246824-YTG-G-1208
Johnson Controls Unitary Products
65
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZH120 (10 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
675
0.53
726
0.74
776
0.94
824
1.12
870
1.30
914
1.48
957
1.65
1000
1.82
1041
1.99
1082
2.17
2800
686
0.63
738
0.84
787
1.04
835
1.23
881
1.41
925
1.58
969
1.76
1011
1.93
1052
2.10
1093
2.27
3000
699
0.75
750
0.96
800
1.16
847
1.34
893
1.52
938
1.70
981
1.87
1024
2.04
1065
2.21
1106
2.39
3200
713
0.88
764
1.09
814
1.28
861
1.47
907
1.65
952
1.83
995
2.00
1037
2.17
1079
2.34
1119
2.52
3400
728
1.02
779
1.23
829
1.43
877
1.61
923
1.79
967
1.97
1010
2.14
1053
2.31
1094
2.48
1135
2.66
3600
745
1.18
796
1.39
846
1.59
893
1.77
939
1.95
984
2.13
1027
2.30
1069
2.47
1111
2.64
1152
2.82
3800
763
1.36
815
1.57
864
1.76
912
1.95
958
2.13
1002
2.31
1046
2.48
1088
2.65
1129
2.82
1170
3.00
4000
783
1.55
835
1.76
884
1.96
932
2.15
978
2.33
1022
2.50
1066
2.67
1108
2.84
1149
3.02
1190
3.19
4200
805
1.77
856
1.98
906
2.17
953
2.36
999
2.54
1044
2.72
1087
2.89
1129
3.06
1171
3.23
1211
3.41
4400
828
2.00
879
2.21
929
2.41
976
2.59
1022
2.77
1067
2.95
1110
3.12
1152
3.29
-
-
-
-
4600
852
2.25
904
2.46
953
2.66
1001
2.85
1047
3.03
1092
3.20
1135
3.37
-
-
-
-
-
-
4800
879
2.52
930
2.73
980
2.93
1027
3.12
1073
3.30
-
-
-
-
-
-
-
-
-
-
5000
906
2.81
958
3.02
1007
3.22
1055
3.41
-
-
-
-
-
-
-
-
-
-
-
-
3 HP & Field Supplied Drive
ZH150 (12.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive
Standard 3 HP & Drive
3200
713
0.88
764
1.09
814
1.28
861
1.47
907
1.65
952
1.83
995
2.00
1037
2.17
1079
2.34
1119
2.52
3400
728
1.02
779
1.23
829
1.43
877
1.61
923
1.79
967
1.97
1010
2.14
1053
2.31
1094
2.48
1135
2.66
3600
745
1.18
796
1.39
846
1.59
893
1.77
939
1.95
984
2.13
1027
2.30
1069
2.47
1111
2.64
1152
2.82
3800
763
1.36
815
1.57
864
1.76
912
1.95
958
2.13
1002
2.31
1046
2.48
1088
2.65
1129
2.82
1170
3.00
4000
783
1.55
835
1.76
884
1.96
932
2.15
978
2.33
1022
2.50
1066
2.67
1108
2.84
1149
3.02
1190
3.19
4200
805
1.77
856
1.98
906
2.17
953
2.36
999
2.54
1044
2.72
1087
2.89
1129
3.06
1171
3.23
1211
3.41
4400
828
2.00
879
2.21
929
2.41
976
2.59
1022
2.77
1067
2.95
1110
3.12
1152
3.29
1194
3.46
1235
3.64
4600
852
2.25
904
2.46
953
2.66
1001
2.85
1047
3.03
1092
3.20
1135
3.37
1177
3.54
1219
3.72
1259
3.89
4800
879
2.52
930
2.73
980
2.93
1027
3.12
1073
3.30
1118
3.47
1161
3.65
1203
3.82
1245
3.99
1285
4.16
5000
906
2.81
958
3.02
1007
3.22
1055
3.41
1101
3.59
1146
3.76
1189
3.94
1231
4.11
1273
4.28
1313
4.45
5200
936
3.12
987
3.33
1037
3.53
1084
3.72
1130
3.90
1175
4.07
1218
4.24
1260
4.42
1302
4.59
1343
4.76
5400
966
3.45
1018
3.66
1067
3.86
1115
4.05
1161
4.23
1206
4.40
1249
4.57
1291
4.74
1333
4.91
1373
5.09
5600
999
3.80
1050
4.01
1100
4.20
1147
4.39
1193
4.57
1238
4.75
1281
4.92
1323
5.09
1365
5.26
1405
5.44
5800
1032
4.16
1084
4.37
1133
4.57
1181
4.75
1227
4.93
1271
5.11
1315
5.28
1357
5.45
1398
5.62
-
-
6000
1067
4.54
1119
4.75
1168
4.95
1216
5.13
1262
5.31
1306
5.49
1350
5.66
-
-
-
-
-
-
6200
1103
4.94
1155
5.15
1204
5.34
1252
5.53
1298
5.71
-
-
-
-
-
-
-
-
-
-
Hi Static 5 HP & Drive
5 HP & Field Supplied Drive
Содержание PREDATOR R-410A
Страница 112: ...246824 YTG G 1208 112 Johnson Controls Unitary Products Typical ZR078 120 Reheat Wiring Diagram...
Страница 113: ...246824 YTG G 1208 Johnson Controls Unitary Products 113 Typical ZR150 Reheat Wiring Diagram...
Страница 126: ...246824 YTG G 1208 126 Johnson Controls Unitary Products...
Страница 127: ...246824 YTG G 1208 Johnson Controls Unitary Products 127...