4880

LRA

4960 5280 5330 6054 5780 6440 7014 7794

-

-

-

-

-

-

-

480

FLA

169

194

219

258

292

328

359

364

423

452

503

541

592

647

696

480

FLA

746

790

843

892

950

1080

1187

1296

-

-

-

-

-

-

-

LRA

1283 1419 1440 1805 2035 2223

2711

2711

3246 3246 3600 3976 3976 4591 5217

LRA

5843 5217 5727 6317 6031 6720 7319 8133

-

-

-

-

-

-

-

575

FLA

141

162

185

216

250

274

300

318

353

377

420

452

500

540

581

575

FLA

622

659

704

744

793

901

991

1081

-

-

-

-

-

-

-

LRA

909

909

1100

1384 1556 1700 1900 2066 2078 2413 2760 2960 3089 3550 4039

LRA

4100 4200 4200 5225 4963 5148 5610 6232

-

-

-

-

-

-

-

600

FLA

135

155

177

207

240

263

288

305

338

361

403

433

479

518

557

600

FLA

596

632

675

713

760

863

950

1036

-

-

-

-

-

-

-

LRA

949

949

1148

1444 1624 1774 1983 2156 2168 2518 2880 3089 3223 3704 4215

LRA

4633 4487 4383 5452 5179 5372 5854 6503

-

-

-

-

-

-

-

2300

FLA

36

41.1

46

55

63

70

73.9

80

87

95

106

113

124

135

146

2300

FLA

154

165

176

186

198

225

248

267

290

312

334

383

438

493

548

LRA

240

267

298

340

397

435

480

520

543

590

669

719

791

867

935

LRA

960

1008

1100

1172

1230 1350 1592 1592 1882 2031 2171 2390 2879 3199 3356

3300

FLA

25.5

29

33

39

44

49

52

55.3

61

67

72.8

79

86.1

94.4

102

3300

FLA

108

115

123

130

138

157

173

186

202

217

233

267

306

344

382

LRA

160

175

210

240

280

310

310

343

382

415

466

501

551

576

652

LRA

682

719

744

819

858

942

1110

1110

1311

1416 1514 1661

2011

2388 2479

4000

FLA

21

24

26.7

32

36

40

42.5

46

50.1

55

60.1

65.2

71

77.9

84

4000

FLA

88.6

94.8

101

107

114

130

143

154

166

179

192

220

252

283

315

LRA

135

154

166

195

230

240

270

283

315

340

384

413

455

499

538

LRA

540

554

631

674

713

780

923

923

1077

1177

1246 1428 1669 1842 2047

4160

FLA

20.2

23

25.7

30.8

34.6

38.5

40.9

44.2

48.2

52.9

57.8

62.7

68.3

74.9

80.8

4160

FLA

85.2

91.1

97.1

102

110

125

137

148

160

172

185

212

242

273

303

LRA

140

160

173

203

239

250

270

294

328

328

399

430

473

519

560

LRA

562

576

656

701

742

811

960

960

1120

1224 1296 1485 1736 1772 1968

TABLE 10 - 

50 HZ ELECTRICAL DATA

TABLE 10

 - 50 HZ ELECTRICAL DATA (CONT'D)

MOTOR CODE

5CC 5CD 5CE 5CF 5CG 5CH 5CI

5CJ 5CK 5CL 5CM 5CN 5CO 5CP 5CQ 5CR 5CS

MOTOR CODE

5CT 5CU 5CV 5CW 5CX 5DA 5DB 5DC 5DD 5DE 5DF 5DG 5DH 5DJ

2

5DK 5DL

SHAFT HP (MAX)

148

168

198

225

252

272

292

321

353

390

419

462

507

546

575

617

658

SHAFT HP (MAX)

704

750

800

850

900

1000 1100 1200 1300 1400 1500 1650 1750 2000 2250 2500

INPUT KW (MAX)

119

135

158

179

201

215

231

254

279

309

332

363

398

429

451

484

516

INPUT KW (MAX)

553

589

628

667

706

785

863

942

1015 1093 1171 1288 1359 1554 1748 1942

F.L. EFF. - % 

1

93

93

93.4 93.7 93.7 94.2 94.2 94.2 94.2 94.2 94.2

95

95

95

95

95

95

F.L. EFF. - % 

1

95

95

95

95

95

95

95

95

95.5

95.5

95.5

95.5

96

96

96

96

F.L. POWER 

FACTOR 

1

0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.88

F.L. POWER 

FACTOR 

1

0.88

0.89

0.89

0.89

0.89

0.88

0.87

0.88

0.88

0.88

0.88

0.88

0.89

0.89

0.89

0.89

VOLTS

AMPERES (MAXIMUM)

VOLTS

AMPERES (MAXIMUM)

346

FLA

230

261

306

347

389

418

448

493

536

592

636

696

763

822

866

929

979

346

FLA

1048 1104 1177 1251 1325 1488 1656

-

-

-

-

-

-

-

-

-

LRA

1385 1721 1790 2208 2467 2598 2840 3081 3350 3706 3810 4177 4830 4944 5373 5780 5780

LRA

6615 6931 7356 7794 8319 8559 9346

-

-

-

-

-

-

-

-

-

380

FLA

210

238

278

316

354

380

408

449

488

539

579

633

695

748

788

846

892

380

FLA

954

1005 1072 1139 1206 1355 1508

-

-

-

-

-

-

-

-

-

LRA

1385 1385 1640 1890 2144 2464 2590 2806 3050 3375 3700 3810 4400 4500 4892 5600 5491

LRA

5491 6313 6694 7113 7404 7794 8511

-

-

-

-

-

-

-

-

-

400

FLA

200

226

264

300

336

361

388

427

464

512

550

601

660

711

749

804

847

400

FLA

906

955

1018 1082 1146 1287 1433

-

-

-

-

-

-

-

-

-

LRA

1458 1458 1726 1990 2257 2594 2726 2954 3211 3533 3895 4011 4632 4737 5149 5895 5780

LRA

5780 6645 7046 7487 7794 8204 8959

-

-

-

-

-

-

-

-

-

415

FLA

192

218

255

290

324

348

374

411

447

494

530

580

636

685

722

774

817

415

FLA

874

920

982

1043 1104 1241 1381

-

-

-

-

-

-

-

-

-

LRA

1283 1385 1490 1700 2031 2175 2366 2569 2794 3088 3402 3478 3810 4117 4480 5130 5108

LRA

5512 5780 6131 6513 6938 7138 7794

-

-

-

-

-

-

-

-

-

3300

FLA

24.1 27.4 32.2 36.4 40.8 43.8

47

51.7 56.2 62.1 66.7 72.9

80

86.2 90.8 97.4 103

3300

FLA

110

116

123

131

139

156

174

187

202

217

233

256

267

306

344

382

LRA

159

162

209

236

241

274

294

318

317

388

423

455

499

516

572

614

644

LRA

693

725

744

819

875

871

1135 1135 1135 1415 1415 1415 1667 1836 2233 2481

NOTES:

  

1. High voltage and special motor designs may not meet efficiency, power factor or amperes values shown for standard motors.

2. Min. reduced voltage tap 80%.

TABLE 9 -  

60 HZ ELECTRICAL DATA

Содержание YK

Страница 1: ...FORM 160 75 EG1 519 MODEL YK CENTRIFUGAL LIQUID CHILLER STYLE G 250 through 3000 ton 879 through 10 500 kW Utilizing R 134a or R 513A...

Страница 2: ...D STANDARDS on page 17 for approvals Nomenclature COMPRESSOR CODE YK ED ER Q7 ES G S MOTOR CODE POWER SUPPLY for 60Hz 5 for 50Hz DESIGN LEVEL CONDENSER CODE EVAPORATOR CODE UNIT TYPE YORK YK Centrifug...

Страница 3: ...NSON CONTROLS 3 Table Of Contents INTRODUCTION 5 EQUIPMENT OVERVIEW 9 OPTIVIEW CONTROL CENTER 19 ACCESSORIES AND MODIFICATIONS 27 APPLICATION DATA 39 DIMENSIONS 74 WEIGHTS 97 GUIDE SPECIFICATIONS 99 S...

Страница 4: ...JOHNSON CONTROLS FORM 160 75 EG1 519 4 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...gned to operate on a continuous basis with cold ECWT and full condenser flow at all load points taking full advantage of Real World conditions This type of operation benefits the cooling tower as well...

Страница 6: ...on of AHRI Standard 550 590 I P Under this Certification Program chillers are regularly tested in strict compliance with this Standard This provides an independent third party verification of chiller...

Страница 7: ...are approved to UL Standard 1995 for listing by a qualified nationally recognized testing laboratory for the United States and Canada Recognition of safety and reliability is your assurance of troubl...

Страница 8: ...ely generated by use of the computer This information is important to an owner s operating budget As a result part load information has now been standardized within the AHRI Certification Program in t...

Страница 9: ...erformance The insert type journal and thrust bearings are fabricated of aluminum alloy and are precision bored and axially grooved The specially engineered single helical gears with crowned teeth are...

Страница 10: ...iron adaptor mounted on the compressor This unique design allows the motor to be rigidly coupled to the compressor to provide factory alignment of motor and compressor shafts Motor drive shaft is dire...

Страница 11: ...iminator on R_ thru Z_ shells located above the tube bundle to prevent liquid re frigerant carryover into the compressor A 1 1 2 38 mm liquid level sight glass is conveniently located on the side of t...

Страница 12: ...its major components Panel verbiage is available in eight languages and can be changed on the fly without having to turn off the chiller Data can be displayed in either English or Metric units Smart F...

Страница 13: ...a color coded message to indicate severity red for safety fault orange for cycling faults yellow for warnings and green for normal messages E Safety shutdowns enunciated through the display and the st...

Страница 14: ...inverter heat sink temp 5 VSD high converter heat sink temperature TM model drive only 6 Harmonic filter high heat sink temperature 7 Harmonic filter high total demand distortion G Cycling shutdowns e...

Страница 15: ...SD invalid current scale selection 11 VSD low phase A B C inverter heat sink temp 12 VSD low converter heat sink temperature 13 VSD precharge low DC bus voltage 14 VSD logic board processor 15 VSD run...

Страница 16: ...rent protected power for all controls N A numbered terminal strip for all required field interlock wiring O An RS 232 port to output all system operating data shutdown cycling message and a record of...

Страница 17: ...s REFRIGERANT CONTAINMENT The standard unit has been designed as a complete and compact factory packaged chill er As such it has minimum joints from which refrigerant can leak The entire assembly has...

Страница 18: ...JOHNSON CONTROLS FORM 160 75 EG1 519 18 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 19: ...soft keys are redefined with one keystroke based on the screen displayed at the time The graphic display presents several operat ing parameters at once In addition the operator can view a graphical re...

Страница 20: ...w protocol allows increased remote control of the chiller as well as 24 hour performance monitoring via a remote site In addition compatibility is maintained with the present network of BAS communicat...

Страница 21: ...een Animation of the evaporation process indicates whether the chiller is presently in a RUN condition bubbling Liquid flow in the pipes is indicated by alternating shades of color moving in and out o...

Страница 22: ...VGD and the Power Panel LD26781 HOT GAS BYPASS SCREEN This screen displays a cutaway view of the Hot Gas Bypass Valve The setpoints relating to the Hot Gas Bypass Control are maintained on this scree...

Страница 23: ...een from the COMPRESSOR screen and the screen displays the basic stall position and pressure details LD27309 HISTORY SCREEN This screen allows the user to browse through the faults In order to get a m...

Страница 24: ...own time period control over four hours and verification of time re maining in pulldown cycle from the display readout It displays a separate digital setpoint for current limiting between 30 and 100 L...

Страница 25: ...meters having to do with the operation of the chiller LD27306 MOTOR DETAILS This screen displays information pertinent to the Motor Temperature Monitoring feature The feature consists of motor winding...

Страница 26: ...ecording the cause of any shutdowns Safety Cycling or Normal The condition of the chiller is displayed at the System Status line that contains a message describing the operating state of the chiller w...

Страница 27: ...tallations and multiple chiller installa tions In multiple chiller installations cycling chillers off as the building load falls will result in higher loads on the remaining chillers This would seem t...

Страница 28: ...ired The displacement power factor is 0 98 or better when the optional har monic filter is provided Additionally variable speed drives have the following advantages Lowest chiller life cycle through p...

Страница 29: ...t Feature can be used with a UPS supplied by others or without a UPS In order to start the most quickly the OptiView control panel and VSD control circuit except the trigger board must be on a UPS If...

Страница 30: ...d bearings Standard features include a lockable door interlocked disconnect switch UL listed ground fault protection over voltage and under voltage protection 3 phase sensing motor over current protec...

Страница 31: ...sensing overloads phase rotation and single phase failure protection high tem perature safety protection motor current imbalance and under voltage safeties open and shorted SCR protection momentary p...

Страница 32: ...r the unit mounted version is factory installed Available for 2300 4160 volts see Table 3 the starter enclosure is NEMA 1 with a hinged access door with lock and key Electrical lugs for incoming power...

Страница 33: ...ire modified motors A field installed electromechanical compressor motor starter is available selected for proper size and type for job requirements and in accordance with Johnson Controls Engineering...

Страница 34: ...nfigura tion This reduces the voltage to the motor stator by a factor of three This 1 3 voltage results in 1 3 current into the motor at start and 1 3 torque to the shaft Centrifugal com pressor start...

Страница 35: ...P II Totally Enclosed Fan Cooled Motors TEFC TEFC motors are used where the loca tion is extremely dirty dusty or wet both indoors and outdoors A totally enclosed fan cooled unit is enclosed to preven...

Страница 36: ...e designed for one inch 25 mm deflection WATERBOXES Marine Waterboxes Marine waterboxes allow service access for cleaning of the heat exchanger tubes without the need to break the water piping Bolted...

Страница 37: ...tware that reduces operational sound levels expands the chiller operating range and improves chiller performance The OptiSound Control feature continuously monitors the characteristics of the compress...

Страница 38: ...JOHNSON CONTROLS FORM 160 75 EG1 519 38 Figure 1 TYPICAL OPTIMIZED CENTRIFUGAL COMPRESSOR Accessories and Modifications Cont d...

Страница 39: ...than evaporative or closed loop air exchange methods need to request a factory supplied temperature control valve to prevent condensation inside the VSD or SSS cabinet Other areas susceptible to wate...

Страница 40: ...ecial ma terials of construction General Piping All chilled water and condenser water piping should be designed and installed in accordance with accepted piping practice Chilled water and condenser wa...

Страница 41: ...ovided by the following equation Min ECWT LCHWT C RANGE 5 F 12 Load 100 or Min ECWT LCHWT C RANGE 2 8 C 6 6 Load 100 where ECWT entering condensing water temperature LCHWT leaving chilled water temper...

Страница 42: ...s Parallel Arrangement Figure 2 Parallel Evaporators Parallel Condensers on page 42 Chillers may be applied in multiples with chilled and condenser water circuits connected in parallel between the uni...

Страница 43: ...h con densers The water ranges are split which allows a lower temperature difference or head on each chiller than multiple units in parallel For equal chillers the machine at higher temperature level...

Страница 44: ...ves on the evaporator if the optional refrigerant isolation valves are ordered The dual relief valves on the condenser are re dundant and allow changing of either valve while the unit is fully charged...

Страница 45: ...ate An alarm is to be activated and the mechanical ventilation started at a value no greater than the TLV Threshold Limit Value of the refrigerant ELECTRICAL CONSIDERATIONS Motor Voltage Low voltage m...

Страница 46: ...must be sized and installed to meet the National Electrical Code and be verified by Johnson Controls Ampacity on Load Side of Starter Electrical power wire size to the chiller is based on the minimum...

Страница 47: ...ng program is selected from Table 9 on page 60 to Table 12 on page 62 The full load amperes FLA listed in the tables is maximum values and corresponds to the maximum motor kW listed When the input pow...

Страница 48: ...3 1106 70 243 15 725 46 DQ 896 57 3228 204 448 28 1372 87 299 19 906 57 DR 866 55 3463 218 433 27 1301 82 289 18 854 54 DR 1120 71 4035 255 560 35 1685 106 373 24 1114 70 DS 1043 66 4170 263 521 33 15...

Страница 49: ...198 76 4098 259 798 50 2742 173 JR 2479 156 8933 564 1239 78 4054 256 826 52 2903 183 JS 2616 165 10463 660 1308 83 4427 279 872 55 2974 188 JS 2756 174 9933 627 1378 87 4395 277 KP KT 1545 97 6181 39...

Страница 50: ...00 1082 68 3210 203 NS 3271 206 11786 744 1635 103 4892 309 N2 2003 126 8013 506 1002 63 3870 244 668 42 2580 163 N2 2131 134 7678 484 1065 67 3839 242 710 45 2559 161 N3 2375 150 9502 599 1188 75 452...

Страница 51: ...62 2302 145 8650 546 1534 97 5708 360 R3 4996 315 18005 1136 2498 158 9002 568 1665 105 6002 379 R7 5241 331 20965 1323 2621 165 9682 611 1747 110 6404 404 R4 5914 373 21311 1344 2957 187 10655 672 RP...

Страница 52: ...2 4607 291 16602 1047 2304 145 8143 514 1536 97 5497 347 V3 5710 360 20578 1298 2855 180 9865 622 1903 120 6749 426 V4 6299 397 22700 1432 3150 199 10725 677 2100 132 7395 467 V5 7093 447 25559 1613 3...

Страница 53: ...475 3244 205 11689 737 2162 136 7793 492 X4 6281 396 25125 1585 3141 198 11250 710 2094 132 7470 471 X4 8099 511 29185 1841 4049 255 14441 911 ZQ 4769 301 19076 1204 2385 150 6671 421 1590 100 4390 27...

Страница 54: ...3 C4 938 59 3753 237 469 30 1877 118 313 20 1251 79 C5 1221 77 4884 308 611 39 2442 154 407 26 1628 103 DC 796 50 3186 201 398 25 1214 77 265 17 809 51 DD 999 63 3995 252 499 32 1501 95 333 21 1010 64...

Страница 55: ...G5 1973 124 7892 498 986 62 3946 249 658 41 2631 166 HC 1293 82 5170 326 646 41 1967 124 431 27 1312 83 HD 1618 102 6472 408 809 51 2426 153 539 34 1635 103 HE 2108 133 8432 532 1054 66 3075 194 703 4...

Страница 56: ...153 9715 613 1214 77 4790 302 810 51 3226 204 M8 3015 190 12059 761 1504 95 5780 365 1003 63 3947 249 M9 3420 216 13678 863 1710 108 6434 406 NB 2479 156 9916 626 1239 78 3577 226 824 52 2374 150 ND 2...

Страница 57: ...1065 67 3042 192 QF 3680 232 14722 929 1839 116 5268 332 1227 77 3479 220 QH 1902 120 7608 480 951 60 2799 177 Q5 2580 163 10319 651 1287 81 4734 299 Q7 3027 191 12107 764 1510 95 5456 344 1009 64 37...

Страница 58: ...63 3138 198 661 42 2102 133 O8 3053 193 11002 694 1527 96 5501 347 1018 64 3667 231 1122 71 4043 255 561 35 2021 128 374 24 1348 85 O9 3053 193 11002 694 1527 96 5501 347 1018 64 3667 231 1791 113 645...

Страница 59: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 59 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 60: ...1444 1624 1774 1983 2156 2168 2518 2880 3089 3223 3704 4215 2300 FLA 36 41 1 46 55 63 70 73 9 80 87 95 106 113 124 135 146 LRA 240 267 298 340 397 435 480 520 543 590 669 719 791 867 935 3300 FLA 25...

Страница 61: ...7 173 186 202 217 233 267 306 344 382 LRA 682 719 744 819 858 942 1110 1110 1311 1416 1514 1661 2011 2388 2479 4000 FLA 88 6 94 8 101 107 114 130 143 154 166 179 192 220 252 283 315 LRA 540 554 631 67...

Страница 62: ...1177 1301 1320 1655 1865 2037 2485 2485 2976 2976 3300 3348 3644 4687 460 FLA 173 198 225 264 301 337 365 391 427 471 517 556 615 675 LRA 1230 1360 1380 1730 1950 2130 2598 2598 3111 3111 3450 3500 38...

Страница 63: ...47 895 954 1072 1179 1286 1393 LRA 5092 5175 5510 5562 6031 6308 6720 7319 8133 9821 575 FLA 586 617 654 707 747 796 895 984 1074 1163 LRA 4039 4100 4200 4200 4694 4963 5148 5610 6232 7527 600 FLA 562...

Страница 64: ...S TYPE STARTER SOLID STATE STARTER STAR DELTA AUTO TRANSFORMER ACROSS THE LINE PRIMARY REACTOR VOLTAGE LOW MEDIUM LOW LOW LOW MEDIUM LOW MEDIUM LOW MEDIUM MEDIUM MEDIUM 60 HZ 200 4160 200 600 200 600...

Страница 65: ...5 300 1126 7527 1100 300 984 2598 351 80 380 460 440 460 480 3652 503 120 565 5777 790 200 880 7014 1048 300 1180 7527 1300 300 1163 2413 424 80 377 575 575 600 3550 608 120 540 2727 292 80 380 380 38...

Страница 66: ...94 1000 156 MVVSD1250RK 94 1250 195 MVVSD1500RK 94 1500 235 MVVSD1750RK 94 1750 274 MVVSD2000RK 94 2000 312 MVVSD2250RK 94 2250 345 MVVSD2500RK 94 2500 391 MVVSD0500RK 92S 500 62 4160 3 60 MVVSD0600R...

Страница 67: ...NCLATURE MVVSD 2500 R K 80 VOLTAGE CODE 80 2300V 60Hz 92 3300V 50Hz 94 4180V 60Hz K YK OIL PUMP SUPPLY R FIELD INSTALLED MAXIMUM DRIVE HORSEPOWER 0500 500 HP 0600 600 HP 0700 700 HP 0800 800 HP 0900 9...

Страница 68: ...0 230 240 3 60 14L 40B 3111 65 510 380 380 3 60 14L 46B 3111 65 510 460 440 460 480 3 60 14L 50B 3111 65 510 400 380 400 415 3 50 14L 58B 3111 65 510 575 575 600 3 60 26L 17B 5780 125 850 200 200 208...

Страница 69: ...HZ 3300 50Hz 4160 60HZ UMVSSS0853K190 V V 190 1896 UMVSSS0853K280 V V 280 1896 UMVSSS0853K389 V V 389 1896 UMVSSS1708K389 V V 389 3796 MEDIUM VOLTAGE UNIT MOUNTED SOLID STATE STARTER NOMENCLATURE UMVS...

Страница 70: ...BINET UNIT MODEL REFERENCE CHART MVSSS0853R_042 V 42 1896 MVSSS0853R_050 V 50 1896 MVSSS0853R_065 V 65 1896 MVSSS0853R_095 V 95 1896 MVSSS0853R_105 V 105 1896 MVSSS0853R_140 V 140 1896 MVSSS0853R_190...

Страница 71: ...60Hz 92 3300V 50Hz 94 4180V 60Hz K YK OIL PUMP SUPPLY X NO OIL PUMP SUPPLY R FIELD INSTALLED LD19169 MAXIMUM STARTING CURRENT 0853 853 AMPS 1708 1708 AMPS MAXIMUM JOB FLA CURRENT 042 042 AMPS 050 050...

Страница 72: ...TO JS JP TO JS LQ TO LS LQ TO LS H9 KP TO KS K2 TO K4 KP TO KS K2 TO K4 CN CA EN EA 5CK 5CW 5EK 5EW MQ TO MS M2 TO M4 MP TO MS M2 TO M4 K1 KT TO KX K5 TO K7 KP TO KS K2 TO K4 CS DC ES FC 5CN 5DC 5EN 5...

Страница 73: ...CP TO CS DC TO DE D3 TO D5 DP TO DS Q5 CC TO CE C3 TO C5 CP TO CS CH CT EH ET 5CE 5CO 5EE 5EO DC TO DE D3 TO D5 DP TO DS Q5 Q6 Q7 EC TO EE E3 TO E5 EP TO ET FC TO FE F3 TO F5 FQ TO FT P7 EC TO EE E3 T...

Страница 74: ...4877 P8 COMPRESSOR EVAPORATOR CONDENSER SHELL CODES G E H F J J L L A 6 11 2108 6 11 2108 7 6 1 2 2299 7 6 1 2 2299 B 10 6 3200 10 6 3200 10 11 3327 10 11 3327 C 2 0 610 2 0 610 2 1 1 4 641 2 1 1 4 64...

Страница 75: ...445 1 5 1 2 445 E 12 3658 16 4877 12 3658 16 4877 Q6 COMPRESSOR EVAPORATOR CONDENSER SHELL CODES E E F F A 7 0 2134 7 0 2134 B 8 3 2515 8 3 2515 C 1 7 1 2 495 1 7 1 2 495 D 1 5 1 2 445 1 5 1 2 445 NOT...

Страница 76: ...508 1 11 584 1 11 584 2 1 1 4 641 2 1 1 4 641 E 14 0 4267 14 0 4267 16 0 4877 14 0 4267 16 0 4877 ADDITIONAL OPERATING HEIGHT CLEARANCE TO FLOOR TYPE OF CHILLER MOUNTING M NEOPRENE PAD ISOLATORS 1 3 4...

Страница 77: ...overall unit length by adding waterbox depth to tube sheet length 4 Water nozzles can be located on either end of unit Add 1 2 12 mm to nozzle length for flanges connec tions 5 To determine overall he...

Страница 78: ...DD M M C C F G N P BB DD BB DD 1 PASS 2 PASS 3 PASS LD07598a 1 PASS NO OF PASSES EVAPORATOR IN OUT 1 A H H A 2 PASS NO OF PASSES EVAPORATOR IN OUT 2 C B K J 3 PASS NO OF PASSES EVAPORATOR IN OUT 3 G N...

Страница 79: ...3 1 3 1 2 394 3 3 1 2 1003 I J K L 16 12 10 2 1 1 4 641 2 6 762 1 5 432 3 7 1092 1 5 432 3 7 1092 EVAPORATORS COMPACT WATER BOXES A THROUGH L EVAPORATORS NOTES 1 All dimensions are ft inches mm 2 All...

Страница 80: ...A SHELL CODE 2 PASS IN OUT M N P Q CC BB KK JJ SHELL CODES 2 PASS IN OUT R S W X Z DD CC EE BB LL KK MM JJ SHELL CODES 3 PASS IN OUT M Z GG NN PP FF FRONT OF UNIT FLOOR LINE COMPRESSOR END MOTOR END F...

Страница 81: ...1 11 1 2 597 4 3 1 2 1308 R S W 20 18 14 2 8 813 3 5 1 4 1048 2 4 1 2 724 4 6 1 2 1384 10 1 2 267 2 1 635 4 10 1473 X Z 20 18 14 2 11 1 2 902 3 9 3 4 1162 2 8 3 4 832 4 10 3 4 1492 11 279 2 2 7 8 683...

Страница 82: ...A C D E F G H I J K L M N P Q R S W X Z A 1 2 1 4 362 1 3 381 1 3 1 2 394 1 3 3 4 400 1 5 1 2 445 1 11 5 8 565 1 11 5 8 600 2 5 8 613 2 1 3 4 600 B 6 1 2 165 0 7 178 7 1 2 191 7 3 4 197 9 1 2 241 1 3...

Страница 83: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 83 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 84: ...a 1 PASS7 NO OF PASSES CONDENSER IN OUT 1 P Q Q P 2 PASS7 NO OF PASSES CONDENSER IN OUT 2 R S T U 3 PASS7 NO OF PASSES CONDENSER IN OUT 3 V Y X W FRONT OF UNIT FLOOR LINE COMPRESSOR END MOTOR END FRON...

Страница 85: ...All dimensions are ft inches mm 2 Standard water nozzles are furnished as welding stub outs with ANSI AWWA C 606 grooves allowing the option of welding flanges or use of ANSI AWWA C 606 couplings Fac...

Страница 86: ...3 4 197 9 1 2 241 1 2 3 8 365 1 3 3 8 391 1 4 3 8 416 DOUBLE BUNDLE HEAT RECOVERY CONDENSERS CODES B I O U Y DIM TOWER HEATING TOWER HEATING TOWER HEATING TOWER HEATING TOWER HEATING A 1 6 1 2 470 1 5...

Страница 87: ...OF PASSES NUMBER OF PASSES 1 2 3 1 2 3 D K L I B 10 8 6 10 8 6 1 8 7 8 530 1 9 1 4 540 3 6 1 2 1080 9 1 16 230 I 14 10 8 12 8 8 1 11 3 8 594 1 10 1 4 565 3 8 1 8 1121 10 1 8 257 O 16 12 10 14 10 8 2 3...

Страница 88: ...LOOR LINE FRONT OF UNIT MOTOR END FLOOR LINE FRONT OF UNIT COMPRESSOR END MOTOR END FLOOR LINE FRONT OF UNIT COMPRESSOR END MOTOR END FLOOR LINE FRONT OF UNIT COMPRESSOR END MOTOR END FLOOR LINE COMPR...

Страница 89: ...5 1 2 445 3 11 1194 3 11 1194 10 254 1 6 1 2 470 3 11 1194 10 254 1 6 1 2 470 E F 14 10 8 1 7 1 2 495 4 3 1295 4 3 1295 11 279 1 9 1 2 546 4 3 1295 11 279 1 9 1 2 546 G H 14 10 8 2 0 610 4 7 3 8 1407...

Страница 90: ...02 1 10 1 2 572 11 1 4 286 10 1 4 260 1 10 1 2 572 10 1 4 260 i J K L 2 3 686 1 3 8 314 1 11 1 2 597 9 1 2 241 0 10 9 16 268 1 11 1 2 597 10 1 2 267 M N 2 6 762 1 1 1 2 343 2 2 660 1 1 8 308 11 1 2 29...

Страница 91: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 91 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 92: ...R END MOTOR END FRONT OF UNIT COMPRESSOR END MOTOR END FRONT OF UNIT COMPRESSOR END MOTOR END FRONT OF UNIT COMPRESSOR END FRONT OF UNIT COMPRESSOR END MOTOR END FRONT OF UNIT COMPRESSOR END MOTOR END...

Страница 93: ...3 4 806 2 11 1 2 902 7 2 2184 2 7 3 4 806 2 11 1 2 902 NOTES 1 All dimensions are ft inches mm 2 Standard water nozzles are furnished as welding stub outs with ANSI AWWA C 606 grooves allowing the op...

Страница 94: ...C L M 20 14 S V V D 1 PASS 2 PASS 3 PASS LD18383 CONDENSERS MARINE WATER BOXES Heat Recovery Units Main Tower Circuit Only FRONT OF UNIT COMPRESSOR END MOTOR END FRONT OF UNIT COMPRESSOR END MOTOR END...

Страница 95: ...ES Heat Recovery Units Main Tower Circuit Only NOTES 1 All dimensions are ft inches mm 2 Standard water nozzles are furnished as welding stub outs with ANSI AWWA C 606 grooves allowing the option of w...

Страница 96: ...191 10 1 4 260 1 11 584 10 1 4 260 M N 2 8 813 1 2 7 8 378 2 2 660 0 8 203 1 0 305 2 2 660 1 0 305 O6 2 6 1 4 768 1 2 1 4 362 2 1 3 4 654 1 1 1 2 343 1 0 305 2 1 3 4 654 1 0 305 P Q 2 8 813 1 2 1 2 3...

Страница 97: ...762 76300 34609 4815 2184 S V K4 60100 27261 81300 36877 5467 2480 X T K4 59200 26853 80000 36288 5338 2421 X X K4 66000 29937 87000 39463 5875 2665 W W K7 79500 36061 104000 47174 8002 3630 Z Y K7 95...

Страница 98: ...1274 578 1078 489 1322 600 B 1569 712 874 396 1677 761 2113 958 1094 496 2071 939 C D 946 429 778 353 1046 474 1692 767 1524 691 1792 813 E F 726 329 811 368 791 359 1337 606 1722 781 1702 772 I 2066...

Страница 99: ...condenser shall be selected for ____ fouling factor and maximum liquid pressure drop of ____ kPa The waterside shall be designed for 10 3 barg working pressure Power shall be supplied to the compresso...

Страница 100: ...r and all interconnecting unit piping and wiring The chiller shall be painted prior to shipment The initial charge of oil and refrigerant shall be supplied factory charged in the chiller or shipped in...

Страница 101: ...rigerant cooled oil cooler with all piping factory installed Oil side of the oil cooler shall be provided with service valves An automatic oil return system to recover any oil that may have migrated t...

Страница 102: ...0 035 1 mm Each tube shall be roller expanded into the tube sheets providing a leak proof seal and be individually replaceable Water velocity through the tubes shall not exceed 12 ft sec 3 7 m sec A...

Страница 103: ...h the check valve Waterboxes shall be removable to permit tube cleaning and replacement Stubout water connections having ANSI AWWA C 606 grooves shall be provided Waterboxes shall be designed for 150...

Страница 104: ...temperature 8 Compressor thrust bearing positioning and oil temperature 9 Operating hours 10 Number of unit starts B Digital programming of setpoints through the universal keypad including 1 Leaving c...

Страница 105: ...mperature 10 Oil high temperature 11 Oil low differential pressure 12 Oil high differential pressure 13 Oil sump pressure transducer out of range 14 Oil differential pressure calibration 15 Oil variab...

Страница 106: ...perature 7 Leaving chilled liquid flow switch open 8 Motor controller contacts open 9 Motor controller loss of current 10 Power fault 11 Control panel schedule 12 Starter low supply line voltage SSS o...

Страница 107: ...and password recognition which is defined by three different levels of user need view operator and service J Trending data with the ability to customize points of once every second to once every hour...

Страница 108: ...a NEMA 1 enclosure with all power and control wiring between the drive and chiller factory installed including power to the chiller oil pump Field power wiring shall be a single point connection and...

Страница 109: ...formation shall not be acceptable FACTORY INSTALLED COMPRESSOR MOTOR STARTER OPTION THROUGH 900 HP 671 KW 200 600 VOLTS The chiller manufacturer shall furnish a reduced voltage Solid State Starter for...

Страница 110: ...urrent and overload settings adjusted at the factory The starter shall provide through the use of six in line not inside the Delta silicon controlled rectifiers 2 per phase a smooth acceleration of th...

Страница 111: ...following convenience items already mounted and wired to the starter at the factory Auxiliary control supply transformer eliminates the need for running separate 115V 1 phase 50 60 Hz power source wi...

Страница 112: ...easured in Coefficient of Performance COP kW ton kW input kW refrigeration effect kW ton and COP are related as follows kW ton 3 516 COP COP 3 516 kW ton SI Metric Conversion MEASUREMENT MULTIPLY THIS...

Страница 113: ...FORM 160 75 EG1 519 JOHNSON CONTROLS 113 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 114: ...Printed on recycled paper Form 160 75 EG1 519 Supersedes 160 75 EG1 517 2019 Johnson Controls Inc P O Box 423 Milwaukee WI 53201 Printed in USA www johnsoncontrols com Issued on 5 24 2019...

Отзывы: