60
Operating Parameters
Single Speed Models
Entering Water
Temp °F
Water Flow
gpm/ton
Cooling -- No Hot Water Generation
Suction Pressure
psig
Discharge
Pressure psig
Superheat
Subcooling
Water Temp Rise
°F
Air Temp Drop
°F DB
30
1.5
115 - 125
150 - 170
20 - 35
10 - 17
17 - 22
17 - 23
3.0
105 - 120
130 - 145
20 - 35
10 - 17
8 - 10
17 - 23
50
1.5
130 - 140
215 - 235
12 - 20
8 - 14
16 - 22
17 - 23
3.0
128 - 138
190 - 210
12 - 20
8 - 14
8 - 12
17 - 23
70
1.5
138 - 148
280 - 310
10 - 16
10 - 16
15 - 21
17 - 23
3.0
136 - 146
250 - 280
10 - 16
8 - 14
7 - 13
17 - 23
90
1.5
145 - 155
350 - 380
9 - 14
10 - 16
14 - 20
17 - 23
3.0
143 - 153
320 - 350
9 - 14
8 - 14
6 - 10
17 - 23
110
1.5
145 - 155
420 - 450
9 - 14
10 - 16
14 - 20
17 - 23
3.0
143 - 153
405 - 435
9 - 14
8 - 14
6 - 10
17 - 23
Entering Water
Temp °F
Water Flow
gpm/ton
Heating - No Hot Water Generation
Suction Pressure
psig
Discharge
Pressure psig
Superheat
Subcooling
Water Temp Drop
°F
Air Temp Rise
°F DB
30
1.5
73 - 85
270 - 305
8 - 14
3 - 10
6 - 10
15 - 21
3.0
77 - 90
280 - 315
8 - 14
3 - 10
4 - 8
17 - 23
50
1.5
97 - 110
290 - 325
10 - 16
3 - 10
9 - 13
22 - 28
3.0
102 - 115
300 - 335
10 - 16
3 - 10
7 - 11
24 - 30
70
1.5
130 - 145
320 - 355
13 - 19
3 - 10
10 - 14
30 - 36
3.0
135 - 150
325 - 360
13 - 19
3 - 10
8 - 12
32 - 38
90
1.5
150 - 160
350 - 390
13 - 19
3 - 10
10 - 14
30 - 36
3.0
155 - 165
365 - 405
13 - 19
3 - 10
8 - 12
32 - 38
110
1.5
3.0
NOTE:
Cooling performance based on entering air temperatures of 80° F DB, 67° F WB.
Heating performance based on entering air temperature of 70° F DB.
2/15/12
Unit Startup cont.
AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Startup Steps
NOTE:
Complete the Equipment Start-Up/Commissioning Check
Sheet during this procedure. Refer to thermostat operating
instructions and complete the startup procedure. Verify that the
compressor shipping bolt has been removed.
1. Initiate a control signal to energize the blower motor. Check
blower operation through the AID Tool.
2. Initiate a control signal to place the unit in the cooling mode.
Cooling setpoint must be set below room temperature.
3. First stage cooling will energize after a time delay.
4. Be sure that the compressor and water control valve or loop
pump(s) are activated.
5. Verify that the water flow rate is correct by measuring the
pressure drop through the heat exchanger using the P/T plugs
and comparing to unit performance data in catalog.
6. Check the temperature of both the supply and discharge water
(see the Unit Operating Parameters tables).
7. Check for an air temperature drop of 15°F to 25°F across the air
coil, depending on the fan speed and entering water temperature.
8. Decrease the cooling set point several degrees and verify high-
speed blower operation.
9. Adjust the cooling setpoint above the room temperature and verify
that the compressor and water valve or loop pumps deactivate.
10. Initiate a control signal to place the unit in the heating mode.
Heating set point must be set above room temperature.
11. First stage heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water
(see the Unit Operating Parameters tables).
13. Check for an air temperature rise of 12°F to 35°F across the air
coil, depending on the fan speed and entering water temperature.
14. If auxiliary electric heaters are installed, increase the heating
setpoint until the electric heat banks are sequenced on. All
stages of the auxiliary heater should be sequenced on when the
thermostat is in the Emergency Heat mode. Check amperage of
each element.
15. Adjust the heating setpoint below room temperature and verify
that the compressor and water valve or loop pumps deactivate.
16. During all testing, check for excessive vibration, noise or water
leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set
temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the
thermostat and system maintenance.