background image

22

Microprocessor Control cont.

Heating Operation

Heat, 1st Stage (Y1)

The blower motor is started on low speed immediately, the 
loop pump is energized 5 seconds after the “Y1” input is 
received, and the compressor is energized on low capacity 
10 seconds after the “Y1” input. The ECM blower is switched 
to medium speed 15 seconds after “Y1” input.

Heat, 2nd Stage (Y1,Y2) Dual Capacity Units

The second stage compressor will be activated 5 seconds 
after receiving a “Y2” input as long as the minimum first 
stage compressor run time of 1 minute has expired. The 
ECM blower changes from medium to high speed 15 
seconds after the “Y2” input. 

Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units

The 1st stage of resistance heat is energized 10 seconds 
after “W” input, and with continuous 3rd stage demand, the 
second stage of resistance heat will engage after 5 minutes.

Emergency Heat (W Only)

Low speed blower and damper output CR3 will be 
energized immediately after receiving (W only). The first 
stage auxiliary heater will be energized 10 seconds upon 
receiving a (W only) and the blower will shift to high speed 
15 seconds after receiving a “W” only input. If the “W” input 
is not removed, the second, auxiliary heat output will stage 
on, after two minutes.

Cooling Operation

Cool, 1st Stage (Y1,O) 

The blower is started immediately, and the loop pump(s) 
is energized 5 seconds after the “Y1” input is received. The 
compressor will be energized on low capacity 10 seconds 
after the “Y1” input. The ECM blower will shift from low to 
medium speed 15 seconds after the “Y1” input. 

Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units

The second stage compressor will be activated 5 seconds 
after receiving a “Y2” input as long as the minimum first stage 
compressor run time of 1 minute has expired. The ECM blower 
changes to high speed 15 seconds after the “Y2” input. 

Hydronic Cooling Slave Signal (24 vac input on 
P6-pin 15 violet wire)

The control board must be operating in cooling mode (Y1 
and O inputs) or the cooling slave signal is ignored. When 
“Y1”, and “O” inputs have been received and a cooling 
slave input from heating/cooling thermostat located in a 
hydronic heated/force air cooled zone are received the 
control will activate CR3 relay to open damper(s) which 
will allow for cooling to occur in zone. When cooling slave 
input (24VAC) signal is removed the control will turn off the 
CR3 relay output, if spring damper operation is selected, 
or activate, the  CR4 output if POPC damper operation is 
selected. This will close field installed damper(s) located in 
ductwork. NOTE: The control will not operate in forced air 
cooling and hydronic water heating modes simultaneously.

Hot Water Operation

After a hot water input is received, the diverting valve, loop 
pump and load water pump are turned on. Five seconds 
after hot water input is received the compressor is activated 
in second stage. Hydronic Mode Operation with Hydronic 
Priority Setting: If the control receives a demand to heat the 
space (Y1) from the thermostat during water heating mode 
operation, the control will engage medium ECM fan speed 
and the first stage auxiliary heat output. The second stage 
will be energized at five (5) minutes, following the first 
stage. The installer should set medium ECM fan speed for no 
less than the minimum required cfm for the installed electric 
heat package (see Auxiliary Heat Ratings table). 

Blower (G Only)

The blower starts on low speed. Regardless of blower input 
(G) from thermostat, the blower will remain on low speed 
for 30 seconds at the end of each heating, cooling or 
emergency heat cycle.

Lockout Conditions

During lockout mode the appropriate unit and thermostat 
lockout LEDs will illuminate. The compressor, loop pump, 
load water pump and accessory outputs are de-energized. 
Unless the lockout is caused by an ECM low RPM fault, 
the blower will continue to run on low speed, and if the 
thermostat calls for heating 3rd stage, emergency heat 
operation will occur.

Lockout modes can be reset at the thermostat after a five-
second waiting period, which restores normal operation 
but keeps the unit lockout LED illuminated. Interruption 
of power to the unit will reset a lockout without a waiting 
period and clear all lockout LEDs.

High Pressure

This lockout mode occurs when the normally closed safety 
switch is opened momentarily. >600 PSI

Low Pressure

This lockout mode occurs when the normally closed switch 
is opened for 30 continuous seconds. <40 PSI

Freeze Detection Limit (Water Flow)

This lockout mode occurs when the low source water 
thermistor temperature is at or below the selected point 
(well 30°F or loop 15°F) for 30 continuous seconds.

ECM Blower RPM

The control board monitors blower RPM to sense if the 
blower is not operating. This lockout mode occurs if the 
blower RPM falls below the low RPM limit (100 RPM) for 30 

continuous seconds.SW3-3 should be set to OFF (No RPM 

sensing) on this product. 

AFFINITY COMBINATION INSTALLATION MANUAL

Содержание YACT038-072

Страница 1: ...HRU 6 NOMINAL TONS Due to continuous product improvement specifications are subject to change without notice Visit us on the web at www york geothermal com Additional rating information can found at w...

Страница 2: ......

Страница 3: ...8 Physical Data 20 Microprocessor Control 21 Operation Logic 25 Wiring Schematics 26 Unit Startup 30 Operating Parameters 31 Pressure Drop 32 Compressor and Thermistor Resistance 33 Heat of Extraction...

Страница 4: ...neration Option 0 No HWG No IntelliStart 2 HWG w o Factory Installed Pump No IntelliStart 3 No HWG IntelliStart 5 HWG w o Factory Installed Pump IntelliStart Vintage Factory Use Only Controls Option S...

Страница 5: ...ctrical shock could cause serious personal injury CAUTION A minimum of 24 in clearance should be allowed for access to front access panel General Installation Information Vertical Unit Mounting Vibrat...

Страница 6: ...a ground loop system mate the brass connector supplied in CK4LI and CK4L GLI connector kits against the rubber gasket in the swivel connector and thread the female locking ring onto the pipe threads w...

Страница 7: ...ess than 125 ppm Less than 300 ppm Carbon Dioxide Less than 50 ppm 10 50 ppm 10 50 ppm Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm Ammonia Chloride Less than 0 5 ppm Less than 0 5 ppm Les...

Страница 8: ...freeze solution leave in Well position the factory setting Condensate Drain The internal condensate drain assembly consists of a drain tube which is attached to the drain pan a 3 4 in PVC female adapt...

Страница 9: ...ter External Pump Power flow through the unit by checking pressure drop across the heat exchanger Refer to Pressure Drop table Usually 2 5 3 gpm of flow per ton of cooling capacity is recommended in e...

Страница 10: ...e to Thermostat and Valve Unit Power Shut Off Valves to isolate solenoid valve while acid flushing Shut Off Valves Water Out Water In Solenoid Valve Flow Control Valve on outlet of Solenoid Valve P T...

Страница 11: ...aters are recommended Make sure all local electrical and plumbing codes are met for installing a hot water generator The unit is not supplied with an internal circulator A DPK5 kit will need to be pur...

Страница 12: ...ast fill valve is required for initial filling of the system Some have screens which must be cleaned after the initial filling If Hydronic Section there is a restriction in the screen the system could...

Страница 13: ...ommodate the hydronic load while the unit is operating in forced air mode The hydronic storage tank should be sized to provide 2 gallons of storage capacity for every one thousand Btuh s of nominal he...

Страница 14: ...the unit is to be used with an external loop pump FC1 or FC2 flow center the pump s will be connected to the terminals on PB1 in the unit electrical box as shown The pumps will automatically be cycle...

Страница 15: ...ns enclosed in the thermostat for detailed installation and operation information Other Thermostats The unit is compatible with virtually any 24VAC thermostat However the multi stage nature of this pr...

Страница 16: ...t Heater Amps Min Circuit Amp Max Fuse USA Max Fuse CAN Max CKT BRK 208V 240V 208V 240V 208V 240V 208V 240V 208V 240V EAL H 10A Single 34 7 40 53 3 60 60 60 60 60 60 60 EAL H 15A Single 52 0 60 75 85...

Страница 17: ...the DIP switches can be in the On position The first On switch the lowest position number determines the Low Speed Blower setting The second On switch determines the Medium Speed Blower setting and t...

Страница 18: ...Swivel 1 Swivel 1 2 Female 14 4 36 6 9 9 25 1 12 4 31 5 Condensate is 3 4 in PVC female glue socket and is switchable from side to front Unit shipped with deluxe 2 in field adjustable to 1 in duct col...

Страница 19: ...1 Swivel 1 2 Female 14 4 36 6 9 9 25 1 12 4 31 5 064 in cm 25 6 65 0 31 6 80 3 58 4 148 3 7 3 18 5 18 9 48 0 2 3 5 8 15 9 40 4 15 9 40 4 18 9 48 0 10 6 26 9 1 Swivel 1 Swivel 1 2 Female 14 4 36 6 9 9...

Страница 20: ...er Connections Size Swivel in mm 1 25 4 1 25 4 1 25 4 1 25 4 HWG Connection Size Female Sweat I D in mm 1 2 12 7 1 2 12 7 1 2 12 7 1 2 12 7 Coax Piping Water Volume gal l 1 3 4 9 1 6 6 1 1 6 6 1 1 6 6...

Страница 21: ...sting The control allows service personnel to shorten most timing delays for faster diagnostics Refer to Dip Switch description Fault Retry All faults except for low RPM faults with the ECM blower mot...

Страница 22: ...put if spring damper operation is selected or activate the CR4 output if POPC damper operation is selected This will close field installed damper s located in ductwork NOTE The control will not operat...

Страница 23: ...FaultFlash Thermostats When the heat pump microprocessor control is configured for ComforTalk or FaultFlash SW2 8 off thermostats the thermostats will flash or display alert codes when a lockout cond...

Страница 24: ...the outputs from the control board such as compressor diverting valve reversing valve blower hot water pump and loop pump on the LED display Outputs Normal SW2 8 Thermostat Selection Configures the c...

Страница 25: ...n On Load Pump Off Off Off Off Off Off On Aux Heater Off Off Staged Staged Off Off Off Acc Relay On On On Off On On Off Diverting Valve Off Off Off Off Off Off On ECM Speed On On On On On On Off T Sta...

Страница 26: ...ection Violet P5 3 4 9 11 2 10 8 1 12 5 14 13 6 7 P6 6 5 4 8 7 12 1 2 9 10 3 13 14 16 11 15 Blk 20 Acc Com Acc NC Acc NO P3 SV Blk 23 White 22 NOTE 2 ECM Fan Motor Grn 15 10 16 3 8 On Off PWM RPM C2 R...

Страница 27: ...ump Relay Breaker Violet Blue 2 3 HE1 TS1 HE2 TS2 Black Gray Black Gray Green P9 ER 1 ER 2 N O N O Brown Orange 5 4 EA Series PCB P2 1 L2 L1 G 208 230 60 1 Green P11 2 3 4 5 1 C 1 2 3 4 Brown Orange P...

Страница 28: ...1 2 9 10 3 13 14 16 11 15 Blk 20 Acc Com Acc NC Acc NO P3 SV Blk 23 White 22 NOTE 2 ECM Fan Motor Grn 15 10 16 3 8 On Off PWM RPM C2 RPM grnd P12 P11 2 3 4 5 1 LP Blue Blue Cap Black 1 CC Violet 2 Bl...

Страница 29: ...ary heat operation Note 4 5 Low voltage wiring CLASS 2 208 230 60 1 208 230 60 1 With optional EA Series 20kW Auxiliary Electric Heat Shown Circuit 2 Circuit 1 Note 2 Place auxiliary heat schematic fr...

Страница 30: ...ing temperature to maintain desired comfort level 9 Instruct the owner operator in the proper operation of the hydronic temperature control and system maintenance Forced Air Startup Instructions NOTE...

Страница 31: ...on Pressure PSIG Discharge Pressure PSIG Super heat F Sub cooling F Water Temp Rise F Air Temp Drop F DB 20 1 5 Operation Not Recommended Operation Not Recommended 2 25 3 0 57 64 272 282 12 21 8 16 3...

Страница 32: ...3 049 part load 5 1 1 1 1 1 0 0 9 0 9 8 2 0 1 8 1 7 1 6 1 5 11 3 4 3 1 2 9 2 8 2 5 14 5 0 4 7 4 4 4 1 3 8 064 full load 8 2 0 1 8 1 7 1 6 1 5 12 3 6 3 3 3 2 3 0 2 6 16 6 5 6 0 5 6 5 2 4 8 20 9 7 9 1...

Страница 33: ...1 51 1 74 072 ZPS60K5E PFV 0 31 0 36 1 72 1 98 9 24 2013 Thermistor Temperature F Microprocessor Resistance Ohms 5 75757 70117 14 57392 53234 23 43865 40771 32 33809 31487 41 26269 24513 50 20570 1923...

Страница 34: ...Load 6 0 31 3 39 4 43 7 55 5 53 3 50 3 9 0 23 2 32 5 41 5 46 6 48 7 55 6 53 8 51 3 49 6 12 0 23 6 33 4 42 8 48 3 48 8 55 7 54 1 51 4 49 8 064 Part Load 6 0 29 8 39 4 46 0 60 4 57 8 54 7 10 0 19 5 30...

Страница 35: ...freeze Type Antifreeze by wt Heating Cooling Pressure Drop EWT F C 30 1 1 90 32 2 30 1 1 Water 0 1 000 1 000 1 000 Ethylene Glycol 10 0 973 0 991 1 075 20 0 943 0 979 1 163 30 0 917 0 965 1 225 40 0 8...

Страница 36: ...minal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext 240 60 0 922 0 786 0 910 0 920 0 943 1 150 0 893 275 69 0 944 0 827 0 924 0 940 0 958 1 105 0 922 300 75 0 959 0 860 0 937 0 955 0...

Страница 37: ...s per minute WPD water pressure drop psi and feet of water HC air heating capacity MBtu h HE total heat of extraction MBtu h HR total heat of rejection MBtu h kW total power unit input kilowatts LAT l...

Страница 38: ...n be installed and superheat and subcooling numbers calculated If superheat and subcooling are outside recommended ranges an adjustment to the refrigerant charge may be necessary NOTE Refrigerant test...

Страница 39: ...___ WATTS o ______ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o x 3 413 p _____ btu hr 7 EFFICIENCY Cooling EER p o q _____ EER Heating COP p o x...

Страница 40: ...F ______ F F F NOTE Do not attach refrigerant gauges unless a problem is suspected FD TXV CV Suction Discharge Compressor RV Air Coil Source Coax Load Coax DV open Inactive circuit Refrigerant charge...

Страница 41: ...ne Unit Amp Draw ____________ Line Voltage _________ Loop ______ Open ______ Closed Subcooling _______ Superheat _______ NOTE Do not attach refrigerant gauges unless a problem is suspected Entering So...

Страница 42: ...rts When ordering service or replacement parts refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit If replacement parts are required mention the...

Страница 43: ...08 33P619 09 DanfossTXV model TR6 3 Ton 3 8 TR6 4 Ton 1 2 TR6 5 Ton 1 2 TR6 6 Ton 1 2 Reversing Valve 33P503 05 33P526 05 Diverting Valve 33P503 05 33P526 05 Filter Drier 36P500B01 36P500B02 Refriger...

Страница 44: ...Nomenclature Hot Water Generation Option and Updated Open Loop Solenoid Valve Connection Option Wiring Diagrams 30 Sept 2014 MA All Updated to new Revision Reformatted Layout 27 Dec 2013 DS All Update...

Страница 45: ...AFFINITY COMBINATION INSTALLATION MANUAL...

Страница 46: ...t to change design and specifications without notice Product Affinity Series Type Geothermal Heat Pumps Size 3 6 Ton Dual Capacity Document Type Installation Manual Part Number IM1300YK6 Release Date...

Отзывы: