Subject: Recommended Operating Guidelines for YCAL Chillers
LITERATURE SUPPLEMENT
Form No.: 150.62-NM2 (LS2)
File with: 150.62-NM2 (699)
201
GENERAL
By observing a few recommended operating guidelines, compressor cycling can be reduced and optimum chilled
liquid temperature control can be achieved when operating YCAL chillers in both water and brine systems.
MINIMUM WATER VOLUME
Minimum water volume in the chilled water system should be 5.0 gallons per ton. Chilled liquid volumes below
this minimum will definitely suffer from chilled liquid temperature control problems and compressor cycling.
Chilled liquid volumes in the range of 7-11 gallons/ton are generally recommended as the industry standard and
will provide the best chilled liquid temperature control with minimum compressor cycling.
MINIMUM LEAVING CHILLED LIQUID CONTROL RANGE PROGRAM SETTINGS
For optimum chilled liquid temperature control, and reduced compressor cycling, leaving chilled liquid setpoint
control range settings should be equal to or greater than the minimum ranges specified in the Table 1 below.
These recommended settings vary according to the number of compressors in the chiller and the chilled liquid
differential actually measured across the evaporator when the chiller is fully loaded. Typically, chilled liquid
system designs utilize an evaporator temperature differential design of 10 ºF, but measurements should be made
to assure that the chiller flows meet design and if not, the minimum control range may need to be varied
accordingly. Use the table below for programming the control range when “leaving” chilled liquid control is
selected.
Recommended Programmed Leaving Chilled Liquid Setpoint
Control Range
Number of
Compressors In
the Chiller
5
º
F Evap Diff
10
º
F Evap Diff
15
º
F Evap Diff
2
± 2.0
º
F
± 2.2
º
F
± 2.5
º
F
3
± 1.8
º
F
± 2.0
º
F
± 2.5
º
F
4
± 1.4
º
F
± 1.8
º
F
± 2.5
º
F
6
± 1.4
º
F
± 1.4
º
F
± 1.8
º
F
TABLE 1 - MINIMUM SETPOINT RANGES
Содержание MILLENNIUM YCAL0043SC
Страница 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Страница 108: ...YORK INTERNATIONAL 108 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC LD03532 FIG 12 ELEMENTARY DIAGRAM ...
Страница 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Страница 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Страница 111: ...YORK INTERNATIONAL 111 FORM 150 62 NM2 FIG 13 ELEMENTARY DIAGRAM Cont d LD03533 ELEMENTARY DIAGRAM YCAL0107SC ...
Страница 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Страница 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Страница 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Страница 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Страница 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Страница 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Страница 124: ...YORK INTERNATIONAL 124 APPENDIX 1 DIMENSIONS FIG 19 TYPE CP 1 FIG 20 TYPE CP 2 LD03839 LD03840 ...
Страница 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Страница 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Страница 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...