HIGH ENGINE TEMPERATURE OVERRIDE
PV
Process variable; actual engine temperature in ºF
Output
Control variable output signal from 0 to 100%
The following tables list the default factory values for
the PID control loops.
CHILLED WATER OUT TEMPERATURE
SPEED
PRV
HGV
P
0.400
0.300
0.500
I
0.060
0.102
0.103
D
0.000
0.000
0.000
Setpoint Ramp Rate:
0.5 ºF/sec
LOW PRESSURE OVERRIDE
Setpoint:
28.0 psig
P:
1.000
I:
2.000
D:
0.000
ENGINE LOAD LIMITER
Setpoint:
100.0
P:
0.800
I:
1.500
D:
0.000
HIGH PRESSURE OVERRIDE
Setpoint:
175.0
P:
1.000
I:
2.000
D:
0.005
HIGH ENGINE TEMPERATURE OVERRIDE
Setpoint:
190.0
P:
0.900
I:
2.000
D:
0.000
ADDITIONAL ENTRY FIELDS
HGV Ramp Time:
60.0 sec
PRV Minimum Start Position:
2.0%
PRV Ramp Time:
100.0 sec
PRV Response Gain:
4800
PanelView Plus 1000 Control Center