JOHNSON CONTROLS
FORM 201.21-NM2 (616)
HISTORY KEY (CON'T)
Remote Temperature Reset
One of the 5 messages below indicates whether remote
temperature reset was active or disabled at the chiller
keypad at the time of the fault. If active, the type of reset
signal selected is indicated. If the option is not factory
enabled, the option will not appear.
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
4.0 TO 20.0 MILLIAMPS
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
0.0 TO 20.0 MILLIAMPS
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
2.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
0.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE TEMP RESET INPUT
◄ ►
DISABLED
PROGRAM
SUCTION PRESSURE CUTOUT = XXX.X PSIG
PROGRAM
LOW AMBIENT TEMP CUTOUT = XXX.X °F
PROGRAM
LEAVING LIQUID TEMP CUTOUT = XXX.X °F
Low Ambient Temp Cutout
OPTIONS
LOW AMBIENT TEMP CUTOUT
◄ ►
XXXXXXXXXXXXXXXXXXXX
This message indicates whether the low ambient cutout
was enabled or disabled at the time of the fault.
Remote Current Reset
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
4.0 TO 20.0 MILLIAMPS
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
0.0 TO 20.0 MILLIAMPS
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
2.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
0.0 TO 10.0 VOLTS DC
OPTIONS
REMOTE CURRENT LIMIT INPUT
◄ ►
DISABLED
This message indicates whether remote current reset
was active or disabled at the chiller keypad at the time
of the fault and if active, the type of reset signal selected.
One of the following messages will be indicated: DIS-
ABLED (no signal), 0-10VDC, 2-10VDC, 0-20ma, and
4-20ma. If the option is not factory enabled, the option
will not appear.
PROGRAM VALUES
Suction Pressure Cutout
This message indicates the he suction pressure cutout
programmed at the time of the fault.
Low Ambient Cutout
This message displays the low ambient temp cutout
programmed at the time of the fault.
Low Leaving Chilled Liquid Temp Cutout
This message displays the low leaving Chilled liquid
temperature cutout programmed at the time of the
fault.
Motor Current Limit
PROGRAM
MOTOR CURRENT LIMIT
= XXX %FLA
This message indicates the motor current limit pro-
grammed at the time of the fault.
8
Содержание YCAV0569
Страница 43: ...43 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Страница 51: ...51 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Страница 53: ...53 JOHNSON CONTROLS FORM 201 21 NM2 616 ELEMENTARY CONTROL WIRING DIAGRAM CON T 6 LD12519...
Страница 57: ...57 JOHNSON CONTROLS FORM 201 21 NM2 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12515...
Страница 59: ...59 JOHNSON CONTROLS FORM 201 21 NM2 616 CONNECTION WIRING DIAGRAM 2 COMPRESSOR YCAV CHILLER CON T 6 LD12513...
Страница 60: ...60 JOHNSON CONTROLS FORM 201 21 NM2 616 LOCATION LABEL LD10519 TECHNICAL DATA...
Страница 61: ...61 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Страница 91: ...91 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 6...
Страница 107: ...107 JOHNSON CONTROLS FORM 201 21 NM2 616 FIG 15 VSD LOGIC BOARD LD10582 COMPONENT LOCATIONS CON T 6 VSD LOGIC BOARD...
Страница 179: ...179 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This Page Intentionally Left Blank...
Страница 201: ...201 JOHNSON CONTROLS FORM 201 21 NM2 616 This page intentionally left blank 8...
Страница 221: ...221 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...
Страница 249: ...249 JOHNSON CONTROLS FORM 201 21 NM2 616 8 This page intentionally left blank...