YORK INTERNATIONAL
19
FORM 160.60-O1
MICRO PANEL CONTROL CENTER
The Control Center front panel layout consists of five key
groups, one switch, and 1 line by 40 character alphanu-
meric vacuum fluorescent display: (See Fig. 4)
CHARACTER DISPLAY
The alphanumeric vacuum fluo-
rescent display is located to the right of the
STA-
TUS
key. All messages, parameters, setpoints, and data
can be viewed at this location. The main communica-
tions between the operator or service technician and the
MicroComputer Control Center occur on this display.
DISPLAY
Provides a direct read-out of each monitored
parameter on the alphanumeric display.
ENTRY
These keys are used to enter the values for the
operator programmed setpoints. These keys are used in
conjunction with the
SETPOINT
keys while in program
mode.
SETPOINTS
These keys are used as follows:
1. To view each setpoint, in any Mode, or
2. To select the individual setpoints that are programmed
by the operator in
PROGRAM
mode only.
Pressing the appropriate key enables the operator to pro-
gram that setpoint by pressing the
ENTRY
keys.
SERVICE
Included in this group of keys are those func-
tions that are only relevant to servicing the chiller.
Typically, these keys would not be used for daily chiller
operation.
ACCESS CODE
Permits operator to access the
program.
PROGRAM
Permits operator to program the Control
Center.
MODE
Permits operator to check what mode the
Control Center is presently in (
LOCAL
,
REMOTE
or
SERVICE
).
1.
Service
allows manual PRV or engine speed
control with visual display readout of operation.
Also allows manual engine speed control with
visual display readout of engine speed.
2.
Local
allows manual chiller start from the
COM-
PRESSOR
switch on Control Center front.
3.
Program
allows operator programming of system
setpoints.
4.
Remote
allows remote start, remote stop of com-
pressor and remote reset of LCWT and % engine load
limit.
COMPRESSOR
START
,
RUN
,
STOP/RESET
SWITCH
This 3 position rocker switch is used to start
(except in
REMOTE
mode), stop/run/reset the system.
OPERATION
DISPLAYING SYSTEM PARAMETERS
The
DISPLAY
keys are used to display selected moni-
tored parameters as follows: (Refer to Fig. 4)
Press and
release
the appropriate
DISPLAY
key
the message will be displayed for 2 seconds.
- or -
Press and
hold
the appropriate
DISPLAY
key the
message will be displayed and updated every 0.5 sec-
onds until the
DISPLAY
key is released.
- or -
Press and
release
appropriate
DISPLAY
key, then press
and release the
DISPLAY HOLD
key the message
will be displayed and updated every 2 seconds until the
DISPLAY HOLD
key is again pressed and released, or
10 miutes have elapsed, whichever comes first.
NOTE: If the display actually displays Xs, then the moni-
tored parameter is out of normal operating range
(Ref. Fig. 5). If the English/Metric jumper is
installed on the Micro Board, all temperatures
are displayed in degrees Fahrenheit (°F) and all
pressures are displayed in pounds per square
inch gauge (PSIG) except oil pressure which is
displayed in pounds per square inch differential
(PSID). If the English/Metric jumper is not in-
stalled, all temperatures are displayed in degrees
Centigrade (°C) and all pressures are displayed
in Kilo-Pascals (kPa).
OUT OF RANGE VALUES FOR YG & YB CHILLER VARIABLES (R134A)
VARIABLE
DISPLAY -> X’S WHEN,
EVAP PRESSURE (WATER & BRINE)
<= 6.8 PSIG
OR
>= 77.4 PSIG
COND PRESSURE
<= 6.8 PSIG
OR
>= 315.0 PSIG
HOP TRANSDUCER PRESSURE
>= 315.0 PSIG
LOP TRANSDUCER PRESSURE
>= 315.0 PSIG
DISCHARGE TEMPERATURE
<= 20.3°F
OR
>= 226.4°F
OIL TEMPERATURE
<= 20.3°F
OR
>= 226.4°F
LEAVING COND WATER TEMP.
<= 8.4°F
OR
>= 134.1°F
ENTERING COND WATER TEMP.
<= 8.4°F
OR
>= 134.1°F
LEAVING CHILLED WATER TEMP.
>= 81.1°F
ENTERING CHILLED WATER TEMP.
<= 0.1°F
OR
>= 93.0°F
FIG. 5
SYSTEM PARAMETERS OUT OF RANGE
READINGS (Also see page 51)
S
E
C
T
2