5012886-YIM-B-0517

Johnson Controls Unitary Products

25

Pin Temperature sensor connections at right on upper edge of UCB

SAT+

Supply Air Temperature sensor input from 10K

 

@ 77

°

F, Type III negative temperature coefficient 

thermistor

Input required for operation; 3.625 VDC reading SAT+ to SAT

 

with open circuit. Used in heat/cool staging cutouts, free cooling 
operation, demand ventilation operation, comfort ventilation 
operation, economizer loading operation, VAV cooling 
operation, hydronic heat operation.

RAT+

Return Air Temperature sensor input from 10K

 

@ 77°F, Type III negative temperature coefficient 
thermistor

Input required for operation; 3.625 VDC reading RAT+ to RAT

 

with open circuit. Used in return air enthalpy calculation. 
Substitutes for space temperature if no other space 
temperature input is present.

OAT+

Outside Air Temperature sensor input from 10K

 

@ 77°F, Type III negative temperature coefficient 
thermistor

Input required for operation but may be a communicated value; 
3.625 VDC reading OAT+ to OAT

 with open circuit. Used in 

heat/cool cutouts, low ambient cooling determination, dry bulb 
free cooling changeover, outside air enthalpy calculation, 
economizer loading operation, heat pump demand defrost 
calculation.

CC1+

#1 refrigerant circuit Condenser Coil temperature 

sensor input from 10K

 @ 77°F, Type III negative 

temperature coefficient thermistor

Input required for heat pump units, not required for A/C units; 
3.625 VDC reading CC1+ to
CC1

 with open circuit. Used in heat pump demand defrost 

calculation.

EC1+

#1 refrigerant circuit Evaporator Coil temperature 

sensor input from 10K

 @ 77°F, Type III negative 

temperature coefficient thermistor

Input required for operation; 3.625 VDC reading EC1+ to EC1

 

with open circuit. Used in suction line temperature safety.

CC2+

#2 refrigerant circuit Condenser Coil temperature 

sensor input from 10K

 @ 77°F, Type III negative 

temperature coefficient thermistor

Input required for 2-compressor heat pump units, not required 
for 2-compressor A/C units, not active for 1-compressor units; 
3.625 VDC reading CC2+ to CC2

 with open circuit. Used in 

heat pump demand defrost calculation.

EC2+

#2 refrigerant circuit Evaporator Coil temperature 

sensor input from 10K

 @ 77°F, Type III negative 

temperature coefficient thermistor

Input required for operation of 2-compressor units, not active for 
1-compressor units; 3.625 VDC reading EC2+ to EC2

 with 

open circuit. Used in suction line temperature safety.

Pinned connections on right edge of UCB

RAH+

Return Air Humidity input from 0-10 VDC @ 0-

100% RH sensor

Input required for reheat units, optional in all other units, may be 
a communicated value. Used in return air enthalpy calculation, 
temperature/humidity setpoint reset, reheat operation.

DCT PRS+

Supply Duct Pressure input from 0-10 VDC @ 0-

5” w.c. sensor

Input required for variable air volume units. Used in VAV indoor 
blower operation.

DFS (upper pin)

24 VAC hot return from Dirty Filter Switch

Optional input; switch closure for greater than 15 seconds 
during indoor blower operation
initiates a notification alarm

DFS (lower pin)

24 VAC hot out for Dirty Filter Switch

Connects through circuit trace to the R terminal

APS (up-

per pin)

24 VAC hot return from Air Proving Switch

When this optional input is enabled: the air proving switch must 
close within 30 seconds
of initiation of indoor blower operation and not open for greater 
than 10 seconds during in- door blower operation to allow heat/
cool operation and prevent an “APS open” alarm; the air proving 
switch must open within 30 seconds of termination of indoor 
blower operation to prevent an “APS stuck closed” notification 
alarm

APS (lower pin)

24 VAC hot out for Air Proving Switch

Connects through circuit trace to the R terminal

C

Common for the VFD output

Negative of the VDC circuit for the VFD output

Table 9:

Smart Equipment™ UCB Details (Continued)

Description

Function & Comments

Содержание YD360 Series

Страница 1: ...Unit 9 6 Unit Dimensions Inches 14 7 Piping And Electrical Connection Sizes 30 40 50T Inches 16 8 Electrical Power Knockout Sizes Inches 16 9 Smart Equipment UCB Details 23 LIST OF FIGURES 1 Corner We...

Страница 2: ...50 Ton C00 Cooling Only Product Options AA None TA Technicoat Condenser Coil Installation Options A None 2 208 230 3 60 4 460 3 60 5 575 3 60 Configured Split Condenser Model Number Nomenclature A St...

Страница 3: ...n the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Improper installation may create a condition where the operation of the product could ca...

Страница 4: ...em Scroll Tandem Scroll Quantity 2 2 2 Cooling Nominal Capacity Tons System 1 15 20 25 System 2 15 20 25 Capacity Stages System 1 2 2 2 System 2 2 2 2 SYSTEM DATA No Refrigeration Circuits 2 2 2 Sucti...

Страница 5: ...ngth to support the unit The condensing unit must be mounted on level supports The supports can be channel iron beams or wooden beams treated to reduce deterioration Minimums of two 2 beams are requir...

Страница 6: ...on of vibration Holes are provided in the base rails for bolting the unit to its foundation For ground level installations precautions should be taken to protect the unit from tampering and unauthoriz...

Страница 7: ...of the unit When preparing to move the unit always determine the center of gravity see Table 3 and Figure 1 of the unit in order to equally distribute the weight Slings connected to the compressor end...

Страница 8: ...to compressor replacement repairing refrigerant leaks replacing refrigerant components such as filter drier pressure switch metering device or coil Units are shipped with compressor mountings which ar...

Страница 9: ...3 60 1 1 2 4 2 9 63 5 70 575 3 60 4 9 0 14 78 575 3 60 1 1 2 4 2 2 47 1 50 YD480 208 230 3 60 4 30 1 47 225 208 230 3 60 1 1 2 4 5 8 151 1 175 460 3 60 4 16 7 26 114 460 3 60 1 1 2 4 2 9 82 6 90 575 3...

Страница 10: ...emperatures must also be insulated Never solder suction and liquid lines together They can be taped together for convenience and support purposes but they must be completely insulated from each other...

Страница 11: ...ctions of the main lines Connect the main liquid line to the liquid line connection on the evaporator unit while maintaining a flow of nitrogen Make the suction line connection at the evaporator and r...

Страница 12: ...Line Solenoid Wiring NOTE For applications on airhandlers evaporator DX coils other than ND360 600 certified matchups liquid line solenoids may be required for proper operation and refrigerant system...

Страница 13: ...On non ND models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit Non ND units may not include any or all of the components required to wire the unit Use...

Страница 14: ...4 Johnson Controls Unitary Products Figure 6 YD Unit Dimensions Table 6 Unit Dimensions Inches MODEL A B C D E F G H YD360 128 5 88 5 37 5 41 8 40 0 46 1 37 1 23 6 YD480 128 5 88 5 57 7 41 8 40 0 46 1...

Страница 15: ...183 2 313 88 140 22 358 20 858 19 358 37 518 12 878 9 628 5012886 YIM B 0517 Johnson Controls Unitary Products 15 Figure 7 30 Ton Power And Control Wiring Connections Figure 8 40 50 Ton Power And Cont...

Страница 16: ...NTRY SIZE SUCTION LINE SYS 1 1 5 8 OD LIQUID LINE SYS 1 7 8 OD SUCTION LINE SYS 2 1 5 8 OD LIQUID LINE SYS 2 7 8 OD POWER WIRING KNOCKOUT SEE TABLE 8 CONTROL WIRING 7 8 HOLE Table 8 Electrical Power K...

Страница 17: ...ent clearances been provided 2 Has all foreign matter been removed from the interior of the unit tools construction or shipping materials etc 3 Have the condenser fans been rotated manually to check f...

Страница 18: ...minute If it fails to close the unit will shut down the associated compressor and begin an ASCD If the call for cool is still present at the end of the anti short cycle time delaying the control boar...

Страница 19: ...of System 2 When the LPS of UCB 2 falls below its cut out point the PR2 relay brings on the 3LLS Solenoid allowing refrigerant in system 2 to return flow to the compressor for normal mechanical coolin...

Страница 20: ...enance consists of changing or cleaning filters and general cleaning of the outdoor coil MOTORS Outdoor fan motors are permanently lubricated and require no maintenance OUTDOOR COIL Dirt should not be...

Страница 21: ...cursor is on the top Status line hit the ENTER button This action steps the LCD display into the status mode Hit ENTER to view the status menu Press Enter Step 2 Scroll down to DVent Mode This is the...

Страница 22: ...CANCEL JOY C PWR 7 7 77 Clg Engaged LeadLag Engaged Press Enter Joy Stick Down 2 Step 6 By toggling down twice the screen reaches the ClgOcc SP screen or Cooling Occupied Set Point ENTER CANCEL JOY C...

Страница 23: ...mostat connection strip C and indoor blower VFD pin C 24V 24 VAC 75 VA transformer hot Powers the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for facto...

Страница 24: ...hing in series Unit wiring harness jumper plug for factory shutdown accessories must be removed if the switching of field added external accessories for unit shutdown are wired between thermo stat con...

Страница 25: ...ut from 10K 77 F Type III negative temperature coefficient thermistor Input required for 2 compressor heat pump units not required for 2 compressor A C units not active for 1 compressor units 3 625 VD...

Страница 26: ...no input within 5 minutes from initiation of H1 output initiates an Ignition Failure alarm input for longer than 5 minutes without H1 output initiates a Gas Valve Mis wire alarm Pin Cooling and fan o...

Страница 27: ...put is needed input must be present to allow FAN output and unit operation One FAN OVR trip lasting longer than 5 minutes or three FAN OVR trips in a two hour period cause a Fan Overload Lockout and u...

Страница 28: ...munication circuit COM Common for the FC Field Connected BUS BACnet MSTP communication circuit Negative of the VDC FC bus BACnet MSTP communication circuit SHLD Shield for the FC Field Connected BUS B...

Страница 29: ...with the TXV s left to the factory setting If the TXV s have been adjusted in the field the charging chart may no longer apply Outdoor Air Entering Condenser F 300 350 400 450 500 550 600 120 130 140...

Страница 30: ...scharge Pressure psi Suction Pressure psi Charging Curves 50 Ton 115 105 95 85 65 1 Make sure that all condenser fans are running when charging 2 This chart is applicable to unit with the TXV s left t...

Страница 31: ...5012886 YIM B 0517 Johnson Controls Unitary Products 31 Typical Wiring Diagrams Figure 17 Typical 208 230 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Страница 32: ...5012886 YIM B 0517 32 Johnson Controls Unitary Products Typical Wiring Diagrams Figure 18 Typical 460 575 Volt YD360 480 600 Condensing Unit Wiring Diagram...

Страница 33: ...ocedures are followed and checks are made at initial start up This confidence is supported by the 30 day dealer protection coverage portion of our standard warranty policy which states that Johnson Co...

Страница 34: ...he equipment If the system is a VAV system the CFM will be the airflow when the remote VAV boxes are in the full open position and the frequency drive is operating at 60 HZ Do not proceed with the equ...

Страница 35: ...ystem 2 Is Condenser below Evaporator Yes No Yes No Total Line Length end to end _______ Ft _______ Ft Vertical Lift in Ft _______ Ft _______ Ft Vertical Fall in Ft _______ Ft _______ Ft Number of Elb...

Страница 36: ...t or change required to obtain the correct airflow Was it necessary to increase of decrease the airflow to meet the design conditions If the motor pulley size was changed measure the outside diameters...

Страница 37: ...hird if equipped Fourth if equipped Heat Pump 1st Stage Outside air temperature ________________ db F ________________ wb F ________________ RH Return Air Temperature ________________ db F ___________...

Страница 38: ..._______________________________ ________________________________________________________________________________________________________ _______________________________________________________________...

Отзывы: