DESCRIPTION

Evaporator blower units are designed with two distinct mod-
ules to provide maximum application flexibility. The 30 and 40
ton units are shipped as single packages with the blower
module mounted on top of the coil module, The blower mod-
ule can be repositioned in the field to meet almost any instal-
lation requirement. Blower and coil modules for the 50 ton
units are shipped separately to simplify handling. These mod-
ules can be connected in the field with the same flexibility as
the smaller units.

The blower module includes the blower wheels and room for
a field-mounted motor and drive. The coil module includes
direct expansion coils, 1 in. throwaway filters, liquid line sole-
noid valves for both capacity reduction and pumpdown, ther-
mal expansion valves, distributors and a condensate drain
pan.

Every evaporator coil is pressurized with air to 325 psig and
leak tested under water. After the headers are brazed onto
the coil and the coil is installed in the unit, the coil is pressur-
ized with a combination of refrigerant-22 and nitrogen to 150
psig for pressure testing and additional leak testing. After the
coil is evacuated and dehydrated, it is pressurized with a
holding charge of refrigerant-22 for storage and/or shipping.

Steam coils, hot water coils, base sections, suspension hard-
ware, blower motors and drive packages are available as
field-installed accessories to provide additional application
flexibility.

These evaporator blowers, combined with condensing units,
provide  years of quiet, efficient and dependable operation.
These units are manufactured under ISO 9001 Quality  Sys-
tem Certification.

MODULAR DESIGN 

These evaporator blowers can be arranged for a variety of air
discharge patterns in either the horizontal or the vertical posi-
tion.

The above illustration shows three of the common installation
arrangements. Refer to the unit installation instructions for
other possibilities.

Units may be bottom-supported or ceiling-suspended and
can be arranged to meet almost any space or duct require-
ments. Each unit is available with a choice of blower motors,
drive packages and other accessories to make them suitable
for most applications.

FACTORY-MOUNTED COMPONENTS 

PART LOAD OPERATION  These evaporator blowers have
multiple coils with pre-piped distributors, expansion valves
and solenoid valves. Field modifications are not required for
part load operations. Capacity reduction not only provides
economical operation, but also maintains more even temper-
ature and humidity levels in the conditioned space.

EASY SERVICE  Serviceable expansion valves are provided
on every unit. These superior valves are factory-installed to
provide many  years of trouble-free operation. If service is
required, it is not necessary to unbraze any joints.

PUMPDOWN Evaporator blowers include a solenoid valve
for non-recycling pumpdown. When the cooling requirement
in the conditioned space is satisfied, the refrigerant is
pumped into the high side of the system.

ACCESSORIES

BASE SECTIONS (30 and 40 ton only)  Base sections can
used to elevate units above the floor. If desired, outdoor air
may be introduced through these sections by cutting an
access opening to accommodate the outdoor air duct con-
nection. These bases have a durable finish to match the
evaporator blower unit. They may have to be insulated for
certain applications.

SUSPENSION PACKAGES  These accessories can be used
to suspend horizontal units from above without interfering
with access to the unit. They can also be used for elevating a
floor-mounted unit (either horizontal or vertical) to provide
additional height for the installation of a trap at the conden-
sate drain connection. All suspension packages can be used
with vibration isolators.

HOT WATER COILS  Drainable water coils are available for
field installation between the blower and the coil modules of
both horizontal and vertical units. Since their casings match
the dimensions and the finish of the basic units, they become
an integral part of the unit after installation. The coils slide out
of their casings for easy installation. Coils have copper tubes
that have been mechanically expanded into aluminum fins.
Both headers are located on the same end of the coil. Coils
are leak-tested at 325 psig under water and dried before their
connections are capped for storage and shipping.

STEAM COILS (LEU360 only)  A steam coil is available on
the LEU360 for installation between the blower and coil mod-

 FIGURE 1 :  UNIT INSTALLATION

Содержание LEU360

Страница 1: ...ent positions and suspended in various positions The LEU600 can be position in up to 7 different arrangements and suspended also The LEU line will give you the power to condition large amounts of buil...

Страница 2: ...COIL DIMENSIONS 11 7 BASE SECTION DIMENSIONS 11 8 BLOWER CURVE LEU360 15 9 BLOWER CURVE LEU480 17 10 BLOWER CURVE LEU600 19 LIST OF TABLES 1 STATIC RESISTANCES FOR UNIT ACCESSORIES 4 2 UNIT BLOWER MO...

Страница 3: ...ther accessories to make them suitable for most applications FACTORY MOUNTED COMPONENTS PART LOAD OPERATION These evaporator blowers have multiple coils with pre piped distributors expansion valves an...

Страница 4: ...motors have inherent protection except those available for the 50 ton unit Motors for 50 ton units require a starter and overload elements DRIVE PACKAGES Different size pulleys and belts are avail ab...

Страница 5: ...cept the motors for the LEU600 These motors require external protection starter with overloads and periodic lubrication All motors have a solid base TABLE 3 UNIT DRIVE DATA UNIT MODEL DRIVE DATA BELT...

Страница 6: ...DO NOT USE STEAM IN HOT WATER Coils DO NOT OPERATE THE SUPPLY AIR BLOWER ABOVE ITS NOMINAL HP RATING WHEN A UNIT IS EQUIPPED WITH A STEAM COIL ACCESSORY ALTHOUGH THESE COILS ARE SUITABLE OF A MUCH HIG...

Страница 7: ...multiply these values by 2 31 TABLE 8 STEAM COIL CAPACITY1 LEU360 only MBH 2psig2 STEAM COIL MODEL UNIT MODEL CFM DRY BULB TEMPERATURE OF AIR ENTERING COIL F 10 30 50 70 1NF0454 LEU360 8 000 535 483...

Страница 8: ...550 13 TG2Y 799 8 Unitary Products Group FIGURE 2 COIL CIRCUITING LIQUID LINE...

Страница 9: ...LEU360 480 TABLE 10 UNIT DIMENSIONS LEU 360 480 MODEL A B C D E F G H J K M N P LEU360 100 1 8 95 5 8 33 1 4 36 5 8 73 1 4 2 1 2 18 7 8 16 1 2 15 13 16 21 7 8 22 9 16 1 2 1 8 LEU480 103 1 8 98 5 8 40...

Страница 10: ...ER COIL DIMENSIONS TABLE 11 HOT WATER COIL DIMENSIONS COIL MODEL UNIT MODEL DIMENSIONS A B C D E F 1HW0406 LEU360 100 1 8 37 7 8 6 3 4 3 7 8 1 3 8 1 3 8 1HW0407 LEU480 LEU600 103 1 8 45 1 4 6 1 2 4 1...

Страница 11: ...2 2 2 1 2 1 Coils are field installed between the evaporator coil and the blower section of the unit FIGURE 7 BASE SECTION DIMENSIONS TABLE 13 BASE SECTIONS DIMENSIONS1 1 Ventilation air can be broug...

Страница 12: ...GE LBS REFRIGERANT 22 System 1 18 12 14 System 2 12 19 DRAINABLE HOT WATER COIL ACCESSORY Tube copper OD inches 1 2 1 2 1 2 Rows Deep 2 2 2 Fins Aluminum per 1 inch 12 12 8 Face Area feet2 21 2 27 2 2...

Страница 13: ...195 40 60 460V 5 6 7 385 12 30 7 1 2 10 5 245 20 30 10 12 5 320 20 30 480 208 3 60 7 1 2 21 0 135 35 60 10 25 0 175 40 60 230 460 3 60 230V 7 1 2 21 0 150 35 60 10 25 0 195 40 60 460V 7 1 2 10 5 245 2...

Страница 14: ...1 81 9 2 7 9 1 71 10 0 8 6 1000 2 25 7 6 6 6 2 15 8 2 7 1 2 06 8 8 7 6 1 97 9 5 8 2 1 88 10 4 9 0 1 Unit resistance is based on a wet evaporator coil and clean filters 2 Available static pressure in I...

Страница 15: ...550 13 TG2Y 1001 Unitary Products Group 15 FIGURE 8 BLOWER CURVE LEU360...

Страница 16: ...22 6 8 5 9 1 08 7 8 6 7 0 93 8 8 7 6 0 76 9 8 8 4 0 55 10 8 9 3 900 1 76 8 1 7 0 1 64 9 3 8 0 1 50 10 5 9 0 9156 1 84 8 3 7 2 1 72 9 5 8 2 1 58 10 7 9 2 1 Unit resistance is based on a wet evaporator...

Страница 17: ...550 13 TG2Y 1001 Unitary Products Group 17 FIGURE 9 BLOWER CURVE LEU480...

Страница 18: ...2 50 16 0 13 8 9307 2 88 13 5 11 6 2 81 15 3 13 2 1 Unit resistance is based on a wet evaporator coil and clean filters 2 Available static pressure in IWG to overcome the resistance of the duct system...

Страница 19: ...550 13 TG2Y 1001 Unitary Products Group 19 FIGURE 10 BLOWER CURVE LEU600...

Страница 20: ...ide the rigid support required for shipping rigging and years of dependable operation Exterior panels of 18 gauge steel finished with baked enamel to provide a long lasting quality appearance Removabl...