SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
JOHNSON CONTROLS
85
FORM 160.54-O1
ISSUE DATE: 9/10/2014
2
OVERVIEW
This screen displays all information pertaining to the
Mod “A” Solid State Starter.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. For the Solid State Starter
this is the data returned by the Starter Logic Board.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link Gateway interface in
ISN mode, or a locally programmed value.
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Scale/Model
Display information about the Liquid Cooled Solid
State Starter Rating and the maximum allowed Full
Load Amps.
Voltage – Phase A, B, C
Display the 3-phase input line voltage values being
read from the Solid State Starter.
Current – Phase A, B, C
Display the 3-phase motor current values being read
from the Solid State Starter.
For fields requiring access level of SER
-
VICE. Service Technicians refer to the
OptiView Control Center - Service Instruc
-
tions (Form 160.54-M1) for operation
instructions and explanation of all pro-
grammable setpoints and displayed values.
PROGRAMMABLE
Local Motor Current Limit
Access Level Required: OPERATOR
Allows the user to specify the maximum allowed mo-
tor current (as a percentage of FLA). When the motor
MOD “A” SOLID STATE STARTER SCREEN
LD10707a
FIGURE 27 -
MOD “A” SOLID STATE STARTER SCREEN