036-21410-001-A-0502
16
Unitary Products Group
TABLE 7: COOLING CAPACITIES FOR DJ180 AT 115°F
RETURN AIR
OUTDOOR AMBIENT TEMPERATURE (°F): 115
CFM
WB
TEMP °F
GROSS
CAPACITY
1
(MBH)
INPUT
POWER
2
(kW)
GROSS SENSIBLE CAPACITY
1
(MBH)
(RETURN AIR DRY BULB TEMP. - (°F) )
86
83
80
77
74
71
68
4500
72
178.8
17.24
107.6
94.7
81.9
69.1
56.2
#N/A
#N/A
67
163.6
16.78
137.2
124.4
111.6
98.8
85.9
73.1
60.3
62
154.2
16.31
154.2
144.3
131.5
118.7
105.9
93.0
80.2
57
152.0
16.24
152.0
148.0
135.1
122.3
109.5
96.6
83.8
5250
72
183.3
17.38
119.6
104.5
89.3
74.1
59.0
#N/A
#N/A
67
167.7
16.91
152.0
136.8
121.7
106.5
91.3
76.2
61.0
62
158.1
16.44
158.1
153.1
143.4
128.2
113.1
97.9
82.8
57
155.8
16.37
155.8
153.8
147.4
132.2
117.0
101.9
86.7
6000
72
187.8
17.52
131.7
114.2
96.7
79.2
61.7
#N/A
#N/A
67
171.8
17.05
166.8
149.3
131.8
114.3
96.8
79.3
61.8
62
161.9
16.57
161.9
161.9
155.3
137.8
120.3
102.8
85.3
57
159.6
16.50
159.6
159.6
159.6
142.1
124.6
107.1
89.6
6750
72
193.0
17.53
142.5
122.6
102.6
82.7
62.8
#N/A
#N/A
67
176.5
17.06
174.0
159.8
139.8
119.9
100.0
80.1
60.1
62
166.4
16.59
166.4
166.4
163.1
143.2
123.2
103.3
83.4
57
164.0
16.52
164.0
164.0
164.0
144.1
124.1
104.2
84.3
7500
72
198.1
17.55
153.3
130.9
108.6
86.2
63.8
#N/A
#N/A
67
181.3
17.08
181.3
170.3
147.9
125.6
103.2
80.8
58.5
62
170.9
16.60
170.9
170.9
170.9
148.5
126.2
103.8
81.5
57
168.4
16.54
168.4
168.4
168.4
146.0
123.7
101.3
79.0
1. The capacities are gross ratings. For net capacity, deduct the supply air blower motor heat, MBH = 3.415 x kW. Refer to the appro-
priate blower performance table for the kW of the supply air blower motor.
2. These ratings include condenser fan motor and compressor motor power but not the supply air blower motor power.