96
YORK INTERNATIONAL
97
YORK INTERNATIONAL
FORM 201.19-EG4
Electrical Data
MULTIPLE POINT POWER SUPPLY CONNECTION -3 & 4 COMPRESSOR UNITS (SEE FIG. 5 or 6)
(Two Field Provided Power Supply Circuits To The Chiller. Field Connections to Factory Provided Terminal Block (Std) or Disconnects (Opt)
in the Options Panel. Factory-wired Terminal Blocks or Individual System Circuit Breakers (Opt
10
) in each of the two Motor Control Centers.)
SYSTEM #1 FIELD-SUPPLIED WIRING
FACTORY PROVIDED (LUGS)
MODEL
VOLTS
MIN NF
WIRE RANGE
7
COMPRESSOR #3 FANS
11, 12
YCAS MCA
1
DISC SW
2, 9
STD. TERMINAL OPT. NF. RLA Y-D-LRA XL-LRA RLA Y-D-LRA XL-LRA QTY FLA LRA
MIN.
3, 5
MAX.
4, 6
BLOCK DISC SW. (EA.) (EA.)
380 326 400 350 400 2/0 - 500 (2) 3/0 - 250 121 285 900 121 285 900 8 5.1 21.0
0218EB
460 278 400 300 350 2/0 - 500 (2) 3/0 - 250 100 228 719 100 228 719 8 5.2 29.0
575 220 250 250 250 2/0 - 500 #6 - 350 80 182 574 80 182 574 8 3.9 25.9
380 441 600 500 600 (2) 1/0 - 300 (2) 250-500 121 285 900 213 343 1093 8 5.1 21.0
0248EB
460 373 400 450 500 2/0 - 500 (2) 3/0 - 250 100 228 719 176 280 893 8 5.2 29.0
575 296 400 350 400 2/0 - 500 (2) 3/0 - 250 80 182 574 141 224 714 8 3.9 25.9
380 426 600 500 500 (2) 1/0 - 300 (2) 250-500 165 343 1093 165 343 1093 8 5.1 21.0
0268EB
460 361 400 400 450 2/0 - 500 (2) 3/0 - 250 137 280 893 137 280 893 8 5.2 29.0
575 285 400 350 350 2/0 - 500 (2) 3/0 - 250 109 224 714 109 224 714 8 3.9 25.9
380 485 600 600 600 (2) 1/0 - 300 (2) 250-500 212 343 1093 166 343 1093 8 5.1 21.0
0288EB
460 410 600 450 500 2/0 - 500 (2) 250-500 176 280 893 137 280 893 8 5.2 29.0
575 325 400 400 400 2/0 - 500 (2) 3/0 - 250 141 224 714 109 224 714 8 3.9 25.9
380 473 600 600 600 (2) 1/0 - 300 (2) 250-500 195 343 1093 166 343 1093 9 5.1 21.0
0308EB
460 402 600 450 500 2/0 - 500 (2) 3/0 - 250 161 280 893 137 280 893 9 5.2 29.0
575 318 400 350 400 2/0 - 500 (2) 3/0 - 250 129 224 714 109 224 714 9 3.9 25.9
380 492 600 600 600 (2) 1/0 - 300 (2) 250-500 195 343 1093 184 343 1093 11 5.1 21.0
0328EB
460 417 600 450 500 (2) 1/0 - 300 (2) 250-500 161 280 893 152 280 893 11 5.2 29.0
575 330 400 400 450 2/0 - 500 (2) 3/0 - 250 129 224 714 122 224 714 11 3.9 25.9
380 427 600 500 500 (2) 1/0 - 300 (2) 250-500 166 343 1093 166 343 1093 8 5.1 21.0
0358EB
460 363 400 400 450 2/0 - 500 (2) 3/0 - 250 138 280 893 138 280 893 8 5.2 29.0
575 285 400 350 350 2/0 - 500 (2) 3/0 - 250 109 224 714 109 224 714 8 3.9 25.9
380 473 600 600 600 (2) 1/0 - 300 (2) 250-500 194 343 1093 166 343 1093 9 5.1 21.0
0398EB
460 403 600 450 500 2/0 - 500 (2) 3/0 - 250 162 280 893 138 280 893 9 5.2 29.0
575 318 400 350 400 2/0 - 500 (2) 3/0 - 250 129 224 714 109 224 714 9 3.9 25.9
380 526 600 600 700 (2) 2/0 - 500 (2) 250-500 196 343 1093 213 343 1093 9 5.1 21.0
0418EB
460 444 600 500 600 (2) 1/0 - 300 (2) 250-500 162 280 893 176 280 893 9 5.2 29.0
575 353 400 400 450 2/0 - 500 (2) 3/0 - 250 129 224 714 141 224 714 9 3.9 25.9
See page 105 for Electrical Data footnotes.
OVER-CURRENT
PROTECTION
FIELD PROVIDED POWER SUPPLY
COMPRESSOR #1
Содержание R-407C Optimized
Страница 91: ...91 YORK INTERNATIONAL FORM 201 19 EG4 This page intentionally left blank...
Страница 110: ...110 YORK INTERNATIONAL Typical Control Wiring 2 Compressor...
Страница 118: ...118 YORK INTERNATIONAL This page intentionally left blank...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 19 EG4 This page intentionally left blank...