13
Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Ext
Loop
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA*
026
208-230/60/1
187/253
18.2
11.6
58.3
21.0
5.4
17.0
19.9
30
038
208-230/60/1
187/253
23.8
15.2
83.0
30.0
5.4
20.6
24.4
40
049
208-230/60/1
187/253
33.0
21.1
104.0
37.0
5.4
26.5
31.8
50
064
208-230/60/1
187/253
42.3
27.1
152.9
54.0
5.4
32.5
39.3
70
072
208-230/60/1
187/253
46.3
29.6
179.2
63.0
5.4
35.0
42.4
75
7/10/13
Rated voltage of 208-230/60/1.
HACR circuit breaker in USA only.
Min/Max voltage of 187/253.
All fuses Class RK-5
* With optional GeoStart