TABLE 16: 

Air Flow Data - 60 Hz Models

208 Volt

Models

Blower

Motor

Speed

CFM

@ External Static Pressure - IWC

m³/min @ External Static Pressure - Pascal

0.10

0.20

0.30 0.40

0.50

0.60 0.70

0.80 0.90 1.00 0.025 0.050 0.075 0.100 0.125 0.150 0.175 0.200 0.225 0.250

MX12B

Hi/#1

1234 1212 1178 1145 1079 1043 995 911 623 371 34.54 33.94 33.00 32.05 30.20 29.20 27.87 25.50 17.44 10.40

MedHi/#2

1099 1066 1037 987 933 888 801

NA

NA

NA 30.76 29.86 29.03 27.65 26.13 24.86 22.43

NA

NA

NA

Med/#3

928 892 840 768 731 664 566 523 476 226 25.99 24.98 23.53 21.52 20.48 18.60 15.84 14.64 13.33 6.32

MedLo/#4

859 705 612 502 472 403 328

NA

NA

NA 24.06 19.75 17.12 14.06 13.21 11.28 9.19

NA

NA

NA

Lo/#5

835 635 451 396 315

NA

NA

NA

NA

NA 23.37 17.79 12.62 11.08 8.83

NA

NA

NA

NA

NA

MX12D

Hi/#1

1510 1366 1307 1234 1176 1116 1051 917 834 696 42.27 38.25 36.60 34.54 32.93 31.24 29.44 25.69 23.34 19.48

MedHi/#2 1421 1224 1120 1051 988 914 780 740 669 583 39.77 34.28 31.36 29.43 27.65 25.60 21.84 20.72 18.73 16.31

Med/#3

1345 1124 889 812 675 615 568 501 424 384 37.65 31.48 24.90 22.74 18.90 17.22 15.89 14.03 11.87 10.75

MedLo/#4 1272 1034 616 518 454 351 313 271 250 210 35.61 28.95 17.23 14.52 12.71 9.84

8.76

7.57

6.99

5.88

Lo/#5

1219 928 451 349 287 244 212 110

NA

NA 34.12 25.98 12.62 9.77

8.05

6.83

5.93

3.08

NA

NA

MX16C

Hi/#1

1805 1771 1737 1696 1652 1587 1531 1469 1371 924 50.54 49.60 48.64 47.48 46.27 44.43 42.86 41.14 38.37 25.87

MedHi/#2 1637 1589 1558 1512 1455 1397 1343 1291 1194 853 45.83 44.48 43.63 42.34 40.73 39.11 37.59 36.14 33.44 23.87

Med/#3

1470 1424 1381 1327 1266 1211 1154 1068 1005 760 41.16 39.87 38.67 37.14 35.44 33.91 32.30 29.90 28.13 21.29

MedLo/#4 1327 1237 1171 1109 1049 976 875 807 720 658 37.15 34.63 32.79 31.06 29.37 27.34 24.49 22.59 20.16 18.42

Lo/#5

1279 1063 992 935 858 762 667 587 508 428 35.82 29.76 27.78 26.19 24.03 21.33 18.68 16.44 14.23 11.98

MX20D

Hi/#1

2075 2031 1996 1957 1912 1862 1813 1762 1693 1524 58.11 56.88 55.90 54.80 53.53 52.14 50.76 49.33 47.42 42.66

MedHi/#2 1896 1849 1808 1766 1720 1679 1636 1585 1532 1461 53.10 51.77 50.63 49.46 48.16 47.02 45.80 44.38 42.89 40.90

Med/#3

1685 1638 1587 1539 1489 1444 1398 1349 1294 1248 47.19 45.86 44.44 43.10 41.69 40.44 39.14 37.76 36.23 34.95

MedLo/#4 1527 1481 1425 1370 1323 1277 1227 1166 1118 1065 42.77 41.48 39.90 38.36 37.04 35.75 34.35 32.64 31.32 29.82

Lo/#5

1465 1301 1244 1177 1119 1065 998 927 833 795 41.03 36.42 34.84 32.96 31.33 29.81 27.93 25.96 23.31 22.26

230 Volt

Models

Blower

Motor

Speed

CFM

@ External Static Pressure - IWC

m³/min @ External Static Pressure - Pascal

0.10

0.20

0.30 0.40

0.50

0.60 0.70

0.80 0.90 1.00 0.025 0.050 0.075 0.100 0.125 0.150 0.175 0.200 0.225 0.250

MX12B

Hi/#1

1264 1241 1209 1184 1132 1067 1037 988 821 493 35.40 34.74 33.87 33.16 31.70 29.87 29.04 27.66 22.98 13.81

MedHi/#2

1107 1073 1048 997 948 902 855 778 586 370 30.98 30.05 29.34 27.93 26.55 25.25 23.93 21.79 16.41 10.36

Med/#3

937 904 861 807 736 682 582 557 501 357 26.24 25.32 24.10 22.59 20.62 19.09 16.31 15.59 14.04 10.01

MedLo/#4

875 688 629 559 465 418 348 377

NA

NA 24.51 19.25 17.62 15.66 13.03 11.70 9.75 10.54

NA

NA

Lo/#5

839 549 466 404 328 285 205 181 154

NA 23.49 15.38 13.06 11.33 9.19

7.97

5.75

5.08

4.30

NA

MX12D

Hi/#1

1485 1362 1304 1248 1180 1130 1065 985 863 708 41.59 38.13 36.52 34.95 33.05 31.63 29.83 27.58 24.18 19.83

MedHi/#2 1408 1198 1119 1054 989 911 801 746 701 618 39.43 33.54 31.34 29.50 27.70 25.52 22.42 20.88 19.63 17.31

Med/#3

1348 1115 888 817 676 635 577 528 447 407 37.74 31.23 24.86 22.89 18.93 17.78 16.15 14.78 12.51 11.39

MedLo/#4 1278 1019 580 518 454 363 318 284 262 225 35.78 28.52 16.23 14.51 12.71 10.18 8.89

7.95

7.35

6.30

Lo/#5

1240 964 441 352 294 252 214 187

NA

NA 34.72 27.00 12.34 9.87

8.23

7.05

6.00

5.24

NA

NA

MX16C

Hi/#1

1869 1833 1804 1772 1728 1674 1623 1554 1150 383 52.33 51.33 50.50 49.63 48.38 46.89 45.43 43.51 32.19 10.72

MedHi/#2 1695 1653 1627 1576 1527 1477 1419 1370 751

NA 47.45 46.29 45.56 44.13 42.75 41.37 39.73 38.35 21.02

NA

Med/#3

1546 1513 1468 1417 1361 1310 1253 1120 892 387 43.29 42.36 41.10 39.67 38.10 36.67 35.10 31.36 24.97 10.84

MedLo/#4 1327 1283 1223 1163 1105 1036 857 768 614 384 37.16 35.93 34.24 32.56 30.93 29.00 24.00 21.50 17.20 10.76

Lo/#5

1241 1103 1037 968 891 759 629 581 523 381 34.74 30.88 29.03 27.11 24.95 21.24 17.61 16.28 14.66 10.67

MX20D

Hi/#1

2085 2046 2008 1976 1935 1879 1836 1797 1724 1559 58.37 57.28 56.21 55.32 54.19 52.62 51.41 50.32 48.26 43.66

MedHi/#2 1917 1868 1829 1792 1731 1702 1655 1615 1568 1485 53.68 52.30 51.20 50.16 48.47 47.66 46.33 45.22 43.91 41.58

Med/#3

1678 1645 1601 1556 1502 1461 1406 1362 1319 1280 46.98 46.07 44.82 43.57 42.04 40.90 39.36 38.14 36.94 35.84

MedLo/#4 1534 1494 1435 1384 1344 1289 1236 1192 1142 1086 42.97 41.82 40.18 38.75 37.62 36.08 34.62 33.39 31.97 30.41

Lo/#5

1410 1259 1211 1148 1095 1038 996 940 840 800 39.47 35.24 33.90 32.13 30.65 29.06 27.90 26.32 23.53 22.40

NOTE: 

Air flow data shown above 1/2” w.c. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is limited to 

1/2” w.c. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.

1. Dry coil conditions only, tested without filters.
† Speed temp High #1 not recommended for the unit.
Air handler units are UL Listed up to 0.5" w.c. external static pressure, including air filter, wet coil, and largest kW size heater, unless otherwise noted.

Содержание MX Series

Страница 1: ...vailable from Distribution may be applied to the center of the blower access panel The unit can be positioned for bottom return air in the upflow position top return air in the downflow position and r...

Страница 2: ...HUD modular home construction practices These instructions are required as a minimum for a safe installation INSPECTION As soon as a unit is received it should be inspected for possible dam age durin...

Страница 3: ...document 13 Reposition and replace blower access panel AIR HANDLER AND COIL DOWNFLOW 1 Position blower casing over duct connection and secure such that the supply air end of the blower is down 2 Apply...

Страница 4: ...insulation The supply air duct should be properly sized by use of a transition to match unit opening All ducts should be suspended using flexible hang ers and never fastened directly to the structure...

Страница 5: ...heater is installed mark the name plate appropriately to indicate that no heat kit is installed The HEAT ENABLE jumper See Figure 10 must be moved to the HEAT position to enable operation of the heat...

Страница 6: ...e HEAT position if a heat kit is installed with the air handler With the jumper in the NO HEAT position the control will not energize the heat relay outputs or sense the limit switch input If the jump...

Страница 7: ...lay outputs and energize the blower if it wasn t already ener gized When the limit switch closes the control will re energize electric heat according to the thermostat inputs using normal timings Fan...

Страница 8: ...ss current than copper conductors of the same size SECTION VIII BLOWER SPEED CONNECTIONS All air handlers contain a programmed 5 speed high efficiency brush less DC motor Adjust blower motor speed to...

Страница 9: ...5 6 7 5 4HK 6501006 0 5 Med 3 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501306 0 5 Med 3 9 8 13 33 3 44 4 3 3 4 3 6 5 8 6 9 8 13 4HK165N1506 0 5 Med 3 10 8 14 4 36 9 49 1 3 6 4 8 7 2 9 6 10 8 14...

Страница 10: ...0 110 3 3 4HK16502006 80 94 1 107 5 100 110 3 2 4HK16502506 100 115 7 132 5 125 150 1 1 0 1 O C P Over Current Protection device must be HACR type Circuit Breaker or Time Delay fuse TABLE 12 Electrica...

Страница 11: ...4 18 24 1 See conversion Table 10 TABLE 14 Electrical Data For Single Source Power Supply Copper Wire 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O...

Страница 12: ...0 70 0 80 0 90 1 00 0 025 0 050 0 075 0 100 0 125 0 150 0 175 0 200 0 225 0 250 MX12B Hi 1 1264 1241 1209 1184 1132 1067 1037 988 821 493 35 40 34 74 33 87 33 16 31 70 29 87 29 04 27 66 22 98 13 81 Me...

Страница 13: ...move humidistat jumper on air handler control board 3 For heat pump applications set MODE jumper on air handler control board to the HP position 4 To change quantity of heat during HP defrost cycle re...

Страница 14: ...1 and W2 on air handler control board SECTION X MAINTENANCE Filters must be cleaned or replaced when they become dirty Inspect at least once per month The frequency of cleaning depends upon the hours...

Страница 15: ...819682 UIM A 0212 Johnson Controls Unitary Products 15 SECTION XI WIRING DIAGRAM FIGURE 13 Wiring Diagram MX12 16...

Страница 16: ...otice Published in U S A 819682 UIM A 0212 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 628582 UIM A 0111 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIG...

Отзывы: