JOHNSON CONTROLS
FORM 150.26-EG1 (116)
20
Or combine the two formulas:
Cond. Water GPM =
Condenser Tons x 30
Condenser Water Range (ºF)
SAMPLE SELECTION
Water Cooled Chiller (YCWL)
GIVEN
– Chill 200 GPM of water from 56ºF to 44ºF and 0.0001 evaporator fouling factor
with 85ºF to 95ºF condensing water available. The fouling factor is 0.0005 for the con-
denser.
FIND
– The required unit size capacity, kW, EER, and water pressure drop.
SOLUTION:
1. Chilled water range = 56ºF - 44ºF = 12ºF and correction factors are 1.009 for Tons
and 1.001 for kW for the evaporator.
Capacity (Tons) =
GPM x Chilled Water Range
24
=
200 x 12
24
= 100TR
2. From the rating, a model YCWL01180SE has a capacity range required. For the
evaporator leaving water temperature of 44ºF and a condenser leaving water tem-
perature of 95ºF, the unit capacity rating table indicates:
Tons
=
108.4
KW
=
83.5
EER
=
15.6
Correcting for the 12ºF chilled water range and the 0.0005 condenser-fouling fac
tor (Correction factors for the condenser are 0.995 for Tons and 1.010 for kW):
Tons = 108.4 x 1.009 x 0.995 = 108.8TR
KW
= 83.5 x 1.001 x 1.010 = 84.4 kW
Selection Data (Cont'd)
Содержание YCWL Series
Страница 4: ...JOHNSON CONTROLS FORM 150 26 EG1 116 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 43: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 43 Unit Dimensions Four Compressor Cont d ...
Страница 45: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 45 Unit Dimensions Five Six Compressor Cont d ...
Страница 47: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 47 Unit Dimensions SI Four Compressor Cont d ...
Страница 49: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 49 Unit Dimensions SI Five Six Compressor Cont d ...
Страница 64: ...JOHNSON CONTROLS FORM 150 26 EG1 116 64 Typical Control Panel Wiring 4 COMPRESSOR UNITS LD18412 ...
Страница 65: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 65 Typical Control Panel Wiring Cont d 4 COMPRESSOR UNITS ...
Страница 66: ...JOHNSON CONTROLS FORM 150 26 EG1 116 66 5 6 COMPRESSOR UNITS Typical Control Panel Wiring Cont d LD18413 ...
Страница 67: ...FORM 150 26 EG1 116 JOHNSON CONTROLS 67 Typical Control Panel Wiring Cont d 5 6 COMPRESSOR UNITS ...