262291-YTG-F-1009
22
Johnson Controls Unitary Products
TABLE 12: WJ240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW
Blower Performance (Downflow Discharge)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM
KW
BHP CFM RPM
KW
BHP CFM RPM
KW
BHP
0.4
9339 1014 7.07 8.63 8912
982
6.17 7.53 8487
949
5.55 6.77 8255
917
5.07
6.18 7835
885
4.63
5.65 7593
853
4.39
5.36
0.6
8855 1015 6.49 7.91 8480
983
5.99 7.31 8143
951
5.22 6.36 7781
918
4.75
5.80 7357
887
4.24
5.17 7081
854
3.83
4.59
0.8
8450 1016 6.11 7.45 8050
984
5.73 6.99 7704
952
5.13 6.26 7309
919
4.34
5.30 6850
886
4.11
4.93 6554
855
3.63
4.36
1.0
7994 1018 5.74 7.01 7590
985
5.08 6.19 7226
953
4.73 5.77 6793
920
4.04
4.84 6330
888
3.65
4.38 6009
856
3.26
3.91
1.2
7541 1019 5.33 6.50 7119
987
4.76 5.81 6744
954
4.11 4.93 6266
921
3.72
4.46 5800
889
3.39
4.07 5447
856
2.86
3.43
1.4
7086 1020 5.04 6.16 6653
988
4.27 5.21 6200
955
3.70 4.44 5743
922
3.34
4.01 5189
890
3.00
3.60 4762
858
2.59
3.11
1.6
6571 1022 4.83 5.89 6128
989
3.93 4.72 5650
956
3.30 3.96 5108
923
3.15
3.79 4496
891
2.64
3.16
-
-
-
-
1.8
6055 1022 4.23 5.16 5606
990
3.59 4.31 5073
956
3.21 3.85 4511
923
2.78
3.34 3788
892
2.03
2.43
-
-
-
-
2.0
5464 1023 3.73 4.47 4949
990
3.31 3.97
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 turn
2 turns
3 turns
4 turns
5 turns
6 turns
10 HP motor
7.5 HP motor
5 HP motor
20-Ton Standard Drive, Cooling Only, Bottom Connection
VP68 x BK110
3000
4000
5000
6000
7000
8000
9000
10000
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
External Static (" WC)
SCFM
1 turn
2 turns
3 turns
4 turns
5 turns
6 turns