Electrical Data
AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Single Speed Unit with Variable Speed ECM Motor
Model
Rated Voltage
Voltage
Min/Max
Compressor
HWG
Pump FLA
Ext
Loop
FLA
Blower
Motor FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
018
208-230/60/1
187/253
10.4
6.7
33.5
N/A
0.4
5.4
4.0
16.5
18.1
20
022
208-230/60/1
187/253
14.0
9.0
48.0
17.0
0.4
5.4
4.0
18.8
21.0
30
030
208-230/60/1
187/253
20.0
12.8
58.3
21.0
0.4
5.4
4.0
22.6
25.8
35
036
208-230/60/1
187/253
22.0
14.1
73.0
26.0
0.4
5.4
4.0
23.9
27.4
40
042
208-230/60/1
187/253
26.0
16.6
79.0
28.0
0.4
5.4
4.0
26.4
30.6
45
048
208-230/60/1
187/253
31.0
19.8
109.0
38.0
0.4
5.4
4.0
29.6
34.6
50
060
208-230/60/1
187/253
41.2
26.4
134.0
47.0
0.4
5.4
7.0
39.2
45.8
70
070
208-230/60/1
187/253
44.2
28.3
178.0
63.0
0.4
5.4
7.0
41.1
48.2
70
7/15/22
Single Speed Unit with 5-Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
HWG
Pump
FLA
Ext
Loop
FLA
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
022
208-230/60/1
187/253
14.0
9.0
48.0
17.0
0.4
5.4
4.1
18.9
21.1
30
030
208-230/60/1
187/253
20.0
12.8
58.3
21.0
0.4
5.4
4.1
22.7
25.9
35
036
208-230/60/1
187/253
22.0
14.1
73.0
26.0
0.4
5.4
4.1
24.0
27.5
40
042
208-230/60/1
187/253
26.0
16.6
79.0
28.0
0.4
5.4
7.6
30.0
34.2
50
048
208-230/60/1
187/253
31.0
19.8
109.0
38.0
0.4
5.4
7.6
33.2
38.2
50
060
208-230/60/1
187/253
41.2
26.4
134.0
47.0
0.4
5.4
7.6
39.8
46.4
70
070
208-230/60/1
187/253
44.2
28.3
178.0
63.0
0.4
5.4
7.6
41.7
48.8
70
7/15/13
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Single Speed Unit with PSC Motor
Model
Rated Voltage
Voltage
Min/Max
Compressor
HWG
Pump FLA
Ext
Loop
FLA
Blower
Motor FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
LRA**
012
208-230/60/1
187/253
7.7
4.9
25.0
N/A
-
5.4
0.6
10.9
12.2
15
07/15/22
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only