YCCS System Manager and Zone Coordinator Installation Instructions 

5

428546-YIM-C-1110

Note:

Power supply wire colors may be different 

on transformers not manufactured by Johnson 
Controls, Inc. Follow the transformer 
manufacturer’s instructions and project installation 
drawings for wiring details.

3. Connect the Ethernet communication cable to the 

RJ-45, 8-pin Ethernet port (Figure 1).

Note:

The Ethernet communication cable is 

optional. It is only required for remote access to the 
controller.

4. Connect the phone line to the modem port, if using 

the internal modem.

Note:

The 24 VAC power should be connected to 

all network devices so transformer phasing is 
uniform across the devices. Powering devices with 
uniform 24 VAC supply power phasing reduces 
noise, interference, and ground loop problems. The 
controllers do not require an earth ground 
connection.

Table 3 outlines the System and Zone Communication 
Bus limits for the controllers. Table 4 outlines Ethernet 
limits in YCCS applications. 

     

Table 3:  System and Zone Communication Bus Limits

Category

Limits

General

System Manager (YK-SMU2xx-0)

Supports one System Communication Bus trunk and daisy-chained field controllers only.

Zone Coordinator (YK-ZCUxxx-0)

Supports one System Communication Bus and one Zone Communication Bus per Zone 

Coordinator, and daisy-chained field controllers only.

Number of Devices 

Supported

System Manager (YK-SMU2xx-0)

Supports up to 38 devices total on the System Communications Bus, including: 
•  up to 10 Zone Coordinators
•  up to 24 factory- or field-mounted RoofTop Unit (RTU) controllers
•  up to 4 Input/Output Module (IOM) controllers 
•  up to 24 TEC Series thermostat controllers

Note:

The total number of TECs and RTU Controllers combined cannot exceed 24 devices.

Zone Coordinator (YK-ZCUxxx-0)

In a Changeover Bypass (COBP) system, supports up to 26 devices total on the Zone 

Communication Bus, including:
•  up to 24 zone damper controllers
•  1 factory- or field-mounted Change Over Bypass (COBP) RTU controller
•  1 bypass damper controller
In a Variable Air Volume (VAV) system, supports up to 33 devices total on the Zone 

Communication Bus, including:
•  up to 32 VAV zone damper controllers
•  1 factory- or field-mounted VAV RTU controller

Bus Length

System Bus: 

305 m (1,000 ft) of cable

Zone Bus: 

305 m (1,000 ft) of cable

Cable Type

Stranded 0.6 mm (22 AWG) 3-wire twisted, shielded cable with drain wire (preferred). 

Stranded 0.6 mm (22 AWG) 4-wire (two-twisted-pairs) shielded cable (acceptable).

Note:

The + and - Bus leads must be a twisted pair. On Bus applications using 4-wire cable 

(two twisted pairs), isolate and insulate unused conductors.

Terminations

One EOL switch in the ON position.

Table 4:  Ethernet Limits

Category

Limits

General

Point-to-point star topology with network hubs/switches.

Line Length and Type

2,012 m (6,600 ft) for plastic/glass fiber optic with external adapter; 100 m (330 ft) CAT5 cable.

Terminations

For 10/100 Base-T, no line terminators allowed.

Содержание YK-SMU2x0-0

Страница 1: ...trollers have no user serviceable parts inside the housing Parts Included One System Manager or Zone Coordinator with removable mounting base Materials and Special Tools Needed three fasteners appropr...

Страница 2: ...pervisory controller securely and evenly on the surface Mount the supervisory controller in areas free of corrosive vapors and observe the environmental limitations listed in the Technical Specificati...

Страница 3: ...or ports modular jacks and terminal blocks Power Supply The Zone Coordinator and System Manager requires a dedicated Class 2 24 VAC 10 VA minimum power supply System Communication Zone Communication B...

Страница 4: ...three Zone Communication Bus wires for the Zone Coordinator Figure 3 and Figure 4 Note When the controllers are connected to the System Communication Bus you must set the End of Line EOL switch to th...

Страница 5: ...ices Supported System Manager YK SMU2xx 0 Supports up to 38 devices total on the System Communications Bus including up to 10 Zone Coordinators up to 24 factory or field mounted RoofTop Unit RTU contr...

Страница 6: ...ly of the communication trunk Do this on the last unit in line 7 Use an existing hole or drill a hole and insert a sheet metal screw in the back plate below the communication connector 8 Wrap the bare...

Страница 7: ...2 COM AI1 AI2 COM AI3 AI4 1 64 32 16 8 4 2 128 O N 24V COM 24V COM COM J2 COM AI1 AI2 COM AI3 AI4 1 64 32 16 8 4 2 128 O N 24V COM 24V COM Drain Wire Drain Wire Tape back Drain Wire Drain Wire Drain W...

Страница 8: ...Line EOL termination to reduce interference Interference is caused by signal reflection that occurs when data transmissions reach the end of a bus segment and bounce back Figure 8 The high baud rates...

Страница 9: ...re Light Sensor Refrigerant Sensor To 24VAC BO 3 BO 2 BO 1 BO 4 COM Monitored Contact To Scheduled Item 1 To Scheduled Item 2 To Scheduled Item 3 To Scheduled Item 4 Non CCS HVAC System Universal CV U...

Страница 10: ...reliable partition disconnect and isolate a portion of the Bus for testing purposes and test the Bus portion connected to the System Manager and Zone Coordinator controllers Correcting Physical Commun...

Страница 11: ...touch screen user interface and Ethernet port for Web browser access and optional internal modem Power Supply Requirement Dedicated nominal 24 VAC Class 2 power supply North America at 50 60 Hz 20 VA...

Страница 12: ...l internal modem YK ZCU400 0 VAV Zone Coordinator with color touch screen user interface and Ethernet port for Web browser access YK ZCU410 0 VAV Zone Coordinator with color touch screen user interfac...

Отзывы: