Unit Capacity
Total cooling capacity can be detemined by using correc-
tion factors C1, C2 and C3.
Given cooling capacity = Cooling capacity at standard
rating conditions x C1 x C2 x C3.
C1 = Capacity correction factor for tempetature
C2 = Capacity correction for piping length
C3 = Capacity correction for indoor unit fan speed
Capacity correction factor for temperature
Capacity correction factor for indoor fan speed (C3)
Fan speed
Correction factor C3
Indoor unit
High
1
Medium
0.90
Low
0.75
Indoor unit
10
0.98
7.5
1.00
Piping length (m)
Correction factor C2
Capacity correction factor for piping length (C2)
Operating temperature limits
Cooling mode
Heating mode
Maximum
+ 25°C
(heat pump mode)
+ 46°C
Minimum
+ 21°C
(-5 with low ambiant kit)
- 8°C
Inlet air wet bulb temperature,indoor unit (CWB)
10
15
20
25
30
35
20
25
30
35
40
Air intake dry bulb temperature, outdoor unit (CDB)
Capacity correction factor C1
Operating temperature range
110 %
100 %
90 %
85 %
120 %
R.C.
45
1 0
R.C. = Standard rating condition : Indoor 27°C DB / 19.5°C WB
Outdoor 35°C DB / 24°C WB
INDOOR UNIT INSTALLATION ACCESSORIES
Description
Use
Description
Use
Q'ty
Q'ty
Bracket
(left)
Bracket
(right)
Wall bracket
Tapping screw
(Ø4x20)
Cover plate
(left)
Cover plate
(right)
Tapping screw
(Ø4x10)
Coupler heat insulater (small)
Coupler heat insulater (large)
Nylon fastener
Drain hose
Insulation (Drain hose)
VT wire
Hanging bracket for ceiling
installation
Bracket for wall installation
For indoor side pipe joint
(Small pipe)
For indoor side pipe joint
(Large pipe)
For indoor side pipe joint
(Small pipe)
For drain hose
Adhesive type
1
1
2
1
1
2
6
1
1
1
1
1
1
For drain hose
(L 280 mm)
12 - Technical Appendix
13 - Accessories