FORM 201.25-NM1 (302)
59
YORK INTERNATIONAL
5.8 LOCAL PRINTER OPTION
The Micro Panel is capable of supplying a printout of
chiller conditions or fault shutdown information at any
given time. This allows operator and service personnel
to obtain data and system status with the touch of the
keypad. In addition to manual print selection, the mi-
cro panel will provide an automatic printout whenever
a fault occurs. An explanation of the keypad use to ob-
tain a printout is discussed in the “PRINT” KEY Sec-
tion on Page 52.
YORK recommends the field tested WEIGH-TRONIX
IMP-24, Model 2600 printer. This is a compact low cost
printer that is ideal for service work and data logging.
Paper is in the form of a compact roll and is easily
handled compared to larger printers using wider busi-
ness form style paper. The paper is 2.25” wide desktop
calculator paper that can be easily and inexpensively
purchased at most stationery stores. Shown in Fig. 17
and 18 is the WEIGH-TRONIX printer and a typical
sample printout.
The WEIGH-TRONIX IMP-24 Model 2600 printer can
be purchased for approximately $150.00. Contact
Weigh-Tronix for purchase information:
Weigh-Tronix
2320 Airport Blvd.
Santa Rosa, Ca. 95402
Phone: 1-800-358-9110 or 1-707-527-5555
(International Orders Only)
The printout is made to be universal
to all types of chillers both air and wa-
ter cooled with or without options.
Items may be indicated on the print-
out which may not be present on the
chiller.
Installation Limitations
The following limitations must be adhered to. Failure
to do so may result in improper printer and/or chiller
operation.
1. The printer option is adaptable to all versions and
revisions of Microprocessor boards and EPROMs.
No modifications are necessary to the panel.
2. Maximum cable length between the printer and the
Microprocessor Board is 25 feet. Twisted pair
shielded cable is required.
3. The printer must be supplied a 115VAC source.
4. The printer may be left connected to the micro panel.
FIG. 17 –
WEIGH-TRONIX IMP-24 MODEL 2600
PRINTER
FIG. 18 –
PRINTOUT
23899A
YORK INTERNATIONAL CORPORATION
RECIPROCATING WATER CHILLERS
SYSTEM STATUS
8:45AM 6/3/98
SYS 1
COMPRESSOR RUNNING
SYS 2
ANTI-COIN TIMER 13 SEC
RETURN WATER TEMP
65.0 DEGF
LEAVING WATER TEMP
54.0 DEGF
LOW WATER CUTOUT
36.0 DEGF
SETPOINT TEMP
45.0 DEGF
OUTSIDE AIR TEMP
75.0 DEGF
LOW AMBIENT CUTOUT
10.0 DEGF
LOW PRESSURE CUTOUT
4 4 PSIG
LEAD SYSTEM
SYS 1
CONTROL TYPE
LCHWT
COOLING RANGE
45.0 TO 47.0 DEGF
SYSTEM 1 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
50 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
143 PSIG
OIL PRESSURE
75 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
OFF
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
SYSTEM 2 DATA
COMPRESSOR STATUS
ON
MOTOR AMPS
0 %FLA
SUCTION PRESSURE
61 PSIG
DISCHARGE PRESSURE
80 PSIG
OIL PRESSURE
1 PSID
LIQUID LINE SOLENOID
OFF
RUN PERMISSIVE
ON
STAGES OF LOADING
1
FORWARD FANS
1
REVERSE FANS
OFF
HOT GAS BYPASS VALVE
OFF
S M T W T F S
✱
=HOLIDAY
SUN
START=06:00AM
STOP=11:00PM
MON START=06:00AM
STOP=11:00PM
TUE
START=06:00AM
STOP=11:00PM
WED START=06:00AM
STOP=11:00PM
THU
START=06:00AM
STOP=11:00PM
FRI
START=06:00AM
STOP=11:00PM
SAT
START=06:00AM
STOP=11:00PM
HOL
START=00:00AM
STOP=00:00AM
7