![York YCUL0045E Скачать руководство пользователя страница 81](http://html1.mh-extra.com/html/york/ycul0045e/ycul0045e_installation-operation-and-maintenance_4223692081.webp)
JOHNSON CONTROLS
81
FORM 150.63-NM8 (1020)
2
OPTION 3 – AMBIENT CONTROL TYPE:
(YCUL0045-0255 ONLY)
A M B I E N T C O N T R O L
S T A N D A R D
The low ambient cutout is adjustable from 25°F to 60°F
(-3.9°C to 15.6°C).
or
A M B I E N T C O N T R O L
L O
W A
M
B I E N T
The low ambient cutout is programmable down to 0°F
(-17.8°C).
A low ambient kit MUST be installed for
this option to be chosen. If the kit is NOT installed,
and low ambient is selected, low pressure faults and
compressor damage may occur.
OPTION 4 – LOCAL/REMOTE CONTROL TYPE:
L O C A L / R E M O T E M O D E L
L O
C A L
When programmed for LOCAL, an ISN or RCC control
can be used to monitor only. The micro panel will operate
on locally programmed values and ignore all commands
from the remote devices. The chiller will communicate
and send data to the remote monitoring devices.
or
L O C A L / R E M O T E M O D E
R E
M
O T E
This mode should be selected when an ISN or RCC
control is to be used to control the chiller. This mode will
allow the ISN to control the following items: Remote
Start/Stop, Cooling Setpoint, Load Limit, and History
Buffer Request. If the unit receives no valid ISN trans
-
mission for 5 minutes, it will revert back to the locally
programmed values.
OPTION 6 – UNIT CONTROL MODE:
C O N T R O L M O D E
S U C T I O N P R E S S U R E
Unit control is based on Suction Pressure Control.
or
C O N T R O L M O D E
D I S C H A R G E A I R
Unit control is based on Discharge Air Temp. Control.
OPTION 6 – DISPLAY UNITS:
This mode displays system operating values in Imperial
units of °F or PSIG.
or
This mode displays system operating values in Scientific
International Units of °C or BARG.
OPTION 7 - LEAD/LAG TYPE (two system units
with Discharge Air Temp Control only):
SYS 1 selected as lead compressor. SYS 1 lead option
MUST be chosen if Hot Gas Bypass is installed.
or
SYS 2 selected as lead compressor.
or
Lead/lag between systems may be selected to help equal-
ize average run hours between systems on chillers with 2
refrigerant systems. Auto lead/lag allows automatic lead/
lag of the two systems based on an average run hours of
the compressors in each system. A new lead/lag assign-
ment is made whenever all compressors shut down. The
micro will then assign the “lead” to the system with the
shortest average run time.
OPTION 8 - CONDENSER FAN CONTROL MODE
(YCUL0045-0255 Only):
Condenser fans are controlled by discharge pressure
only. This mode may only be chosen when discharge
pressure transducers are installed.
or
D I S P L A Y U N I T S
I M
P E R I A L
D I S P L A Y U N I T S
S I
L E A D / L A G C O N T R O L
M A N U A L S Y S 1 L E A D
L E A D / L A G C O N T R O L
M A N U A L S Y S 2 L E A D
L E A D / L A G C O N T R O L
A U T O
M
A T I C
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Содержание YCUL0045E
Страница 8: ...JOHNSON CONTROLS 8 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...JOHNSON CONTROLS 113 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 115: ...JOHNSON CONTROLS 115 FORM 150 63 NM8 1020 4...
Страница 119: ...JOHNSON CONTROLS 119 FORM 150 63 NM8 1020 4...
Страница 121: ...JOHNSON CONTROLS 121 FORM 150 63 NM8 1020 4...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 63 NM8 1020 4...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 63 NM8 1020 4...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 63 NM8 1020 4...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 63 NM8 1020 4...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 63 NM8 1020 4...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 63 NM8 1020 4...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 141: ......
Страница 142: ...NOTES...
Страница 143: ...NOTES...