background image

MODEL

BLOWER

RANGE

(RPM)

MOTOR*

ADJUSTABLE

MOTOR PULLEY

FIXED

BLOWER PULLEY

BELTS

HP

SERVICE

FACTOR

FRAME

SIZE

EFFICIENCY

(%)

PITCH

DIA.
(IN.)

BORE

(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

PITCH

LENGTH

(IN.)

DESIG-

NATION

QTY

BHN090

975-1220

2

1.20

56

82.0

3.4 - 4.4

7/8

6.2

1

50.3

A49

1

BHN120

860-1090

3

1.20

56

82.0

3.4 - 4.4

7/8

7.0

1

57.3

A56

1

*

All motors are 1750 RPM, have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air,

  upstream of any heating device.

BLOWER MOTOR AND DRIVE DATA

BLOWER

SPEED,

RPM

CFM

2250

2550

3000

3400

3750

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

975

0.83

1.16

1.08

0.66

1.27

1.18

0.37

1.45

1.35

0.08

1.65

1.54

-

-

-

1025

0.98

1.21

1.13

0.82

1.34

1.25

0.52

1.54

1.44

0.21

1.75

1.63

-

-

-

1070

1.12

1.32

1.23

0.95

1.46

1.36

0.67

1.68

1.57

0.37

1.89

1.76

0.07

2.11

1.97

1130

1.31

1.43

1.33

1.16

1.57

1.46

0.86

1.83

1.71

0.56

2.04

1.90

-

-

-

1175

1.51

1.51

1.41

1.36

1.67

1.56

1.07

1.92

1.79

0.75

2.18

2.03

-

-

-

1220

1.68

1.66

1.55

1.53

1.81

1.69

1.23

2.10

1.96

-

-

-

-

-

-

MODEL BHN090 - (SIDE DUCT APPLICATIONS)

BLOWER

SPEED,

RPM

CFM

2250

2550

3000

3400

3750

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

975

0.76

1.16

1.08

0.57

1.27

1.18

0.24

1.45

1.35

-

-

-

-

-

-

1025

0.91

1.21

1.13

0.73

1.34

1.25

0.39

1.54

1.44

0.04

1.75

1.63

-

-

-

1070

1.05

1.32

1.23

0.86

1.46

1.36

0.54

1.68

1.57

0.20

1.89

1.76

-

-

-

1130

1.24

1.43

1.33

1.07

1.57

1.46

0.73

1.83

1.71

0.39

2.04

1.90

-

-

-

1175

1.44

1.51

1.41

1.27

1.67

1.56

0.94

1.92

1.79

0.58

2.18

2.03

-

-

-

1220

1.61

1.66

1.55

1.44

1.81

1.69

1.10

2.10

1.96

-

-

-

-

-

-

MODEL BHN090 - (BOTTOM DUCT APPLICATIONS)

BLOWER PERFORMANCE - (7-1/2 & 10 TON SUPPLY AIR)

BLOWER

SPEED,

RPM

CFM

3000

3500

4000

4500

5000

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

860

1.05

1.40

1.31

0.85

1.58

1.48

0.62

1.80

1.68

0.32

2.05

1.91

-

-

-

915

1.23

1.55

1.45

1.05

1.76

1.64

0.80

1.98

1.85

0.51

2.23

2.08

0.22

2.48

2.31

950

1.42

1.68

1.57

1.24

1.91

1.78

1.00

2.14

2.00

0.70

2.43

2.27

0.40

2.72

2.54

1000

1.60

1.83

1.71

1.44

2.07

1.93

1.20

2.33

2.17

0.93

2.62

2.45

0.65

2.91

2.72

1050

1.80

1.98

1.84

1.65

2.25

2.10

1.42

2.55

2.37

1.14

2.86

2.67

0.85

3.17

2.96

1090

1.99

2.12

1.97

1.84

2.41

2.24

1.63

2.72

2.54

1.34

3.06

2.86

-

-

-

MODEL BHN120 - (SIDE DUCT APPLICATIONS)

BLOWER

SPEED,

RPM

CFM

3000

3500

4000

4500

5000

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

860

0.92

1.40

1.31

0.67

1.58

1.48

0.39

1.80

1.68

0.02

2.05

1.91

-

-

-

915

1.10

1.55

1.45

0.87

1.76

1.64

0.57

1.98

1.85

0.21

2.23

2.08

-

-

-

950

1.29

1.68

1.57

1.06

1.91

1.78

0.77

2.14

2.00

0.40

2.43

2.27

0.04

2.72

2.54

1000

1.47

1.83

1.71

1.26

2.07

1.93

0.97

2.33

2.17

0.63

2.62

2.45

0.29

2.91

2.72

1050

1.67

1.98

1.84

1.47

2.25

2.10

1.19

2.55

2.37

0.84

2.86

2.67

0.49

3.17

2.96

1090

1.86

2.12

1.97

1.66

2.41

2.24

1.40

2.72

2.54

1.04

3.06

2.86

-

-

-

NOTES: 1. Blower performance includes a wet indoor coil and 2" filters.

2. Blower performance includes the maximum number of heat exchangers.
3. Refer to page 8 for the resistance of the unit accessories.
    ESP = External Static Pressure available for the supply and return air duct sytem. All internal unit resistances have been deducted from the total static pressure of the blower.

MODEL BHN120 - (BOTTOM DUCT APPLICATIONS)

511.17-TG2Y 

8

Unitary Products Group

Содержание SUNLINE 2000 B1HN090

Страница 1: ...unit and discard them If a bottom supply return is desired you simply remove the two bottom duct covers and discard them No panel cutting or swapping is required Convertible airflow design allows max...

Страница 2: ...M PROTECTION Crankcase heaters and internal compressor protection are standard on all compressors Each unit has suction line freezestats low pressure switches high pressure switches and high temperatu...

Страница 3: ...e refrigeration system including circulating fan heat BTU s per hour divided by the total electric input watts x 3 412 AFUE Annual Fuel Utilization Efficiency determined in accordance with DOE test pr...

Страница 4: ...4 0 CHARGE REFRIGERANT 22 lbs oz SYSTEM NO 1 9 0 11 8 SYSTEM NO 2 9 0 13 8 NOTE Filter racks are adapted for 1 or 2 thick filters PHYSICAL DATA COMPONENT WEIGHTS BASIC COMPONENT MODEL BHN 090 120 Basi...

Страница 5: ...W Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 3750 72 99 8 6 80 69 58 46...

Страница 6: ...Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH Total Cap 1 MBH Power Input2 KW Sensible Capacity 1 MBH CFM WB F Entering Dry Bulb F Entering Dry Bulb F 86 83 80 77 74 71 68 86 83 80 77 74 71...

Страница 7: ...56 6 8 68 6 9 79 7 5 93 8 3 CFM RET AIR F CAP KW OUTDOOR AIR TEMPERATURE F 72 RH 10 0 10 20 30 40 50 60 3000 55 MBH KW 30 7 1 41 7 2 52 7 4 64 7 6 77 7 9 93 8 3 109 8 7 127 9 6 70 MBH KW 29 7 4 39 7...

Страница 8: ...0 1 61 1 66 1 55 1 44 1 81 1 69 1 10 2 10 1 96 MODEL BHN090 BOTTOM DUCT APPLICATIONS BLOWER PERFORMANCE 7 1 2 10 TON SUPPLY AIR BLOWER SPEED RPM CFM 3000 3500 4000 4500 5000 ESP BHP KW ESP BHP KW ESP...

Страница 9: ...16 7 9 6 8 3 150 73 59 3 5 2 5 2 54 10 6 4 8 3 9 55 9 31 4 27 6 70 40 35 Dual numbers shown as 17 3 16 7 indicates compressor 1 2 respectively NOTES 1 Dual element time delay type 2 Maximum HACR break...

Страница 10: ...must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit The products of combustion must not be allowed to accumulate within a confined spac...

Страница 11: ...3 Replace the side duct covers DETAIL X SIDE SUPPLY AND RETURN AIR DUCT OPENINGS CENTER OF GRAVITY B A R O M E T R I C R E L I E F R A I N H O O D R E A R V I E W L H E N D V I E W 2 3 3 8 2 3 3 4 A...

Страница 12: ...310 378 302 120 1 612 322 416 492 382 BHN UNIT 6 POINT LOADS LBS TOTAL A B C D E F 090 1 237 155 186 217 264 226 189 120 1 612 199 246 293 347 291 236 NOTE These weights are with economizer and 24kW e...

Страница 13: ...the curb from the roof All electrical connections can be made inside the curb ROOF CURB BENEFITS UNIT AND CURB APPLICATION ROOF CURB DIMENSIONS BHN 7 1 2 10 TON Supply and Return Air including duct s...

Страница 14: ...rainhood and filters The outdoor air dampers open when the indoor fan motor is energized Damper capable of providing 0 thru 100 of outdoor return air opening MANUAL OUTDOOR DAMPER Provides 0 thru 35 o...

Страница 15: ...511 17 TG2Y Unitary Products Group 15...

Страница 16: ...up P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1998 All Rights Reserved Code EBY EGY 511 17 TG2Y Superse...

Отзывы: