YORK INTERNATIONAL
6
FORM 201.19-W3 (1104)
ELECTRICAL DATA
MULTIPLE POINT POWER SUPPLY CONNECTION
Two fi eld provided power sup ply cir cuits to the unit.
Field Power Wiring connections to fac to ry provided,
Non-Fused Dis con nect Switches (Opt), Circuit Breakers
(Opt) or Ter mi nal Blocks (Opt).
Suitable for:
Y -
∆
Start and
Across-The-Line-Start
MULTIPLE POINT POWER SUPPLY CONNECTION - 2 COMPRESSOR UNITS
(Two Field Provided Power Supply Circuits To The Chiller. Field Connections to Factory Provided Terminal Block (Std), Disconnects (Opt),
or Individual System Circuit Breakers (Opt) in each of the two Motor Control Centers.)
LD05548
See page 4 for notes.
Options:
Term. Block
NF Disc SW
or Circ Brkr
1T
Control
Transformer
GRD
2 L
CTB
Options:
Term. Block
NF Disc SW
or Circ Brkr
GRD
CIRCUIT #1
CIRCUIT # 2
FIELD PROVIDED
UNIT POWER SUPPLY
FIELD PROVIDED
UNIT POWER SUPPLY
STD FIELD PROVIDED
120-1-60Hz POWER SUP-
PLY (NOT REQUIRED IF
OPTIONAL CONTROL
TRANSFORMER FITTED)
OPTIONAL CONTROL
TRANSFORMER
SEE NOTE 3
SEE NOTE 3
0373 380 148 150 200 250 # 2 - 4/0 # 4 - 300 # 6 - 350 108 241 761 3 4.4 17.1
0403 380 160 200 200 250 # 2 - 4/0 # 4 - 300 # 6 - 350 118 241 761 3 4.4 17.1
0453 380 188 200 225 300 1/0 - 300 # 6 - 350 # 6 - 350 140 309 979 3 4.4 17.1
0503 380 215 250 300 350 1/0 - 300 # 6 - 350 (2) 3/0-250 161 309 979 3 4.4 17.1
0543 380 193 200 250 300 1/0 - 300 # 6 - 350 # 6 - 350 141 309 979 4 4.4 17.1
0573 380 227 250 300 350 2/0 - 500 # 6 - 350 (2) 3/0-250 168 309 979 4 4.4 17.1
0623 380 247 250 300 400 2/0 - 500 # 6 - 350 (2) 3/0-250 183 309 979 4 4.4 17.1
0653 380 232 250 300 350 2/0 - 500 # 6 - 350 (2) 3/0-250 168 309 979 5 4.4 17.1
Model
Volts MRA
1
Min. NF
Protection
13
Factory Provided (Lugs) Wire Range
7
Compressor Fans
11, 12
YCAS
(MCA)
Disc. Sw.
2, 9
Min.
3, 5
Max.
4, 6
*Standard Terminal *Optional NF. Optional
RLA Y-LRA X-LRA Qty.
FLA LRA
Block Disc Switch Circuit Breaker (Ea.) (Ea.)
Overcurrent
*
“Optional” Circuit Breakers are REQUIRED for units with CE mark.
See page 4 for Electrical Data Notes.
SYSTEM #1 FIELD SUPPLIED WIRING
Содержание YCAS Series
Страница 5: ...YORK INTERNATIONAL 5 FORM 201 19 W3 1104 This page intentionally left blank...
Страница 20: ...YORK INTERNATIONAL 20 FORM 201 19 W3 1104 ELEMENTARY DIAGRAM FIG 6 ELEMENTARY DIAGRAM WYE DELTA START LD09480...
Страница 25: ...YORK INTERNATIONAL 25 FORM 201 19 W3 1104 LEGEND LD010027...
Страница 26: ...YORK INTERNATIONAL 26 FORM 201 19 W3 1104 LD03282 LD03283 LD03284 035 15164 102 REV E...
Страница 31: ...YORK INTERNATIONAL 31 FORM 201 19 W3 1104 NOTES...