Johnson Controls Unitary Products

VFD

2-10 VDC (0-100%) output for the indoor blower 
Variable Frequency Drive

Output is active with indoor blower operation. For CV units: this 
output provides stepped IntelliSpeed control of the indoor 
blower VFD based on fan-only, cooling stage and heating stage 
outputs. For VAV units: this output provides control of the indoor 
blower VFD based on supply duct static pressure input and 
setpoint.

VFDFLT

24 VAC hot input from the normally open VFD 
alarm contact

The VFD alarm contact switches from R within the unit wiring 
harness. 24 VAC input results in unit shutdown and a “VFD 
fault” alarm

Terminal at lower right corner of UCB

24V FOR OUTPUTS

24 VAC hot for H1, H2, CN-FAN, AUX HGR, FAN 
C1 and
C2 output relay contact switching

Output relay circuitry is isolated from other UCB components 
and the 24 VAC hot source may be from a second transformer 
in the unit

Pin Heat section connections at right on lower edge of UCB

H1

24 VAC hot output for heat section stage 1

Not effective for cooling-only units. Output if demand is present 
and permissions allow one stage or two stages of heat section 
operation

H2

24 VAC hot output for heat section stage 2

Not effective for cooling-only units or units with single-stage 
heat sections. Output if demand is present and permissions 
allow two stages of heat section operation

MV

24 VAC hot input confirming heat section 
operation

Sourced from gas valve in gas heat units or first stage heat 
contactor in electric heat units. Input within 5 minutes from 
initiation of H1 output initiates the “Heat On Fan Delay” timer, 
loss of input following the termination of H1 output initiates the 
“Heat On Fan Delay” timer, no input within 5 minutes from 
initiation of H1 output initiates an “Ignition Failure” alarm, input 
for longer than 5 minutes without H1 output initiates a “Gas 
Valve Mis-wire” alarm

Pin Cooling and fan output connections at right on lower edge of UCB

CN-FAN

24 VAC hot output for the condenser fan contactor 
coil

Output with either C1 or C2 output; interrupted during defrost 
cycle for heat pump units

AUX HGR

24 VAC hot output for hot gas reheat components Effective only for reheat units, output with reheat operation

FAN

24 VAC hot output for indoor blower contactor coil/
indoor blower VFD enable relay coil

Output with heat/cool operation, G input or schedule demand

C1

24 VAC hot output for compressor 1

If demand is present and permissions allow compressor 1 
operation; output with compressor cooling, comfort ventilation 
cooling, reheat or heat pump heating demands

C2

24 VAC hot output for compressor 2

Not effective for one stage compressor UCBs. If demand is 
present and permissions allow compressor 2 operation; output 
with compressor cooling, comfort ventilation cooling or heat 
pump heating demands

Pin Refrigerant circuit safety switch and indoor blower overload connections at center on lower edge of UCB

HPS1

(right pin)

24 VAC hot out for refrigerant circuit 1 High 
Pressure Switch

Connects through circuit trace to the R terminal

HPS1

(left pin)

24 VAC hot return from refrigerant circuit 1 High 
Pressure Switch

Input is only considered if C1 output is needed; input must be 
present to allow C1 output. Three HPS1 trips in a two hour 
period cause a “High Pressure Switch 1 Lockout” and C1 output 
is then prevented until alarm reset. Connects through circuit 
trace to the right LPS1 pin.

LPS1

(right pin)

24 VAC hot out for refrigerant circuit 1 Low 
Pressure Switch

Connects through circuit trace to the left HSP1 pin

Table 9:

Smart Equipment™ UCB Details (Continued)

Description

Function & Comments

Содержание YD360 Series

Страница 1: ...Unit 9 6 Unit Dimensions Inches 14 7 Piping And Electrical Connection Sizes 30 40 50T Inches 16 8 Electrical Power Knockout Sizes Inches 16 9 Smart Equipment UCB Details 23 LIST OF FIGURES 1 Corner We...

Страница 2: ...50 Ton C00 Cooling Only Product Options AA None TA Technicoat Condenser Coil Installation Options A None 2 208 230 3 60 4 460 3 60 5 575 3 60 Configured Split Condenser Model Number Nomenclature A St...

Страница 3: ...n the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Improper installation may create a condition where the operation of the product could ca...

Страница 4: ...em Scroll Tandem Scroll Quantity 2 2 2 Cooling Nominal Capacity Tons System 1 15 20 25 System 2 15 20 25 Capacity Stages System 1 2 2 2 System 2 2 2 2 SYSTEM DATA No Refrigeration Circuits 2 2 2 Sucti...

Страница 5: ...ngth to support the unit The condensing unit must be mounted on level supports The supports can be channel iron beams or wooden beams treated to reduce deterioration Minimums of two 2 beams are requir...

Страница 6: ...on of vibration Holes are provided in the base rails for bolting the unit to its foundation For ground level installations precautions should be taken to protect the unit from tampering and unauthoriz...

Страница 7: ...of the unit When preparing to move the unit always determine the center of gravity see Table 3 and Figure 1 of the unit in order to equally distribute the weight Slings connected to the compressor end...

Страница 8: ...to compressor replacement repairing refrigerant leaks replacing refrigerant components such as filter drier pressure switch metering device or coil Units are shipped with compressor mountings which ar...

Страница 9: ...3 60 1 1 2 4 2 9 63 5 70 575 3 60 4 9 0 14 78 575 3 60 1 1 2 4 2 2 47 1 50 YD480 208 230 3 60 4 30 1 47 225 208 230 3 60 1 1 2 4 5 8 151 1 175 460 3 60 4 16 7 26 114 460 3 60 1 1 2 4 2 9 82 6 90 575 3...

Страница 10: ...emperatures must also be insulated Never solder suction and liquid lines together They can be taped together for convenience and support purposes but they must be completely insulated from each other...

Страница 11: ...ctions of the main lines Connect the main liquid line to the liquid line connection on the evaporator unit while maintaining a flow of nitrogen Make the suction line connection at the evaporator and r...

Страница 12: ...Line Solenoid Wiring NOTE For applications on airhandlers evaporator DX coils other than ND360 600 certified matchups liquid line solenoids may be required for proper operation and refrigerant system...

Страница 13: ...On non ND models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit Non ND units may not include any or all of the components required to wire the unit Use...

Страница 14: ...4 Johnson Controls Unitary Products Figure 6 YD Unit Dimensions Table 6 Unit Dimensions Inches MODEL A B C D E F G H YD360 128 5 88 5 37 5 41 8 40 0 46 1 37 1 23 6 YD480 128 5 88 5 57 7 41 8 40 0 46 1...

Страница 15: ...183 2 313 88 140 22 358 20 858 19 358 37 518 12 878 9 628 5012886 YIM B 0517 Johnson Controls Unitary Products 15 Figure 7 30 Ton Power And Control Wiring Connections Figure 8 40 50 Ton Power And Cont...

Страница 16: ...NTRY SIZE SUCTION LINE SYS 1 1 5 8 OD LIQUID LINE SYS 1 7 8 OD SUCTION LINE SYS 2 1 5 8 OD LIQUID LINE SYS 2 7 8 OD POWER WIRING KNOCKOUT SEE TABLE 8 CONTROL WIRING 7 8 HOLE Table 8 Electrical Power K...

Страница 17: ...ent clearances been provided 2 Has all foreign matter been removed from the interior of the unit tools construction or shipping materials etc 3 Have the condenser fans been rotated manually to check f...

Страница 18: ...minute If it fails to close the unit will shut down the associated compressor and begin an ASCD If the call for cool is still present at the end of the anti short cycle time delaying the control boar...

Страница 19: ...of System 2 When the LPS of UCB 2 falls below its cut out point the PR2 relay brings on the 3LLS Solenoid allowing refrigerant in system 2 to return flow to the compressor for normal mechanical coolin...

Страница 20: ...enance consists of changing or cleaning filters and general cleaning of the outdoor coil MOTORS Outdoor fan motors are permanently lubricated and require no maintenance OUTDOOR COIL Dirt should not be...

Страница 21: ...cursor is on the top Status line hit the ENTER button This action steps the LCD display into the status mode Hit ENTER to view the status menu Press Enter Step 2 Scroll down to DVent Mode This is the...

Страница 22: ...CANCEL JOY C PWR 7 7 77 Clg Engaged LeadLag Engaged Press Enter Joy Stick Down 2 Step 6 By toggling down twice the screen reaches the ClgOcc SP screen or Cooling Occupied Set Point ENTER CANCEL JOY C...

Страница 23: ...mostat connection strip C and indoor blower VFD pin C 24V 24 VAC 75 VA transformer hot Powers the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for facto...

Страница 24: ...hing in series Unit wiring harness jumper plug for factory shutdown accessories must be removed if the switching of field added external accessories for unit shutdown are wired between thermo stat con...

Страница 25: ...ut from 10K 77 F Type III negative temperature coefficient thermistor Input required for 2 compressor heat pump units not required for 2 compressor A C units not active for 1 compressor units 3 625 VD...

Страница 26: ...no input within 5 minutes from initiation of H1 output initiates an Ignition Failure alarm input for longer than 5 minutes without H1 output initiates a Gas Valve Mis wire alarm Pin Cooling and fan o...

Страница 27: ...put is needed input must be present to allow FAN output and unit operation One FAN OVR trip lasting longer than 5 minutes or three FAN OVR trips in a two hour period cause a Fan Overload Lockout and u...

Страница 28: ...munication circuit COM Common for the FC Field Connected BUS BACnet MSTP communication circuit Negative of the VDC FC bus BACnet MSTP communication circuit SHLD Shield for the FC Field Connected BUS B...

Страница 29: ...with the TXV s left to the factory setting If the TXV s have been adjusted in the field the charging chart may no longer apply Outdoor Air Entering Condenser F 300 350 400 450 500 550 600 120 130 140...

Страница 30: ...scharge Pressure psi Suction Pressure psi Charging Curves 50 Ton 115 105 95 85 65 1 Make sure that all condenser fans are running when charging 2 This chart is applicable to unit with the TXV s left t...

Страница 31: ...5012886 YIM B 0517 Johnson Controls Unitary Products 31 Typical Wiring Diagrams Figure 17 Typical 208 230 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Страница 32: ...5012886 YIM B 0517 32 Johnson Controls Unitary Products Typical Wiring Diagrams Figure 18 Typical 460 575 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Страница 33: ...ocedures are followed and checks are made at initial start up This confidence is supported by the 30 day dealer protection coverage portion of our standard warranty policy which states that Johnson Co...

Страница 34: ...he equipment If the system is a VAV system the CFM will be the airflow when the remote VAV boxes are in the full open position and the frequency drive is operating at 60 HZ Do not proceed with the equ...

Страница 35: ...ystem 2 Is Condenser below Evaporator Yes No Yes No Total Line Length end to end _______ Ft _______ Ft Vertical Lift in Ft _______ Ft _______ Ft Vertical Fall in Ft _______ Ft _______ Ft Number of Elb...

Страница 36: ...t or change required to obtain the correct airflow Was it necessary to increase of decrease the airflow to meet the design conditions If the motor pulley size was changed measure the outside diameters...

Страница 37: ...hird if equipped Fourth if equipped Heat Pump 1st Stage Outside air temperature ________________ db F ________________ wb F ________________ RH Return Air Temperature ________________ db F ___________...

Страница 38: ..._______________________________ ________________________________________________________________________________________________________ _______________________________________________________________...

Отзывы: