TABLE 10: WJ180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW
Blower Performance (Downflow Discharge)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM
KW
BHP CFM RPM
KW
BHP CFM RPM
KW
BHP
0.2
7898 1120 5.88 7.18 7577 1082 5.29 6.45 7322 1044 4.78 5.83 7014 1005
4.21
5.13 6651
965
3.77
4.53 6333
926
3.31
3.97
0.4
7493 1122 5.49 6.70 7214 1084 4.96 6.06 6946 1045 4.50 5.49 6605 1005
3.96
4.75 6234
966
3.46
4.15 5912
927
3.05
3.66
0.6
7178 1123 5.17 6.31 6846 1085 4.63 5.65 6565 1046 4.12 4.95 6224 1007
3.70
4.44 5851
967
3.17
3.80 5540
928
2.83
3.40
0.8
6846 1125 4.88 5.95 6506 1086 4.37 5.33 6245 1046 3.85 4.62 5880 1008
3.43
4.12 5492
968
2.96
3.55 5163
928
2.58
3.10
1.0
6506 1126 4.56 5.56 6208 1087 4.15 4.98 5898 1047 3.60 4.32 5460 1009
3.10
3.72 5064
969
2.67
3.21 4665
929
2.30
2.76
1.2
6225 1127 4.31 5.25 5825 1088 3.83 4.60 5495 1048 3.32 3.98 5076 1010
2.83
3.40 4559
969
2.40
2.88 4120
930
2.02
2.42
1.4
5812 1128 4.01 4.81 5476 1089 3.53 4.23 5074 1049 3.06 3.68 4589 1010
2.56
3.07 3944
970
2.05
2.46 3348
932
1.70
2.05
1.6
5441 1130 3.72 4.46 5029 1091 3.18 3.82 4685 1050 2.85 3.42 3991 1011
2.20
2.64 3212
972
1.77
2.12
-
-
-
-
1.8
4983 1131 3.34 4.01 4607 1092 2.91 3.49 4088 1051 2.47 2.96
-
-
-
-
-
-
-
-
-
-
-
-
2.0
4415 1133 2.97 3.56 3817 1093 2.45 2.94
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.2
3691 1134 2.55 3.05
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 turn
2 turns
3 turns
4 turns
5 turns
6 turns
7.5 HP motor
5 HP motor
15-Ton High-Static Drive, Cooling Only, Bottom Duct Connection
1VP62 x BK90
3000
3500
4000
4500
5000
5500
6000
6500
7000
7500
8000
8500
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
External Static ("WC)
SCFM
1 Turn
2 Turns
3 Turns
5 Turns
6 Turns
4 Turns