Pressure Drop
Model
gpm
Pressure Drop (psi)
30°F
50°F
70°F
90°F
110°F
038
full
load
5
1.2
1.2
1.1
1.0
1.0
7
2.2
2.1
1.9
1.8
1.7
9
3.4
3.2
3.0
2.8
2.6
11
4.9
4.6
4.3
4.0
3.7
038
part
load
4
0.9
0.8
0.8
0.7
0.7
6
1.7
1.6
1.5
1.4
1.3
8
2.8
2.6
2.5
2.3
2.1
10
4.2
3.9
3.7
3.4
3.2
049
full
load
6
1.2
1.2
1.1
1.0
1.0
9
2.4
2.2
2.1
2.0
1.8
12
3.9
3.6
3.4
3.2
2.9
15
5.7
5.3
5.0
4.7
4.3
049
part
load
5
1.1
1.1
1.0
0.9
0.9
8
2.0
1.8
1.7
1.6
1.5
11
3.4
3.1
2.9
2.8
2.5
14
5.0
4.7
4.4
4.1
3.8
064
full
load
8
2.0
1.8
1.7
1.6
1.5
12
3.6
3.3
3.2
3.0
2.6
16
6.5
6.0
5.6
5.2
4.8
20
9.7
9.1
8.5
8.0
7.4
064
part
load
6
1.2
1.2
1.1
1.0
1.0
10
2.6
2.5
2.3
2.1
2.0
14
5.0
4.7
4.4
4.1
3.8
18
8.1
7.6
7.1
6.6
6.1
072
full
load
12
3.6
3.3
3.2
3.0
2.6
15
5.7
5.3
5.0
4.7
4.3
18
8.1
7.6
7.1
6.6
6.1
21
10.8
10.1
9.5
8.9
8.2
072
part
load
10
2.6
2.5
2.3
2.1
2.0
13
4.1
4.0
3.7
3.4
3.3
16
6.5
6.0
5.8
5.4
5.0
19
8.9
8.4
7.9
7.4
6.9