JOHNSON CONTROLS
5
Form 160.00-N6
Issue date: 08/27/2021
Unit model number nomenclature
MVVSD __ __ __ __ __ __ - __ __
{
{
Maximum drive
horsepower rating
0500 = 500 hp
0600 = 600 hp
0700 = 700 hp
0800 = 800 hp
0900 = 900 hp
1000 = 1000 hp
1250 = 1250 hp
1500 = 1500 hp
1750 = 1750 hp
2000 = 2000 hp
2250 = 2250 hp
2500 = 2500 hp
R = Remote mount
K = YK, YD, and YK-EP oil
pump supply
Input voltage code
80 = 2300 V/60 Hz
84 = 4160 V/60 Hz
85 = 6600 V/60 Hz
92 = 3300 V/50 Hz
94 = 3300 V/60 Hz
95 = 6600 V/50 Hz
2 5 0 0 R K 8 4
Overload:
105% Full Load RMS current for 40 seconds.
Anti-recycle time:
5 immediate restarts followed by a 10 minute delay.
Efficiency:
96% at rated input voltage and load.
Code approval:
cUL, UL, and CE.
Environmental:
32°F to 104°F (0°C to 40°C), max. 95% humidity, non-condensing, 5000 ft (1524 m) altitude.
Vibration:
0.5 G or less at 10 Hz to 60 Hz
Enclosure:
NEMA 1, IP20, IEC-529.
MVVSD requirements
MVVSD input/output requirements
Nominal rated input voltage
2300
3300
3300
4160
6600
Maximum continuous input voltage
2530
3630
3630
4576
7260
Minimum continuous input voltage
2070
2970
2970
3744
5490
Maximum voltage input dip
10%
10%
10%
10%
10%
Absolute minimum input dip voltage
1955
2805
2805
3536
5610
Input frequency
60 Hz
±2 Hz
50 Hz
±2 Hz
60 Hz
±2 Hz
60 Hz
±2 Hz
60/50 Hz
±2 Hz
Input frequency rate of change
10 Hz/s
10 Hz/s
10 Hz/s
10 Hz/s
10 Hz/s
Maximum input phase unbalance
3%
3%
3%
3%
3%
Input interrupting capacity
50 KA
50 KA
50 KA
50 KA
50 KA
Output voltage
2300
3300
3300
4160
4160
Maximum output frequency
60 Hz
50 Hz
60 Hz
60 Hz
60 Hz