102777-YIM-E-0206
10
Unitary Products Group
TABLE 3: GAS APPLICATION DATA
INPUT CAPACITY (MBH)
AVAILABLE
ON
MODELS
GAS
RATE
1
(FT.3/HR.)
TEMP. RISE °F
AT FULL INPUT
2
3
0 TO 2,000 FEET ABOVE
SEA LEVEL
3,000 FEET ABOVE
SEA LEVEL
4
4,000 FEET ABOVE
SEA LEVEL
4
MAX.
MIN.
MAX.
MIN.
MAX.
MIN.
MIN.
MAX.
233
233
205
205
196
196
Y22, Y23,
Y24
217
5
35
466
233
410
205
392
196
Y22, Y23,
Y24
434
15
45
699
5
233
615
205
587
196
Y24
650
20
50
1.
Based on maximum input and 1075 Btu/Ft.
3
2.
The air flow must be adjusted to obtain a temperature rise within the range shown.
3.
On VAV units, individual room damper boxes must go full open in heating mode to ensure airflow falls within temperature rise
range.
4.
For operation at elevations above 2,000 feet and, in the absence of specific recommendations from local authority having jurisdic-
tion, equipment ratings shall be reduced at the rate of 4% for each 1,000 feet above sea level.
5.
Minimum heating CFM for 699 MBH input heat is 11,700 CFM.
If a unit is to be installed on a roof curb other than
a YORK roof curb, gasketing must be applied to all
surfaces that come in contact with the unit under-
side.
If a unit is to be installed on an angle iron frame it
is recommended that it be sized to allow the bot-
tom rail to overhang to facilitate installation of con-
densate drains (see Fig. 4).
FIGURE 2 -
TYPICAL RIGGING
CABLES
SPREADER BARS
(3 PLACES)
20"
A
B
C
UNIT
UNIT
WEIGHT
(LB)
LIFTING LUG DIMENSIONS
A
B
C
25 TON
30 TON
40 TON
SEE NOTE 5
SEE NOTE 5
SEE NOTE 5
8' 4"
8' 4"
8' 4"
6' 9"
6' 9"
6' 9"
2' 3"
2' 3"
2' 3"
RIGGING:
1) RIG WITH 6 CABLES, THREE SPREADER BARS - 95" ACROSS WIDTH AND
SPREADER BARS OF LENGTH EQUAL TO "A + B".
2) CENTER OF GRAVITY INCLUDES ECONOMIZER, POWER EXHAUST AND
INLET GUIDE VANES.
3) CAUTION: ALL PANELS MUST BE SECURED IN PLACE WHEN THE UNIT
IS LIFTED.
4) CAUTION: THE CONDENSER COIL SHOULD BE PROTECTED FROM DAMAGE BY
THE RIGGING CABLES WITH PLYWOOD OR OTHER SUITABLE MATERIALS.
5) REFER TO INSTALLATION INSTRUCTIONS.
NOTICE TO RIGGERS
Содержание MILLENNIUM Y22
Страница 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Страница 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Страница 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Страница 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Страница 62: ...102777 YIM E 0206 62 Unitary Products Group FIGURE 25 POWER EXHAUST TWO FORWARD CURVED FANS 30 40 TONS ...
Страница 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Страница 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Страница 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Страница 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Страница 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Страница 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Страница 138: ...102777 YIM E 0206 138 Unitary Products Group FIGURE 62 PRESSURE DROP DRY EVAPORATOR COIL VS SUPPLY AIR CFM 30 40 TON ...
Страница 139: ...102777 YIM E 0206 Unitary Products Group 139 ...