York SUNLINE 2000 D1EE 048 Скачать руководство пользователя страница 10

035-12046-003-A-0204

10

Unitary Products Group

TABLE 5

- SUPPLY AIR PERFORMANCE - 5 TON w/Belt-Drive Blower

UNIT

SIZE

(MBH)

AIR FLOW

CFM

Available External Static Pressure - IWG*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

060

2500

1059

1560

1077

1590

1095

1630

1114

1650

1134

1660

1158

1685

1181

1720

2400

1032

1405

1054

1470

1074

1525

1094

1560

1116

1595

1140

1620

1167

1640

2300

1005

1260

1024

1275

1049

1370

1069

1440

1090

1475

1116

1505

1142

1535

2200

980

1160

1002

1170

1022

1190

1044

1250

1066

1350

1090

1410

1117

1440

2100

930

1060

957

1070

983

1080

1010

1100

1039

1160

1064

1260

1092

1340

2000

877

950

908

975

941

1000

976

1020

1009

1050

1040

1100

1070

1225

1900

-

-

-

-

894

885

940

940

980

980

1014

1020

1047

1095

1800

-

-

-

-

855

815

903

860

950

905

988

940

1022

970

1700

-

-

-

-

-

-

884

815

925

850

964

880

1001

910

1600

-

-

-

-

-

-

864

770

908

805

948

835

987

870

1500

-

-

-

-

-

-

-

-

882

740

926

780

965

830

5 TON GAS HEAT VALUES SHOWN @ 230/460/575 VOLTS - Side Duct Connections

UNIT

SIZE

(MBH)

AIR FLOW

CFM

Available External Static Pressure - IWG*

0.90

1.00

1.10

1.20

1.30

1.40

1.50

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

RPM

Watts

060

2500

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2400

1193

1665

-

-

-

-

-

-

-

-

-

-

-

-

2300

1170

1580

1202

1620

-

-

-

-

-

-

-

-

-

-

2200

1148

1480

1180

1530

-

-

-

-

-

-

-

-

-

-

2100

1121

1385

1155

1425

1190

1475

-

-

-

-

-

-

-

-

2000

1100

1285

1133

1340

1169

1385

1205

1445

-

-

-

-

-

-

1900

1079

1180

1110

1240

1143

1280

1178

1330

1222

1375

-

-

-

-

1800

1058

1060

1090

1135

1122

1190

1158

1240

1196

1295

-

-

-

-

1700

1035

960

1071

1030

1103

1100

1134

1140

1164

1175

1197

1205

-

-

1600

1020

900

1056

965

1088

1035

1118

1065

1145

1105

1170

1130

1198

1150

1500

1004

860

1038

880

1070

925

1101

980

1130

1045

1158

1075

1184

1110

NOTE:  FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*

INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS AND GAS-FIRED HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE

VALUES ON APPLICATIONS OTHER THAN GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.

Содержание SUNLINE 2000 D1EE 048

Страница 1: ... Air Damper Accy 530 18 N1 8V Coil Guard 530 18 N7 1V Electric Heater Accessory 530 18 N7 2V Fuse Block Accessory 690 15 N25V Low Ambient to 0 F Renewal Parts Refer to Parts Manual for complete listing of replacement parts on this equipment All forms referenced in this instruction may be ordered from Standard Register Toll Free Tel 877 318 9675 Fax 877 379 7920 APPROVALS Design certified by U L an...

Страница 2: ...2 Physical Data 4 3 Blower Perf 3 5 Ton Direct Drive 8 4 Blower Perf 3 4 Ton Belt Drive 9 5 Blower Perf 5 Ton Belt Drive 10 6 Static Resistances 11 7 Motor and Drive Data Belt Drive 11 8 Electrical Data Direct Drive 11 9 Electrical Data Belt Drive 11 10 Heat Anticipator Setting 12 11 Motor Pulley Adjustment 13 FIGURES No Description Page 1 Center of Gravity 3 2 Recommended Drain Piping 4 3 Economi...

Страница 3: ... ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY Units may also be moved or lifted with a forklift Slotted openings in the base rails are provided for this purpose LENGTH OF FORKS MUST BE A MINIMUM OF 42 Remove the nesting brackets from the four corners on top of the unit All screws that are removed when taking these brackets off must be replaced on the unit Refer to Ta...

Страница 4: ... unit The switch must be separate from all other circuits Refer to Figure 5 for installation location If any of the wire supplied with the unit must be replaced replacement wire must be of the type shown on the wiring diagram Electrical lines must be sized properly to carry the load USE COPPER CONDUCTORS ONLY Each unit must be wired with a separate branch circuit fed directly from the meter panel ...

Страница 5: ... the sensor as follows Wire 73 to terminal Wire 74 to terminal S 5 Assemble the LH and RH side plates to the top cover 2 screws each side to form the hood Apply gasketing to the flange surface on each side plate Extend gasketing 1 4 beyond top and bottom of each flange to insure ade quate corner sealing Secure this assembly to the unit back panel upper right hand corner First remove screw C on uni...

Страница 6: ...C O O L I N G O R H A V E A N D E L E C T R I C H E A T A C C E S S O R Y W I T H T W O S T A G E S O F H E A T U S E T H E R M O S T A T 2 T H 0 4 7 1 0 2 4 A D D J U M P E R COOLING HEATING 24 VOLT THERMOSTAT R C R H Y 1 Y 2 W 1 W 2 G L E D 1 L E D 2 C O M A 1 A 2 T T B R Y 1 Y 2 G B X N W 2 W 1 T H E R M O S T A T 1 T E R M I N A L S U N I T T E R M I N A L S T R I P T B 1 2 4 V O L T T R A N S...

Страница 7: ...lled outdoors Overhanging structures or shrubs should not obstruct the outdoor coil nor the fan outlet HOLE KNOCKOUT SIZE DIA USED FOR A 7 8 Control Wiring Side or Bottom B 2 Power Wiring Side or Bottom Knockouts in the bottom of the unit can be located by the slice in the insulation Do not remove the 2 knockout ring UTILITIES ENTRY DATA FILTER ACCESS ELECTRIC HEAT ACCESS B POWER WIRING ENTRY A B ...

Страница 8: ...rnal Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts 036 HI MED LOW 1684 1487 800 710 1631 1464 780 690 1699 1582 1421 825 750 670 1650 1524 1367 785 720 650 1570 1410 1315 755 690 620 1430 1324 1246 725 650 605 1360 1260 1185 700 630 590 1280 1185 1110 680 610 570 1180 1100 1020 655 590 545 ...

Страница 9: ...S FIRED HEAT EXCHANGERS REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE VALUES ON APPLICATIONS OTHER THAN GAS ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 036 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 190...

Страница 10: ...1001 910 1600 864 770 908 805 948 835 987 870 1500 882 740 926 780 965 830 5 TON GAS HEAT VALUES SHOWN 230 460 575 VOLTS Side Duct Connections UNIT SIZE MBH AIR FLOW CFM Available External Static Pressure IWG 0 90 1 00 1 10 1 20 1 30 1 40 1 50 RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts RPM Watts 060 2500 2400 1193 1665 2300 1170 1580 1202 1620 2200 1148 1480 1180 1530 2100 1121 13...

Страница 11: ...ER SUP PLY VOLTAGE LIMITATIONS SEE NOTE 1 COMPRESSOR COND FAN MOTOR FLA SUPPLY AIR BLOWER MOTOR FLA TOTAL UNIT AMPACITY AMPS MAX FUSE SIZE SEE NOTE 2 AMPS MAX HACR BREAKER SIZE AMPS MIN MAX RLA LRA 036 208 230 1 60 208 230 3 60 460 3 60 575 3 60 187 187 414 518 253 253 504 630 16 7 13 1 6 7 5 1 87 110 54 44 2 3 2 3 1 4 1 4 4 4 4 4 2 2 2 2 27 5 23 1 12 0 10 7 40 35 15 15 40 35 15 048 208 230 1 60 2...

Страница 12: ...witch to protect against excessive discharge pressures due to a blocked condenser coil or a condenser motor failure 3 A Low Pressure Loss of Charge Switch to protect against loss of refrigerant charge If either of the above safety controls opens the refrigerant system will be locked out The lock out of the system can be reset by opening the 24V circuit either at the room thermostat or at the unit ...

Страница 13: ...re readings 3 Using an inclined manometer determine the pressure drop across a dry indoor coil Since the moisture on an indoor coil may vary greatly measuring the pressure drop across a wet coil under field conditions would be inaccurate To assure a dry coil the compressors should be de energized while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the u...

Страница 14: ...month Replace disposable or clean permanent type as necessary DO NOT replace permanent type with disposable MOTORS Indoor fan and outdoor fan motors are permanently lubricated and require no maintenance OUTDOOR COIL Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit Cleaning should be as often as necessary to keep coil clean Use a brush vacuum cl...

Страница 15: ...035 12046 003 A 0204 Unitary Products Group 15 ...

Страница 16: ...ducts Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A 035 12046 003 A 0204 Copyright 2004 by Unitary Products Group All Rights Reserved Supersedes 035 12046 002 A 0302 ...

Отзывы: