251933-YTG-J-1009
50
Johnson Controls Unitary Products
XP036-060 Bottom Duct Application
XP060 (5 Ton Belt Drive) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
1200
727
0.45
810
0.52
889
0.60
966
0.68
1040
0.76
1110
0.85
1179
0.95
1244
1.04
1308
1.14
1369
1.24
1400
759
0.51
842
0.58
922
0.65
998
0.73
1072
0.82
1143
0.91
1211
1.00
1276
1.10
1340
1.20
1401
1.30
1600
795
0.60
878
0.67
958
0.74
1035
0.82
1108
0.91
1179
1.00
1247
1.09
1313
1.19
1376
1.28
1438
1.39
1800
836
0.72
919
0.79
999
0.87
1075
0.95
1149
1.03
1220
1.12
1288
1.22
1353
1.31
1417
1.41
1478
1.51
2000
880
0.89
963
0.96
1042
1.04
1119
1.12
1193
1.20
1263
1.29
1331
1.39
1397
1.48
1460
1.58
1522
1.68
2200
926
1.10
1009
1.17
1089
1.25
1166
1.33
1239
1.41
1310
1.50
1378
1.60
1444
1.69
1507
1.79
1568
1.89
2400
976
1.35
1059
1.42
1138
1.50
1215
1.58
1289
1.66
1359
1.75
1428
1.85
1493
1.94
1557
2.04
1618
2.14
2600
1028
1.64
1111
1.71
1190
1.78
1267
1.87
1340
1.95
1411
2.04
1479
2.13
1545
2.23
1608
2.33
-
-
XP036 - 060 (3-5 Ton Direct Drive) Side Duct
UNIT
TONNAGE
MOTOR
1
SPEED
1. Factory set on medium speed tap.
AVAILABLE EXTERNAL STATIC PRESSURE - IWG
2
2. Includes allowances for a wet evaporator coil and 1” filters. Refer to STATIC RESISTANCES Table for resistance values.
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
CFM
W
A
TTS
3
3
3. Side Duct application (230 Volts)
HI
1528
320
1485
335
1445
349
1409
363
1370
376
1334
390
1292
403
1254
417
1213
430
MED/HI
1437
263
1391
276
1349
290
1308
303
1265
316
1220
329
1173
343
1119
358
1048
374
MED
1293
208
1248
221
1205
234
1160
246
1113
258
1065
272
1001
288
934
303
892
313
MED/LOW 1191
171
1144
183
1096
195
1045
207
991
220
925
235
865
248
-
-
-
-
LOW
1044
130
963
134
903
145
833
158
-
-
-
-
-
-
-
-
-
-
4
3
HI
-
-
2007
696
1968
714
1933
734
1896
749
1855
764
1806
769
1719
743
1574
685
MED/HI
1857
539
1822
557
1786
571
1746
585
1713
602
1671
619
1628
638
1574
653
1500
639
MED
1672
408
1633
426
1586
438
1550
455
1509
472
1462
490
1408
505
1363
521
1330
536
MED/LOW 1574
362
1534
380
1487
391
1458
406
1418
423
1370
440
1319
455
1285
469
1241
485
LOW
1293
223
1252
237
1196
247
-
-
-
-
-
-
-
-
-
-
-
-
5
3
HI
2245
883
2247
931
2236
950
2211
964
2171
979
2114
971
2034
940
1948
898
1855
854
MED/HI
2135
771
2116
784
2108
808
2078
826
2041
844
2004
859
1955
861
1886
843
1792
806
MED
2010
637
1989
656
1975
675
1938
696
1900
715
1867
730
1822
740
1784
756
1716
748
MED/LOW 1748
413
1704
432
1669
451
1631
468
1589
479
1551
497
1513
513
1465
523
-
-
LOW
1562
327
1529
339
1491
356
-
-
-
-
-
-
-
-
-
-
-
-
XP036 (3 Ton Belt Drive) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard Drive Option
HIgh Static Drive Option
800
661
0.39
751
0.45
838
0.53
922
0.61
1002
0.69
1079
0.78
1153
0.87
1225
0.96
1294
1.06
1361
1.16
1000
685
0.43
775
0.50
862
0.57
945
0.65
1025
0.73
1103
0.82
1177
0.91
1248
1.00
1317
1.10
1384
1.20
1200
714
0.46
805
0.53
892
0.60
975
0.68
1055
0.76
1132
0.85
1207
0.94
1278
1.04
1347
1.13
1414
1.23
1400
749
0.52
840
0.58
927
0.66
1010
0.74
1090
0.82
1167
0.91
1242
1.00
1313
1.09
1382
1.19
1449
1.29
1600
789
0.60
880
0.67
967
0.74
1050
0.82
1130
0.91
1207
0.99
1282
1.08
1353
1.18
1422
1.27
1489
1.37
Field Supplied Drive