37
-A- Antifreeze
-C- Compressor configuration
DESCRIPCIÓN
RANGE
UNIT
VALUE
Antifreeze alarm set point
-99.9/99.9
°C
3
Antifreeze alarm dif. set point
99.9
°K
5
Antifreeze alarm set point, lower limit
-99.9/99.9
°C
3
Antifreeze alarm set point, upper limit
-99.9/99.9
°C
5
Antifreeze alarm reset
MANUAL
AUTOMATIC
-
MANUAL
Antifreeze alarm delay (if auto. reset is selected)
0/540
min.
0
Activation set point, antifreeze heater
-99.9/99.9
°C
3
Activation dif. set point, antifreeze heater
-99.9/99.9
°K
2
Backup heater set point (winter cycle)
-99.9/99.9
°C
25
Backup heater dif. set point (winter cycle)
-99.9/99.9
°K
5
Backup heater activation delay
0/60
min.
15
Automatic activation of antifreeze system with the unit OFF
DISABLED
HEATER & PUMP
HEATER & UNIT
HEATER
-
HEATER
DESCRIPTION
RANGE
UNIT
VALUE
Min. compressor ON time
0/9999
sec.
120
Min. compressor OFF time
0/9999
sec.
60
Time between starts of different compressors
0/9999
sec.
3
Time between starts of one compressor
0/9999
sec.
300
Time between starts of pump and compressor
0/999
sec.
20
Time between compressor and pump OFF
0/999
sec.
20
Run hours, pump 1
Run hours, pump 2
Run hours, compressor 1
Run hours, compressor 2
Run hours, compressor 3
Run hours, compressor 4
Run hours for pump maintenance warning
1000/999000
hours
2x1000
Clear pump run hours
Operating hours for maintenance warning of compressor 1 / circuit 1
1000/999000
hours
2x1000
Clearing of operating hours of compressor 1 / circuit 1
Operating hours for maintenance warning of compressor 2 / circuit 1
1000/999000
hours
2x1000
Clearing of operating hours of compressor 2 / circuit 1
Operating hours for maintenance warning of compressor 1 / circuit 2
1000/999000
hours
2x1000
Clearing of operating hours of compressor 1 / circuit 2
Operating hours for maintenance warning of compressor 2 / circuit 2
1000/999000
hours
2x1000
Clearing of operating hours of compressor 2 / circuit 2
Rotational time of tandem compressors
min.
20
Enable compressors C
1
/
1
, C
2
/
1
, C
1
/
2
and C
2
/
2
Y/N
Y
Forced manual operation of compressors
Y/N
N
Содержание YCSA 120 T
Страница 2: ......
Страница 4: ......
Страница 23: ...23 Minimum technical clearance ...
Страница 24: ...24 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Страница 26: ...26 Wiring diagram YCSA YCSA H 120 µC3 400 3 50 ...
Страница 27: ...27 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Страница 29: ...29 Wiring diagram YCSA YCSA H 150 µC3 400 3 50 ...
Страница 30: ...30 Wiring YCSA YCSA H 120 and 150 T TP ...
Страница 35: ...35 General wiring diagram ...
Страница 48: ...www johnsoncontrols com ...