TABLE 39: 10 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP
†
TURNS OPEN
‡
0
1
2
3
4
5
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
0.2
-
-
-
-
-
-
-
-
-
-
-
-
5067
2614
2.80
4809
2290
2.46
0.4
-
-
-
-
-
-
5179
3112
3.34
4884
2703
2.90
4729
2401
2.57
4459
2113
2.27
0.6
-
-
-
-
-
-
4925
2943
3.16
4585
2521
2.70
4429
2244
2.41
4137
1964
2.11
0.8
-
-
-
4974
3220
3.45
4607
2727
2.92
4267
2342
2.51
4099
2080
2.23
3783
1809
1.94
1.0
4975
3453
3.70
4657
2995
3.21
4305
2550
2.73
3941
2171
2.33
3751
1919
2.06
3371
1630
1.75
1.2
4679
3423
3.67
4366
2808
3.01
4022
2373
2.54
3545
1978
2.12
3305
1741
1.87
-
-
-
1.4
4429
3065
3.29
4040
2607
2.80
3669
2673
2.87
2918
1700
1.82
-
-
-
-
-
-
1.6
4107
2845
3.05
3620
2357
2.53
2931
1830
1.96
-
-
-
-
-
-
-
-
-
1.8
3553
2500
2.68
2756
1899
2.04
-
-
-
-
-
-
-
-
-
-
-
-
2.0
2439
1939
2.08
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*.
Blower performance includes two-inch throwaway filters.
†.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the
total static pressure of the blower.
‡.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
**.
W = Watts
TABLE 40: 12-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP
†
TURNS OPEN
‡
0
1
2
3
4
5
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
CFM
W
**
BHP
0.4
-
-
-
-
-
-
5201
3162
3.39
4966
2796
3.00
4681
2405
2.58
4355
2054
2.20
0.6
-
-
-
5220
3395
3.64
4942
2980
3.20
4657
2608
2.80
4358
2230
2.39
4007
1890
2.03
0.8
-
-
-
4944
3194
3.43
4661
2806
3.01
4378
2572
2.76
4016
2057
2.21
-
-
-
1.0
5003
3490
3.74
4647
2988
3.20
4380
2636
2.83
4030
2257
2.42
-
-
-
-
-
-
1.2
4724
3290
3.53
4363
2875
3.08
4012
2505
2.69
-
-
-
-
-
-
-
-
-
1.4
4428
3040
3.26
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
*.
Blower performance includes two-inch throwaway filters.
†.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the
total static pressure of the blower.
‡.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
**.
W = Watts
Содержание Predator BP078
Страница 27: ...127421 YIM C 0606 Unitary Products Group 27 TABLE 24 7 1 2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE1 ...
Страница 33: ...127421 YIM C 0606 Unitary Products Group 33 TABLE 35 7 1 2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE1 ...
Страница 54: ...127421 YIM C 0606 54 Unitary Products Group ...