JOHNSON CONTROLS
78
FORM 150.63-NM8 (1020)
UNIT CONTROLS
460VAC SYSTEM TRIP VOLTS
For individual system high current trip programming
on 460VAC chillers:
• Add the sum of the compressor and fan RLA’s in
the system
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be pro-
grammed
For example, if fan and compressor RLA’s total 100A:
5V x 100A
x 1.25 =
625VA
= 2.8V
225A 225A
The programmed value will be 2.8V. A similar calcula
-
tion and programming will be necessary for the other
system in a 2-system chiller.
460VAC UNIT TRIP VOLTS
For total chiller high current trip programming on
460VAC chillers:
• Add the sum of all the compressor and fan RLA’s
in the chiller
TABLE 16 –
PROGRAM KEY LIMITS AND DEFAULTS
*
The minimum discharge pressure allowed is 160 PSIG. The fan differential Off Pressure will be lowered to prevent going below 160
PSIG based on where the fan control On Pressure is programmed.
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
--
200 PSIG
399 PSIG
395 PSIG
13.8 BARG
27.5 BARG
27.2 BARG
SUCTION PRESSURE CUTOUT
WATER COOLING
44.0 PSIG
70.0 PSIG
44.0 PSIG
3.03 BARG
4.83 BARG
3.03 BARG
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
ANTI-RECYCLE TIMER
--
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON PRESSURE
--
225 PSIG
300 PSIG
240 PSIG
15.5 BARG
20.7 BARG
16.5 BARG
FAN DIFFERENTIAL OFF PRESSURE
--
50 PSIG
100 PSID*
80 PSID
3.45 BARG
6.89 BARG*
5.52 BARG
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
TWO SYSTEMS
4
6
6
UNIT/SYSTEM TRIP VOLTS
CURRENT FEEDBACK
OPTION ENABLED
ONE PER UNIT
0.5
4.5
2
REMOTE UNIT ID
--
0
7
0
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be pro-
grammed
For example, if fan and compressor RLA’s total 180A:
5V x 180A
x 1.25 =
1125VA
= 5.0V
225A 225A
The programmed value will be 5.0V.
208/230VAC CHILLERS
On 208/230VAC chillers, the process is similar, but
instead of performing the calculation using 225A, a
number of 450A must be substituted.
When communications is required with a BAS or
OptiView Panel, individual unit IDs are necessary for
communications with specific chillers on a single RS-
485 line. ID 0-7 is selectable.
R E M O T E U N I T I D
P R O G R A M M E D = X
Содержание YCUL0045E
Страница 8: ...JOHNSON CONTROLS 8 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...JOHNSON CONTROLS 113 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 115: ...JOHNSON CONTROLS 115 FORM 150 63 NM8 1020 4...
Страница 119: ...JOHNSON CONTROLS 119 FORM 150 63 NM8 1020 4...
Страница 121: ...JOHNSON CONTROLS 121 FORM 150 63 NM8 1020 4...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 63 NM8 1020 4...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 63 NM8 1020 4...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 63 NM8 1020 4...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 63 NM8 1020 4...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 63 NM8 1020 4...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 63 NM8 1020 4...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 141: ......
Страница 142: ...NOTES...
Страница 143: ...NOTES...