background image

5715184-BIM-A-0519

30

Johnson Controls Ducted Systems

SECTION IX: SAFETY CONTROLS

CONTROL CIRCUIT FUSE

A 3-amp fuse is provided on the control circuit board to protect the 24-
volt transformer from overload caused by control circuit wiring errors.
This is an ATO 3, automotive type fuse and is located on the control
board.

BLOWER DOOR SAFETY SWITCH

This unit is equipped with an electrical interlock switch mounted in the
burner compartment. This switch interrupts all power at the unit when
the panel covering the blower compartment is removed.

Electrical supply to this unit is dependent upon the panel that covers the
blower compartment being in place and properly positioned.

ROLLOUT SWITCH CONTROLS

These controls are mounted on the burner assembly. If the temperature
in the area surrounding the burner exceeds its set point, the gas valve
is de-energized. The operation of this control indicates a malfunction in
the combustion air blower, heat exchanger or a blocked vent pipe con-
nection. Corrective action is required. These are manual reset controls
that must be reset before operation can continue.

PRESSURE SWITCHES

This furnace is supplied with two pressure switches, which monitor the
flow through the combustion air/vent piping and condensate drain sys-
tem. These switches de-energize the gas valve if any of the following
conditions are present. Refer to "CONDENSATE PIPING AND FUR-
NACE VENTING CONFIGURATION" for tubing connections.

Blockage of vent piping or terminal

Failure of combustion air blower motor

Blockage of combustion air piping or terminals

Blockage of condensate drain piping

LIMIT CONTROLS

There is a high temperature limit control located on the furnace vesti-
bule panel near the gas valve. This is an automatic reset control that
provides over temperature protection due to reduced airflow. This may
be caused by the following:

A dirty filter

Indoor fan motor failure

Too many supply or return registers closed or blocked off

The control module locks out if the limit trips 5 consecutive times. If this
occurs, the control resets and tries ignition again after 1 hour.

SECTION X: NORMAL OPERATION AND 

DIAGNOSTICS

NORMAL OPERATION SEQUENCE

The following describes the sequence of operation of the furnace. Refer
to Owners Manual for component location.

Continuous Blower

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the ON position the thermostat circuit is completed
between terminals R and G. The motor operates continuously on the
speed tap wire that is connected to the HI COOL cooling terminal on the
control board. To obtain a constant air circulation at lower flow rate,
change the high-speed wire to another low-speed wire.

Intermittent Blower - Cooling

Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling. The motor
operates on the speed tap wire that is connected to the HI COOL cool-
ing terminal on the control board. The fan-off setting is fixed at 60 sec-
onds to improve cooling efficiency.

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. When the proper amount of combustion air is
provided, the pressure switch closes and the ignition control provides a
17-second ignitor warm-up period. The gas valve then opens, the gas
starts to flow, ignition occurs, and the flame sensor begins its sensing
function. The blower motor energizes 30 seconds after the gas valve
opens, if a flame is detected. Normal furnace operation continues until
the thermostat circuit between R and W is opened, which causes the
ignition system and gas valve to de-energize and the burner flames to
be extinguished. The vent motor operates for 15 seconds and the
blower motor operates for the amount of time set by the fan-off delay
jumper located on the control board. See Figure 33. The heating cycle
is now complete, and ready for the start of the next heating cycle.

If the flame is not detected within 7 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. Also, if the flame
is lost for 2 seconds during the 10-second stabilization period, the gas
valve is shut off and a retry operation begins. During a retry operation,
the vent motor starts a 15-second inter-purge and the ignitor warm-up
time is extended to 27 seconds. If the flame is established for more than
10 seconds after ignition during a retry, the control clears the ignition
attempt (retry) counter. If three retries occur during a call for heat, the
furnace shuts down for one hour. If there is a call for heat at the end of
the one-hour shut down, the furnace initiates a normal start cycle. If the
problem has not been corrected, the furnace locks out again after three
retries.

A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit results in a disruption in the flame and is sensed within 1.0 sec-
onds. The gas valve de-energizes and the control begins a recycle
operation. A normal ignition sequence begins after a 15-second inter-
purge. If during the five recycles the gas supply does not return, or the
fault condition is not corrected, the ignition control locks out for 60 min-
utes.

During burner operation, a momentary loss of power for 50 milliseconds
or longer de-energizes the gas valve. When the power is restored, the
gas valve remains de-energized and the ignition sequence immediately
restarts.

IGNITION SYSTEM SEQUENCE

1.

Turn the gas supply ON at external valve and main gas valve.

2.

Set the thermostat above room temperature to call for heat.

3.

System start-up occurs as follows:

a.

The induced draft blower motor starts and comes up to
speed. Shortly after inducer start-up, the hot surface igniter
glows for about 17 seconds.

b.

After this warm up, the ignition module energizes (opens) the
main gas valve.

c.

After flame is established, the supply air blower starts within
approximately 30 seconds.

TROUBLESHOOTING

The following visual checks must be made before troubleshooting:

1.

Check to see that the power to the furnace and the ignition control
module is ON.

2.

The manual shut-off valves in the gas line to the furnace must be
open.

3.

Make sure all wiring connections are secure.

4.

Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response, then use the troubleshooting section in this manual to
check the system’s operation.

 CAUTION

Main power to the unit must still be interrupted at the main power
disconnect switch before any service or repair work is to be done to
the unit. Do not rely upon the interlock switch as a main power dis-
connect.
Blower and burner must never be operated without the blower
panel in place.

!

Содержание MM9E Series

Страница 1: ...Termination 21 Downward Venting 22 Direct Vent Air Intake Connection and Vent Connection 22 Outside and Ambient Combustion Air 23 Attic and Crawl Space Combustion Air Termination 24 Gas Valve 27 Readi...

Страница 2: ...The size of the unit must be based on an acceptable heat loss cal culation for the structure ACCA Manual J or other approved meth ods may be used 12 When moving or handling this furnace prior to inst...

Страница 3: ...hes etc Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials When outdoor air is used for combustion the combustion air intake duct system...

Страница 4: ...r protected to avoid physical damage by vehicles 24 in clearance in front and 18 in on side recommended for service access All furnaces approved for alcove installation FOR FURNACES INSTALLED IN THE C...

Страница 5: ...urnace does not operate properly The ducts attached to the furnace plenum must be of sufficient size so the furnace operates at the specified external static pressure and within the air temperature ri...

Страница 6: ...wnflow installations must use a suitable duct connector approved by the furnace manufacturer for use with this furnace The duct connec tors are designed to be connected to the rectangular duct under t...

Страница 7: ...Filters Downflow furnaces typically are installed with the filters located above the furnace extending into the return air plenum or duct Any branch duct rectangular or round duct attached to the plen...

Страница 8: ...ng 7 6 9 17 5 7 6 9 17 5RWDWH YHQW EORZHU HLWKHU ZD IMPORTANT On all installations without a coil a removable access panel is recommended in the outlet duct such that smoke or reflected light would be...

Страница 9: ...ZQIORZ RPEXVWLRQ LU QOHW DV 3LSH QWU OHFWULFDO QWU RQGHQVDWH UDLQ 2SWLRQDO 5HWXUQ LU XWRXW LWKHU VLGH RU ODGGHG GRRU DGG DSSR LPDWHO DQ DGGLWLRQDO 6833 1 RPEXVWLRQ LU QOHW 5 7851 1 9HQW RQQHFWLRQ 2XWO...

Страница 10: ...pples and conventional 90 degree elbow s to enter through the cabinet access holes FIGURE 11 Gas Valve DANGER An overpressure protection device such as a pressure regulator must be installed in the ga...

Страница 11: ...be shut off prior to disconnecting the electrical power before proceeding with the conversion WARNING SHOCK HAZARD Turn off electrical supply to furnace WARNING Never use an open flame to check for l...

Страница 12: ...thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the main electrical source disconnected connect the thermostat wiring from the w...

Страница 13: ...nsate pan is self priming and contains an inter nal trap to prevent flue gas leaking Do not install an external con densate trap IMPORTANT The furnace indoor coil and humidifier drains may be combined...

Страница 14: ...taken to prevent the drain line from freezing Failure to provide proper protection from freezing can result in improper operation or damage to the equipment and possible property damage When exposed t...

Страница 15: ...I VR WKDW QR VDJJLQJ ORRSV ZLOO FROOHFW DQG KROG FRQGHQVDWH ZKLFK ZLOO FDXVH WKH IXUQDFH WR QRW RSHUDWH 6KRUWHQ SUHVVXUH VZLWFK KRVH 5H URXWH DQG VKRUWHQ SUHVVXUH VZLWFK KRVH 6KRUWHQ UDLQ JXWWHU KRVH...

Страница 16: ...KLV SRVLWLRQ 127 0D UHTXLUH WKH ORQJHU KRVH WKDW LV SURYLGHG ZLWK ZLGHU FDELQHWV 0RYH FRQGHQVDWH GUDLQ KRVH WR WKLV SRVLWLRQ 0D H LW HLWKHU VLGH RI WKH FDELQHW 0RYH UDLQ JXWWHU KRVH WR WKLV SRVLWLRQ K...

Страница 17: ...ciety for Test ing and Materials ASTM standards D1785 Schedule 40 PVC D2665 PVC DWV F891 PVC DWV Cellular Core D2261 ABS DWV or F628 Schedule 40 ABS Pipe cement and primer must conform to ASTM Standar...

Страница 18: ...A 100 000 3 80 100 000 3 60 100 000 4 145 100 000 4 125 Elevation 4001 5000 Elevation 8001 9000 Model Input BTUH Pipe Size in Max Equivalent Length ft Model Input BTUH Pipe Size in Max Equivalent Leng...

Страница 19: ...A Dimension Illustrated in Figure 21 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 in 3 in Sweep 4 1 16 in TABLE 9 Equivalent Length of Fittings Fitting Equivalent Length 2 in 90 sw...

Страница 20: ...as supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with local installation c...

Страница 21: ...ustion air sec tions in these instructions Follow the instructions for outdoor combus tion air or ventilated combustion air and the instructions for installing the vent system with the vent terminatin...

Страница 22: ...imming pool or a location where swimming pool chemicals might be stored Be sure the terminal assembly follows the outdoor clearances listed in Section 1 Outdoor Air Contaminants An unconfined space is...

Страница 23: ...n 12 in 30 5 mm of the bottom of the confined space shall communicate directly or by means of ducts with the outdoors crawl spaces or attic spaces 2 One permanent opening commencing within 12 in 30 5...

Страница 24: ...eing placed into operation could result in carbon monxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while...

Страница 25: ...pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note reading The 2 cubic ft dial provides a more accurate measure...

Страница 26: ...300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 232...

Страница 27: ...ench 3 Turn the electrical and gas supplies back on and with the burners in operation check for gas leakage around the gas valve pressure port using an approved non corrosive gas leak detection fluid...

Страница 28: ...ower speed for each model is shown in Table 17 Use of a heating speed other than the default heating blower speed may result in reduced energy efficiency and higher electric utility bills In certain c...

Страница 29: ...B High 1418 1390 1364 1333 1304 1281 1246 1205 Medium High 1305 1281 1244 1217 1182 1149 1109 1066 Medium 1139 1112 1071 1035 992 951 908 874 Medium Low 1017 986 948 901 859 819 765 727 Low 885 821 76...

Страница 30: ...on air is provided the pressure switch closes and the ignition control provides a 17 second ignitor warm up period The gas valve then opens the gas starts to flow ignition occurs and the flame sensor...

Страница 31: ...Flashes and will enter a one hour soft lockout 5 RED FLASHES This fault is indicated if the normally closed rollout switch opens The rollout control is manually reset Check for proper combustion air...

Страница 32: ...e memory has been cleared and resumes the normal slow green flash after a five second pause SECTION XI REPLACEMENT PARTS LIST DESCRIPTION MOTOR MOTOR DIRECT DRIVE BLOWER BLOWER COMBUSTION ELECTRICAL C...

Страница 33: ...RVICE 5754336 UWD A 0519 Fault Code Retrieval To retrieve fault codes push and release ERROR button on control board The LED will flash the last five error codes beginning with the most recent If ther...

Страница 34: ...5715184 BIM A 0519 34 Johnson Controls Ducted Systems NOTES...

Страница 35: ...Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control board volts AC Thermos...

Страница 36: ...atic in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle...

Отзывы: