246653-YTG-E-0108
Johnson Controls Unitary Products
55
4.
Shaded RPMs require Class II blower.
A
IRFLOW
(CFM)
A
VAILABLE
E
XTERNAL
S
TATIC
P
RESSURE
(IWG)
3.2
3.4
3.6
3.8
4.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
8000
1315
6.0
1345
6.4
1375
6.7
1405
7.1
1433
7.4
9000
1360
6.9
1389
7.3
1417
7.6
1445
8.0
1472
8.4
10000
1411
7.9
1438
8.3
1464
8.7
1491
9.1
1517
9.5
11000
1466
9.0
1492
9.5
1517
9.9
1542
10.3
1567
10.8
12000
1526
10.3
1550
10.8
1575
11.2
1599
11.7
1622
12.2
13000
1590
11.8
1613
12.3
1635
12.7
1658
13.2
1681
13.7
14000
1656
13.4
1678
13.9
1700
14.4
1721
14.9
1743
15.5
15000
1725
15.2
1745
15.8
1766
16.3
1787
16.9
1808
17.4
16000
1796
17.3
1816
17.8
1835
18.4
1855
19.0
1875
19.5
17000
1868
19.5
1888
20.1
1907
20.6
1926
21.2
1944
21.8
18000
1943
21.9
1961
22.5
1980
23.2
1998
23.8
2016
24.4
19000
2019
24.6
20000
A
IRFLOW
(CFM)
A
VAILABLE
E
XTERNAL
S
TATIC
P
RESSURE
(IWG)
4.2
4.4
4.6
4.8
5.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
8000
1462
7.8
1490
8.2
1518
8.6
1545
9.0
1572
9.4
9000
1500
8.8
1526
9.2
1553
9.6
1579
10.0
1605
10.4
10000
1543
9.9
1569
10.4
1594
10.8
1619
11.2
1644
11.7
11000
1592
11.2
1617
11.7
1640
12.1
1664
12.6
1688
13.0
12000
1645
12.6
1669
13.1
1692
13.6
1715
14.1
1737
14.6
13000
1703
14.2
1725
14.7
1747
15.2
1769
15.7
1791
16.2
14000
1764
16.0
1785
16.5
1806
17.1
1827
17.6
1847
18.1
15000
1828
18.0
1848
18.5
1868
19.1
1888
19.6
1908
20.2
16000
1895
20.1
1914
20.7
1933
21.2
1952
21.8
1971
22.4
17000
1963
22.5
1981
23.1
2000
23.7
2018
24.3
2036
24.9
18000
2033
25.0
A
IRFLOW
(CFM)
A
VAILABLE
E
XTERNAL
S
TATIC
P
RESSURE
(IWG)
5.2
5.4
5.6
5.8
6.0
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
RPM
BHP
3
8000
1599
9.8
1624
10.2
1650
10.6
1675
11.0
1701
11.4
9000
1630
10.9
1655
11.3
1680
11.7
1705
12.2
1729
12.6
10000
1668
12.1
1692
12.6
1716
13.0
1740
13.5
1763
13.9
11000
1712
13.5
1734
14.0
1757
14.5
1780
14.9
1803
15.4
12000
1759
15.0
1782
15.5
1804
16.0
1825
16.6
1847
17.1
13000
1812
16.8
1833
17.3
1854
17.8
1875
18.4
1896
18.9
14000
1868
18.7
1888
19.2
1908
19.8
1928
20.3
1948
20.8
15000
1927
20.7
1947
21.3
1966
21.9
1985
22.5
2004
23.0
16000
1990
23.0
2008
23.6
2027
24.2
2045
24.8
17000
18000
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2.
Refer to Tables 10, 12, 15, 18, 21, 23 and 42 for component additions and deductions to fan performance tables.
3.
BHP includes drive losses.
TABLE 41: FAN PERFORMANCE - 40 TON AIRFOIL
1,2