York SUNLINE 2000 D1EE 048 Скачать руководство пользователя страница 7

035-12046-003-A-0204

Unitary Products Group

7

FIG. 5

- DIMENSIONS & CLEARANCES - 3 - 5 TONS

DUCT COVERS - Units are shipped with all air duct
openings covered.
For side duct applications;
1.Remove and discard the supply and return air duct

covers.

2.Connect ductwork to duct flanges on the rear of the

unit.

For bottom duct applications;
1. Remove the side supply air duct cover to gain

access to the bottom supply air knockout panel.

2. Remove and discard the bottom knockout panel.
3. Replace the side duct cover.
4. With filter section access panel removed from the

unit, remove and discard the bottom return air
knockout panel.

5. Replace the filter access panel.

CLEARANCES

Front

24"

Back

12" (Less Economizer)

36" (With Economizer

or Fixed Air/Motorized

Air Damper)

Left Side (Filter Access) 24" (Less Economizer)

36" (With Economizer)

Right Side (Cond. Coil) 24"
Below Unit

1

2

0"

Above Unit

2

72" (For Condenser Air

Discharge)

NOTE:

Units and ductwork are approved for zero clearance to combustible

materials when equipped with electric heaters.

1

Units may be installed on combustible floors made from wood or

class A, B or C roof covering material. (Applicable in USA only).

2

Units must be installed outdoors. Overhanging structures or shrubs

should not obstruct the outdoor coil nor the fan outlet.

HOLE

KNOCKOUT

SIZE

(DIA.)

USED FOR

A

7/8" *

Control Wiring

(Side or

Bottom)**

B

2" *

Power Wiring

(Side or

Bottom)

*

Knockouts in the bottom of the unit can be

located by the slice in the insulation.

**

Do not remove the 2" knockout ring.

UTILITIES ENTRY DATA

FILTER ACCESS

ELECTRIC
HEAT
ACCESS

B - POWER WIRING ENTRY

A, B
WIRING ENTRY
(See Detail “B”)

OUTDOOR
COIL

A - CONTROL WIRING ENTRY

!"

“ PVC FEMALE

COND. DRAIN
(See Detail ”A")

BOTTOM SUPPLY &
RETURN AIR OPENINGS
(SEE NOTE)

#

&

%

 

 

%

%

&

$

!"

&

&

&

!

&

%

 

$

 

#

!

&

 

 

"

""

%

&

(Direct-Drive Units)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION

BLOWER
ACCESS

CONTROL

BOX ACCESS

Shown separately to illustrate bottom

duct openings and power connection

locations.

NOTE: For curb-mounted units, refer to the

duct hanger dimensions of the curb for the

proper size of the supply and return air

duct connections.

COMPRES-
SOR

 

"

#

&

3

%

%

&

$

 

%

 

 

%

 

REAR VIEW

SIDE SUPPLY AND RETURN

AIR OPENINGS

UNIT BASE WITH RAILS

FRONT VIEW

All dimensions are in inches. They are sub-

ject to change without notice. Certified di-

mensions will be provided upon request.

UNIT WITH ECONOMIZER RAIN HOOD

""

%

&

B

!

%

&

“A”

"

"

!

&

A

!

 

&

"

'

&

""

%

&

'

 

 %

 

'

!"

!

"

“ CONDENSATE

DRAIN

(must be trapped)

DETAIL “A”

DETAIL “B”

UNIT WITH FIXED OUTDOOR

AIR/MOTORIZED DAMPER RAIN HOOD

DIMENSION “A”

FIXED

OUTDOOR

AIR DAMPER

12

MOTORIZED

DAMPER

$

 

AIR FLOW LEGEND

RETURN AIR

SUPPLY AIR

OUTDOOR AIR

OUTDOOR AIR

(Economizer)

Содержание SUNLINE 2000 D1EE 048

Страница 1: ... Air Damper Accy 530 18 N1 8V Coil Guard 530 18 N7 1V Electric Heater Accessory 530 18 N7 2V Fuse Block Accessory 690 15 N25V Low Ambient to 0 F Renewal Parts Refer to Parts Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Fax 877 379 7920 APPROVALS Design certified by U L an...

Страница 2: ...2 Physical Data 4 3 Blower Perf 3 5 Ton Direct Drive 8 4 Blower Perf 3 4 Ton Belt Drive 9 5 Blower Perf 5 Ton Belt Drive 10 6 Static Resistances 11 7 Motor and Drive Data Belt Drive 11 8 Electrical Data Direct Drive 11 9 Electrical Data Belt Drive 11 10 Heat Anticipator Setting 12 11 Motor Pulley Adjustment 13 FIGURES No Description Page 1 Center of Gravity 3 2 Recommended Drain Piping 4 3 Economi...

Страница 3: ... ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units may also be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose LENGTH OF FORKS MUST BE A MINIMUM OF 42 Remove the nesting brackets from the four corners on top of the unit All screws that are removed when taking these brackets off must be replaced on the unit Refer to Ta...

Страница 4: ... unit The switch must be separate from all other circuits Refer to Figure 5 for installation location If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical lines must be sized properly to carry the load USE COPPER CONDUCTORS ONLY Each unit must be wired with a separate branch circuit fed directly from the meter panel ...

Страница 5: ... the sensor as follows Wire 73 to terminal Wire 74 to terminal S 5 Assemble the LH and RH side plates to the top cover 2 screws each side to form the hood Apply gasketing to the flange surface on each side plate Extend gasketing 1 4 beyond top and bottom of each flange to insure ade quate corner sealing Secure this assembly to the unit back panel upper right hand corner First remove screw C on uni...

Страница 6: ...C O O L I N G O R H A V E A N D E L E C T R I C H E A T A C C E S S O R Y W I T H T W O S T A G E S O F H E A T U S E T H E R M O S T A T 2 T H 0 4 7 1 0 2 4 A D D J U M P E R COOLING HEATING 24 VOLT THERMOSTAT R C R H Y 1 Y 2 W 1 W 2 G L E D 1 L E D 2 C O M A 1 A 2 T T B R Y 1 Y 2 G B X N W 2 W 1 T H E R M O S T A T 1 T E R M I N A L S U N I T T E R M I N A L S T R I P T B 1 2 4 V O L T T R A N S...

Страница 7: ...lled outdoors Overhanging structures or shrubs should not obstruct the outdoor coil nor the fan outlet HOLE KNOCKOUT SIZE DIA USED FOR A 7 8 Control Wiring Side or Bottom B 2 Power Wiring Side or Bottom Knockouts in the bottom of the unit can be located by the slice in the insulation Do not remove the 2 knockout ring UTILITIES ENTRY DATA FILTER ACCESS ELECTRIC HEAT ACCESS B POWER WIRING ENTRY A B ...

Страница 8: ...rnal Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts 036 HI MED LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 570 1180 1100 1020 655 590 545 ...

Страница 9: ...S FIRED HEAT EXCHANGERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 036 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 190...

Страница 10: ...1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 5 TON GAS HEAT VALUES SHOWN 230 460 575 VOLTS Side Duct Connections UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 13...

Страница 11: ...ER SUP PLY VOLTAGE LIMITATIONS SEE NOTE 1 COMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA TOTAL UNIT AMPACITY AMPS MAX FUSE SIZE SEE NOTE 2 AMPS MAX HACR BREAKER SIZE AMPS MIN MAX RLA LRA 036 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 16 7 13 1 6 7 5 1 87 110 54 44 2 3 2 3 1 4 1 4 4 4 4 4 2 2 2 2 27 5 23 1 12 0 10 7 40 35 15 15 40 35 15 048 208 230 1 60 2...

Страница 12: ...witch to protect against excessive discharge pressures due to a blocked condenser coil or a condenser motor failure 3 A Low Pressure Loss of Charge Switch to protect against loss of refrigerant charge If either of the above safety controls opens the refrigerant system will be locked out The lock out of the system can be reset by opening the 24V circuit either at the room thermostat or at the unit ...

Страница 13: ...re readings 3 Using an inclined manometer determine the pressure drop across a dry indoor coil Since the moisture on an indoor coil may vary greatly measuring the pressure drop across a wet coil under field conditions would be inaccurate To assure a dry coil the compressors should be de energized while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the u...

Страница 14: ...month Replace disposable or clean permanent type as necessary DO NOT replace permanent type with disposable MOTORS Indoor fan and outdoor fan motors are permanently lubricated and require no maintenance OUTDOOR COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep coil clean Use a brush vacuum cl...

Страница 15: ...035 12046 003 A 0204 Unitary Products Group 15 ...

Страница 16: ...ducts Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A 035 12046 003 A 0204 Copyright 2004 by Unitary Products Group All Rights Reserved Supersedes 035 12046 002 A 0302 ...

Отзывы: