YORK INTERNATIONAL
100
PROBLEM
CAUSE
SOL
“LOW SUCTION PRESSURE”
4. TXV defective.
4. Replace TXV.
FAULT (CONT’D)
5. Reduced flow of chilled
5. Check GPM (See “Limitations”
liquid through the cooler.
in Installation section). Check
operation of pump, clean
pump strainer, purge chilled
liquid system of air.
6. Defective suction pressure
6. Replace transducer/low
transducer/low pressure
pressure switch or faulty
switch or wiring
wiring. Refer to “Service”
section for pressure/voltage
formula.
7. LLSV defective
7. Replace LLSV
“HIGH DISCHARGE
1. Condenser fans not operating
1. Check fan motor, fuses,
PRESSURE” FAULT
or operating backwards.
and contactors. Assure fan
blows air upward.
2. Too much refrigerant.
2. Remove refrigerant.
3. Air in refrigerant system.
3. Evacuate and recharge
system.
4. Defective discharge
4. Replace discharge pressure
pressure transducer.
transducer. Refer to Service
section for pressure/voltage
formula.
“LOW LIQUID TEMP”
1. Improperly adjusted leaving
1. Re-program the leaving
FAULT
chilled liquid temp cut-out
chilled liquid temp. cut-out.
(glysol only).
2. Micropanel setpoint/range
2. Re-adjust setpoint/range.
values improperly programmed.
3. Chilled liquid flow too low.
3. Increase chilled liquid flow –
refer to Limitations in Instal-
lation section.
4. Defective LWT or RWT sensor.
4. Compare sensor against a
(assure the sensor is properly
known good temperature
installed in the bottom of the well
sensing device. Refer to
with a generous amount of heat
Service section for temp/
conductive compound)
voltage table.
CONT’D
Control Service and Troubleshooting
Содержание MILLENNIUM YCAL0043SC
Страница 106: ...YORK INTERNATIONAL 106 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC FIG 11 ELEMENTARY DIAGRAM ...
Страница 108: ...YORK INTERNATIONAL 108 ELEMENTARY DIAGRAM YCAL0043SC YCAL0087SC LD03532 FIG 12 ELEMENTARY DIAGRAM ...
Страница 109: ...YORK INTERNATIONAL 109 FORM 150 62 NM2 This page intentionally left blank ...
Страница 110: ...YORK INTERNATIONAL 110 ELEMENTARY DIAGRAM YCAL0107SC FIG 13 ELEMENTARY DIAGRAM ...
Страница 111: ...YORK INTERNATIONAL 111 FORM 150 62 NM2 FIG 13 ELEMENTARY DIAGRAM Cont d LD03533 ELEMENTARY DIAGRAM YCAL0107SC ...
Страница 112: ...YORK INTERNATIONAL 112 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0107SC LD03534 ...
Страница 113: ...YORK INTERNATIONAL 113 FORM 150 62 NM2 This page intentionally left blank ...
Страница 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 15 ELEMENTARY DIAGRAM ...
Страница 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0117SC YCAL0173SC FIG 16 ELEMENTARY DIAGRAM ...
Страница 118: ...YORK INTERNATIONAL 118 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 17 ELEMENTARY DIAGRAM ...
Страница 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0197SC YCAL0253SC FIG 18 ELEMENTARY DIAGRAM ...
Страница 124: ...YORK INTERNATIONAL 124 APPENDIX 1 DIMENSIONS FIG 19 TYPE CP 1 FIG 20 TYPE CP 2 LD03839 LD03840 ...
Страница 129: ...YORK INTERNATIONAL 129 FORM 150 62 NM2 This page intentionally left blank ...
Страница 130: ...YORK INTERNATIONAL 130 This page intentionally left blank ...
Страница 131: ...YORK INTERNATIONAL 131 FORM 150 62 NM2 This page intentionally left blank ...