Unit Capacity

Total cooling capacity can be detemined by using correc-
tion factors C1, C2 and C3.
Given cooling capacity = Cooling capacity at standard
rating conditions x C1 x C2 x C3.
      C1 = Capacity correction factor for tempetature
      C2 = Capacity correction for piping length

      C3 = Capacity correction for indoor unit fan speed

Capacity correction factor for temperature

Capacity correction factor for indoor fan speed (C3)

Fan speed

Correction factor C3

Indoor unit

High

1

Medium

0.90

Low

0.75

Indoor unit

10

0.98

7.5

1.00

Piping length (m)

Correction factor C2

Capacity correction factor for piping length (C2)

Operating temperature limits

Cooling mode

Heating mode

Maximum

+ 25°C

(heat pump mode)

+ 46°C

Minimum

+ 21°C

(-5 with low ambiant kit)

- 8°C

Inlet air wet bulb temperature,indoor unit (CWB)

10

15

20

25

30

35

20

25

30

35

40

Air intake dry bulb temperature, outdoor unit (CDB)

Capacity correction factor C1

Operating temperature range

110 %

100 %

90 %

85 %

120 %

R.C.

45

1 0

R.C. = Standard rating condition : Indoor 27°C DB / 19.5°C  WB
                                                     Outdoor 35°C DB / 24°C WB

INDOOR UNIT INSTALLATION ACCESSORIES

Description

Use

Description

Use

Q'ty

Q'ty

Bracket
(left)

Bracket
(right)

Wall bracket

Tapping screw
(Ø4x20)

Cover plate
(left)

Cover plate
(right)

Tapping screw
(Ø4x10)

Coupler heat insulater (small)

Coupler heat insulater (large)

Nylon fastener

Drain hose

Insulation (Drain hose)

VT wire

Hanging bracket for ceiling
installation

Bracket for wall installation

For indoor side pipe joint
(Small pipe)

For indoor side pipe joint
(Large pipe)

For indoor side pipe joint
(Small pipe)

For drain hose

Adhesive type

1

1

2

1

1

2

6

1

1

1

1

1

1

For drain hose
(L 280 mm)

12 - Technical Appendix

13 - Accessories

Содержание MCC

Страница 1: ...MOC MOH MCC MCH MINISPLIT Floor Ceiling TECHNICAL GUIDE Cooling only and Heat Pump Systems Models MCC MOC MCH MOH 09 to 25 Infrared remote control 035 T 700049 001...

Страница 2: ...make sure that the power supply has been disconnected ELECTRICAL CONNECTIONS All electrical wiring and connections must comply with local standards Power supply cord used must not be lighter than Poly...

Страница 3: ...Nominal Current Starting Current Fuse Size Indoor Airflow high speed Indoor unit Outdoor unit V Ph Hz Ph kW A A A m h 09 09 1 0 99 4 6 21 10 490 12 12 1 1 30 6 1 28 10 580 18 18 1 1 89 8 7 43 16 700...

Страница 4: ...clearances A minimium of clearance is necessary around the units to ensure proper air circulation and easy access for maintenance Clearance required for indoor units Clearance required for outdoor uni...

Страница 5: ...urely tighten the hex bolts on both sides Disassemble the side panels and the air inlet grill as shown First open the grill then remove the side panel installation screws Slide the panel toward the to...

Страница 6: ...Pa 3 When pump down is finisned wait 15 minutes to detect potential circuit leakage Open service valves on the outdoor unit Note The expansion device is located in the outdoor unit 6 Table 2 Maximum p...

Страница 7: ...point entered on the control SYSTEM OPERATION MODE SELECTION ROOM TEMPERATURE SETTING Press the TEMP button up or down to change the setting to the desired room temperature The setting range is from 1...

Страница 8: ...ityofthebatteries and that they are in good working condition Also make sure that the controlispointeddirectlyattheairconditioningunitwhenyouareusing it that the distance is a maximum of 10 meters and...

Страница 9: ...it 9 The units are designed to operate for long periods of time with a minimum of maintenance However the following operations must be performed regularly RECOMMENDED FREQUENCY MAINTENANCE OPERATIONS...

Страница 10: ...nt kit 8 C Inlet air wet bulb temperature indo or unit CWB 10 15 20 25 30 35 20 25 30 35 40 Air intake dry bulb temperature outdoor unit CDB Capacity correction factor C1 Operating temperature range 1...

Страница 11: ...35 MSC 35 to 55 MSH 35 to 55 MKC 12 to 55 MKH 12 to 55 MAC 18 to 55 MAH 18 to 55 IS IN COMPLIANCE WITH REQUIREMENTS OF MACHINERY DIRECTIVE CEE 89 392 AS MODIFIED WITH DIRECTIVES CEE 91 368 93 44 93 6...

Страница 12: ...the unit into a suitable container using a refrigerant reclaim or recovery unit This refrigerant may then be re used if appropriate or returned to the manufacturer for disposal Under No circumstances...

Отзывы: