JOHNSON CONTROLS
FORM 201.23-EG1 (1013)
49
Contact your nearest Johnson Controls Sales Office for weight data.
REFRIGERANT R-134A
STANDARD EFFICIENCY
MODEL NUMBER (YCIV____ S/P)
GENERAL UNIT DATA
60Hz
0287
0307
0357
0397
0457
NUMBER OF INDEPENDENT REFRIGERANT CIRCUITS
3
3
3
3
4
REFRIGERANT CHARGE, R-134A, CKT.-1/CKT.-2, LBS
185/170/170
185/185/170
185/185/230
230/230/230
310/310/300/300
OIL CHARGE, CKT.-1/CKT.-2, GAL.
5/4/4
5/4/4
5/5/5
5/5/5
5/5/5/5
GLYCOL CHARGE (43% CONCENTRATION), GAL
5.4
5.5
6.0
6.3
4.3
COMPRESSORS, SEMI-HERMETIC SCREW QTY PER CHILLER
3
3
3
3
4
CONDENSERS, HIGH EFFICIENCY FIN/TUBE WITH INTEGRAL SUBCOOLER
TOTAL CHILLER COIL FACE AREA, FT
2
381
411
469
528
528
NUMBER OF ROWS
3
3
3
3
4
FINS PER INCH
17
17
17
17
17
CONDENSER FANS
NUMBER, CKT.-1/CKT.-2
5/4/4
5/4/4
5/5/6
6/6/6
6/6/3/3
LOW NOISE FANS
FAN MOTOR, HP/KWI
2/1.8
2/1.8
2/1.8
2/1.8
2/1.8
TOTAL CHILLER AIRFLOW, CFM
169000
182000
208000
234000
234000
ULTRA QUIET FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
2/1.5
TOTAL CHILLER AIRFLOW, CFM
169000
182000
208000
234000
234000
DUAL SPEED FANS - NORMAL SPEED
FAN MOTOR, HP
2
2
2
2
2
TOTAL CHILLER, CFM
143000
143000
165000
165000
165000
DUAL SPEED FANS - LOWER SPEED
FAN MOTOR, HP
2
2
2
2
2
TOTAL CHILLER, CFM
109200
109200
126000
126000
126000
HIGH STATIC FANS
FAN MOTOR, HP
5
5
5
5
5
TOTAL CHILLER, CFM
169000
182000
208000
234000
234000
EVAPORATOR, DIRECT EXPANSION
WATER VOLUME, GALS.
202.0
236.0
236.0
236.0
318
MAXIMUM WATER SIDE PRESSURE, PSIG
150
150
150
150
150
MAXIMUM REFRIGERANT SIDE PRESSURE, PSIG
235
235
235
235
235
MINIMUM CHILLED WATER FLOW RATE, GPM
250
300
300
300
400
MAXIMUM CHILLED WATER FLOW RATE, GPM
1200
1200
1200
1200
1400
WATER CONNECTIONS, INCHES
10
10
10
10
10
Содержание YCIV0157E/V
Страница 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Страница 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Страница 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Страница 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Страница 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Страница 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Страница 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Страница 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Страница 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Страница 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Страница 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Страница 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Страница 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Страница 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Страница 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Страница 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...